Additional Information for UL Compliance 

Optidrive E3 is designed to meet the UL requirements. For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333 
In order to ensure full compliance, the following must be fully observed. 
 

Input Power Supply Requirements 

Supply Voltage 

110 – 115 RMS Volts for 115 Volt rated units, + /- 10% variation allowed. 115 Volt RMS Maximum 
200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum 

Frequency 

50 – 60Hz + / - 5% Variation 

Short Circuit Capacity 

Voltage Rating 

Min kW (HP) 

Max kW (HP) 

Maximum supply short-circuit current 

115V 

0.37 (0.5) 

0.75 (1) 

100kA rms (AC) 

230V 

0.37 (0.5) 

1.1 (1.5) 

100kA rms (AC) 

All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above 
specified maximum short-circuit Amperes symmetrical with the specified maximum supply voltage when protected 
by Class J fuses. 

Mechanical Installation Requirements 

All Optidrive E3 units are intended for indoor installation within controlled environments which meet the condition limits shown in section 
9.1 
The drive can be operated within an ambient temperature range as stated in section 9.1 
For IP20 units, installation is required in a pollution degree 1 environment 
For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible 

Electrical Installation Requirements 

Incoming power supply connection must be according to sections 4.3 and 4.4 
Suitable Power and motor cables should be selected according to the data shown in section 9.2 and the National Electrical Code or other 
applicable local codes. 
Motor Cable 

75°C Copper must be used 

Power cable connections and tightening torques are shown in sections 3.3 and 0 
Integral Solid Sate short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in 
accordance with the national electrical code and any additional local codes. Ratings are shown in section 9.2 
Transient surge suppression must be installed on the line side of this equipment and shall provide protection for a rated impulse withstand 
voltage peak of 4kV. 
UL Listed ring terminals / lugs must be used for all bus bar and grounding connections 

General Requirements 

Optidrive E3 provides motor overload protection in accordance with the National Electrical Code (US).  

 

Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-50 = 1 

 

Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information shown 
in section 4.6.2 

 

 

Summary of Contents for optidrive E IP20

Page 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Page 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Page 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Page 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Page 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Page 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Page 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Page 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Page 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Page 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Page 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Page 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Page 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Page 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Page 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Page 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Page 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Page 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Page 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Page 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Page 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Page 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Page 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Page 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Page 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Page 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Page 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Page 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Reviews: