Switched Units: Default functions of the control switches

Switch Position

POT

Notes

Factory Default 

Configuration. 
Run Forward or Reverse  

with speed controlled from 

the Local POT.

Run Reverse

STOP

Run Forward

Sets the output frequency

NOTE

Other functions are possible, please refer to the online documentation for additional information.

Using the Control Terminals

+24 

VDC

DI1

DI2

DI3 

AI2

+10 

VDC

DI4 

AI1

0V

A0

0V

RL1

RL2

No.

Purpose

Function

1

+24VDC 100mA Output

24 VDC Output

2

DI1 Digital Input 1

Function defined  

by P-12 & P-15. 

See below for further info

3

DI2 Digital Input 2

4

DI3 Digital Input 3/AI2 Analog Input 2

5

+10VDC 10mA Output

10 VDC Output for external potentiometer

6

DI4 Digital Input 4/AI1 Analog Input 1

Function defined by P-12 & P-15. Signal format selected by P-16

7

0VDC Common

8

AO Analog Output/Digital Output

Function selected by P-25. See Parameter List

9

0VDC Common

10

RL1 Output Relay

Function defined by P-18. See Parameter List

11

RL2 Output Relay

Connection Example

Factory Default Functions

No.

Description

DI1

0/1

Open : Stop

Closed : Run

DI2

/

Open : Forward Rotation

Closed : Reverse Rotation

DI3

Analog Speed Reference / 

Preset Speed

Open : Speed Reference set by Analog Speed Reference 

Closed : Speed Reference set by Preset Speed 1 (P-20)

AI1

Analog Speed Reference 

Input

Sets the Speed Reference

NOTE

 For Switched units, the internal pot is selected by default in P-16. 

For Non-switched units, an external pot or 0 - 10 V reference may be connected. Other 

signal types may also be used, set P-16 to the correct format.

NOTE

Additional functions are possible, refer to the online documentation for further information.

Motor Thermistor Connection

Where a motor thermistor is to be used, it should be connected as follows:

Control Terminal Strip

Additional Information

Compatible Thermistor: PTC Type, 2.5kΩ trip level.

 

 

Use a setting of P-15 that has Input 3 function as External Trip, 

e.g. P-15 = 3. Refer to online documentation for further details.

 

Set P-47 = “



"

5   CHECK

Summary of Contents for OPTIDRIVE E3 Series

Page 1: ...Quick Start Guide AC Variable Speed Drive IP66 NEMA 4X 0 37kW 22kW 0 5HP 30HP 1 10V 230V Single Phase input 230V 480V 3 Phase input Switched Non switched...

Page 2: ...rrent x 10 2 PREPARE Prepare the Mounting Location The Optidrive must be mounted in a vertical position only Installation should be on a suitable flat flame resistant surface Do not mount flammable ma...

Page 3: ...0 0 1 1 8 33 4 1 31 275 0 10 82 240 0 9 44 4 9 5 20 9 Mounting Clearance Drive Size X Above Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approxim...

Page 4: ...regulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9...

Page 5: ...e side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage pe...

Page 6: ...ommon 10 RL1 Output Relay Function defined by P 18 See Parameter List 1 1 RL2 Output Relay Connection Example Factory Default Functions No Description DI1 0 1 Open Stop Closed Run DI2 Open Forward Rot...

Page 7: ...ress the Navigate key for 1 second The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters Press and hold the Nav...

Page 8: ...7 Motor Rated Voltage Back EMF at rated speed PM BLDC 0 250 500 230 400 V P 08 Motor Rated Current Drive Rating Dependent A P 09 Motor Rated Frequency 10 500 50 60 Hz P 10 Motor Rated Speed 0 30000 0...

Page 9: ...00 s P 25 Analog Output Function Select 0 11 8 Digital Output Mode Logic 1 24V DC Analog Output Mode 0 Drive Enabled Running 1 Drive Healthy 2 At Target Frequency Speed 3 Drive Tripped 4 Output Freque...

Page 10: ...0 10 Unidirectional External 0 10Volt reference pot A 0 20 External 0 20mA signal t 4 20 External 4 20mA signal trip on loss r 4 20 External 4 20mA signal t 20 4 External 20 4mA signal trip on loss r...

Page 11: ...9 2 25 25 8 8 10 5 50 3 4 5 29 2 40 40 8 8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 8 9 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2...

Page 12: ...heatsink 17 Internal memory fault IO 18 4 20mA Signal Lost 19 Internal memory fault DSP 21 Motor PTC thermistor trip 22 Cooling Fan Fault IP66 only 23 Drive internal temperature too high 26 Output Fau...

Reviews: