QC0150 Mains Powered Modbus Transmitter
Installation Manual
8.
Meter Validation
To confirm this meter readings will need to be taken at different intervals and entered into the
meter validation page on Realtime-Online(tm).
Check meter validation(Reports>Meter Validation) then pick sensor ID that is fitted
Enter the reading obtained with date and time > Submit
This will need to be done twice as a minimum to allow the Realtime-
online™ software to check the
readings. (the longer the time between reading the better the result). An initial check whilst on site
can be done with a few hours between readings however for full and accurate calibration, ideally 7
days between readings is desirable (48 hours minimum).
Click the two readings entered on the left of the screen and then Compare Readings the system will
then work out and validate the readings being taken are correct.
If the suggested pulse ratio is significatly diferent to the current Pulse Ratio the amend the Pulse
Factor in Sensor setup to help aid in the calibration of the equipment.
The more readings taken over time help prove correct operation.