5.5. Parameter Factory Reset / User Reset
Optidrive ECO provides a feature to allow the user to define their own default parameter set. After commissioning all required
parameters, the user can save these as the default parameters by setting P6-29 = 1. If required, the User Default Parameters may be
cleared by setting P6-29 = 2.
If the user wishes to reload the User Default Parameters from the drive memory, the following procedure is used.
Factory Parameter Reset, TFT and OLED Display :
User Parameter Reset, TFT and OLED Display :
ECO 01 ECO 01 ECO 01 ECO 01 ECO 01 ECO 01
Stop
P-Def
Stop
Stop
U-Def
Stop
15kW 400V 3Ph 50.0Hz
15kW 400V 3Ph P1-08
30.0
3.0 30.0A
15kW 400V 3Ph
Press and hold the Up,
Down, Start and Stop
keys for >2s.
The display shows
P-def. Briefly press the
Stop key.
The display returns to
Stop. All parameters
are reset to Factory
defaults.
Press and hold the Up,
Down and Stop keys
for >2s.
The display shows
U-def. Briefly press
the Stop key.
The display returns to
Stop. All parameters
are reset to Factory
defaults.
5.6. Resetting the Drive Following a Trip
Optidrive ECO has many protection features, designed to protect both the drive and motor from accidental damage. When any of
these protection features are activated, the drive will trip, and display a fault message. The fault messages are listed in section
When a trip occurs, after the cause of the trip has been investigated and rectified, the user can reset the trip in one of the following
ways:
Press the keypad Stop key.
Power off the drive completely, then power on again.
If P1-13 > 0, switch off digital input 1, then back on again.
If P1-12 = 4, reset via the fieldbus interface.
If P1-12 = 6, reset via BACnet.
5.7. Selecting Between Hand and Auto Control
A
Stop
H
Stop
NOTE
The use of the Hand and Auto
buttons can be disabled by adjusting the
setting of P2-39 Parameter Access Lock.
37kW
400V
3Ph
37kW
400V
3Ph
A = Auto
H = Hand
The active control source is shown
on the OLED display. Use the Hand
and Auto buttons on the keypad to
switch between control sources.
Hand mode permits drive control
directly from the drive keypad. Auto
mode control source is configured
with Parameter P1-12 (Control Mode)
5
LED K
eypad and Display Operation