Par.
Parameter Name
Minimum
Maximum
Default
Units
P2-12
Analog Output 1 Format
-
-
-
-
-
= 0 to10V
-
= 10 to 0V
-
= 0 to 20mA
-
= 20 to 0mA
-
= 4 to 20mA
-
= 20 to 4mA
P2-13
Analog Output 2 Function
0
12
9
-
Digital Output Mode. Logic 1 = +24V DC
0
Drive running
Logic 1 when the Optidrive is enabled (Running).
1
Drive healthy
Logic 1 When no Fault condition exists on the drive.
2
At speed
Logic 1 when the output frequency matches the setpoint frequency.
3
Motor speed > 0
Logic 1 when the motor runs above zero speed.
4
Motor speed >= limit
Logic 1 when the motor speed exceeds the adjustable limit.
5
Motor current >= limit
Logic 1 when the motor current exceeds the adjustable limit.
6
Motor torque >= limit
Logic when the motor torque exceeds the adjustable limit.
7
Analog input 2 >= limit
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit.
NOTE
When using settings 4 – 7, parameters P2-19 and P2-20 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-19, and return to Logic 0 when the signal falls below the
value programmed in P2-20.
Analog Output Mode
8
Motor speed
0 to P1-01.
9
Motor current
0 to 200% of P1-08.
10
Motor torque
0 to 200% of motor rated torque.
11
Motor power
0 to 150% of drive rated power.
12
PID output
Output from the internal PID Controller, 0 – 100%.
P2-14
Analog Output 2 Format
-
-
-
-
-
= 0 to10V
-
= 10 to 0V
-
= 0 to 20mA
-
= 20 to 0mA
-
= 4 to 20mA
-
= 20 to 4mA
9
Extended P
arameters