background image

Optidrive ODE-2 User Guide Revision 3.20 

20 

www.invertekdrives.com 

 

 

6

 

Pa

ra

m

eter

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-44 

PI Reference (Setpoint) Source Select 

Selects the source for the PID Reference / Setpoint 

0 : Digital Preset Setpoint

. P-45 is used 

1 : Analog Input 1 Setpoint 

P-45 

PI Digital Setpoint 

0.0 

100.0 

0.0 

When P-44 = 0, this parameter sets the preset digital reference (setpoint) used for the PI Controller 

P-46 

PI Feedback Source Select 

0 : Analog Input 2

 (Terminal 4) 

1 : Analog Input 1

 (Terminal 6) 

2 : Motor Current

 

3 : DC Bus Voltage

 Scaled 0 – 1000 Volts = 0 – 100% 

4 : Analog 1 – Analog 2

. The value of Analog Input 2 is subtracted from Analog 1 to give a differential signal. The value is limited to 0. 

5 : Largest (Analog 1, Analog 2)

. The largest of the two analog input values is always used for PI feedback 

P-47 

Analog Input 2 Signal Format 

N/A 

N/A 

N/A 

U0-10 



 = 0 to 10 Volt Signal 



 = 0 to 20mA Signal 



 =  4 to 20mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 4 to 20mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 20 to 4mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA 

P-48 

Standby Mode Timer 

0.0 

250.0 

0.0 

When standby mode is enabled, the drive will enter standby mode following a period of operating at minimum speed (P-02) for the 
time set in P-48. When in Standby Mode, the drive display shows 



, and the output to the motor is disabled. 

Standby mode can be disabled by setting P-48 = 0.0 

P-49 

PI Control Wake Up Error Level 

0.0 

100.0 

0.0 

When the drive is operating in PI Control Mode (P-12 = 5 or 6), and Standby Mode is enabled (P-48 > 0.0), P-49 can be used to define 
the PI Error Level (E.g. difference between the setpoint and feedback) for which the drive will remain in Standby Mode. This allows 
the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficiently. 

P-50 

Thermal Overload Value Retention 

0 : Disabled. 
1 : Enabled

. All Optidrives feature electronic thermal overload protection for the connected motor, designed to protect the motor 

against damage. An internal overload accumulator monitors the motor output current over time, and will trip the drive if the usage 
exceeds the thermal limit. When P-50 is disabled, removing the power supply from the drive and re-applying will reset the value of 
the accumulator. When P-50 is enabled, the value is retained during power off. 

 

6.3.

 

Adjusting the Voltage / Frequency (V/f) characteristics 

Volt

age

 

 

The V/f characteristic is defined by several parameters as follows :- 
P-07 : Motor Rated Voltage 
P-09 : Motor Rated Frequency 
The voltage set in parameter P-07 is applied to the motor at the frequency set Under 
normal operating conditions, the voltage is linearly reduced at any point below the 
motor rated frequency to maintain a constant motor torque output as shown by the 
line ‘A’ on the graph. 
By using parameters P-28 and P-29, the voltage to be applied at a particular frequency 
can be directly set by the user, thereby altering the V/F characteristic. 
Reducing the voltage at a particular frequency reduces the current in the motor and 
hence the torque and power, hence this function can be used in fan and pump 
applications where a variable torque output is desired by setting the parameters as 
follows :- 
P-28 = P-07 / 4 
P-29 = P-09 / 2 
This function can also be useful if motor instability is experienced at certain 
frequencies, if this is the case increase or decrease the voltage (P-28) at the speed of 
instability (P-29). 
 
For applications requiring energy saving, typically HVAC and pumping, the energy 
optimiser (P-06) parameter can be enabled.  This automatically reduces the applied 
motor voltage on light load. 

 

Frequency 

Summary of Contents for Optidrive ODE-2-11005-1H01 Series

Page 1: ...ptidrive ODE 2 User Guide Revision 3 20 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Page 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Page 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Page 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Page 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Page 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Page 7: ...ses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power...

Page 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Page 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Page 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Page 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Page 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Page 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Page 14: ...s of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm2 30 12 A...

Page 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Page 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Page 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Page 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Page 19: ...ut Software Protection Enables the internal brake chopper without software protection An external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the anal...

Page 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Page 21: ...y This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain operat...

Page 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Page 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Page 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Page 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Page 26: ...0 75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Page 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Page 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Reviews: