INVERTEC optidrive E IP20 User Manual Download Page 16

Optidrive ODE-3 1Ph Output User Guide Revision 1.00 

16 

www.invertekdrives.com 

 

 

6

 

Pa

ra

m

eter

6.

 

Parameters 

6.1.

 

Standard Parameters 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-01 

Maximum Frequency / Speed Limit 

P-02 

500.0 

50.0 (60.0) 

Hz / RPM 

Maximum output frequency or motor speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM 

P-02 

Minimum Frequency / Speed Limit 

0.0 

P-01 

35.0 

Hz / RPM 

Minimum speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM 

P-03 

Acceleration Ramp Time 

0.00 

600.0 

5.0 

Acceleration ramp time from zero Hz / RPM to base frequency (P-09) in seconds. 

P-04 

Deceleration Ramp Time 

0.00 

600.0 

5.0 

Deceleration ramp time from base frequency (P-09) to standstill in seconds. When set to 0.00, the value of P-24 is used. 

P-05 

Stopping Mode / Mains Loss Response 

Selects the stopping mode of the drive, and the behaviour in response to a loss of mains power supply during operation. 

Setting 

On Disable 

On Mains Loss 

Ramp to Stop (P-04) 

Ride Through (Recover energy from load to maintain operation) 

Coast 

Coast 

Ramp to Stop (P-04) 

Fast Ramp to Stop (P-24), Coast if P-24 = 0 

P-06 

Reserved 

P-07 

Motor Rated Voltage 

150 / 250 

115 / 230 

This parameter should be set to the rated (nameplate) voltage of the motor (Volts). 

P-08 

Motor Rated Current 

Drive Rating Dependent 

This parameter should be set to the rated (nameplate) current of the motor 

P-09 

Motor Rated Frequency 

25 

120 

50 (60) 

Hz 

This parameter should be set to the rated (nameplate) frequency of the motor 

P-10 

Motor Rated Speed 

7200 

RPM 

This parameter can optionally be set to the rated (nameplate) RPM of the motor. When set to the default value of zero, all speed 
related parameters are displayed in Hz and the slip compensation (where motor speed is maintained at a constant value regardless 
of applied load) for the motor is disabled. Entering the value from the motor nameplate allows the Optidrive to display motor speed 
in RPM. All speed related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in RPM. 

Note

 If P-09 value is changed, P-10 value is reset to 0 

P-11 

Start Boost Voltage 

0.0 

100.0 

3.0 

This parameter sets the initial voltage applied to the motor following a start command. The inverter applied the voltage set in this 
parameter at the frequency set in P-32 initially, and then ramps to the motor rated voltage set in P-09 over the time period set in P-
33. Excessive voltage boost levels may result in increased motor current and temperature, and can result in the drive tripping during 
starting.  
An explanation of the motor starting, and procedure for optimising the boost voltage is described in section 6.4. 

P-12 

Primary Command Source 

0: Terminal Control

. The drive responds directly to signals applied to the control terminals. 

1: Uni-directional Keypad Control

.  The drive can be controlled in the forward direction only using the internal keypad, or an 

external remote Keypad. 

2: Uni-directional Keypad Control

.  The drive can be controlled in the forward direction only using the internal keypad, or an 

external remote Keypad. 

3: Modbus Network Control. 

Control via Modbus RTU (RS485) using the internal Accel / Decel ramps

 

4 : Modbus Network Control. 

Control via Modbus RTU (RS485) interface with Accel / Decel ramps updated via Modbus

 

5 : PI Control. 

User PI control with external feedback signal

 

6 : PI Analog Summation Control. 

PI control with external feedback signal and summation with analog input 1 

7 : CAN open Control

. Control via CAN (RS485) using the internal Accel / Decel ramps 

8 : CAN open Control

. Control via CAN (RS485) interface with Accel / Decel ramps updated via CAN 

9 : Slave Mode

. Control via a connected Invertek drive in Master Mode. Slave drive address must be > 1. 

NOTE 

When P-12 = 1, 2, 3, 4, 7, 8 or 9, an enable signal must still be provided at the control terminals, digital input 1 

P-13 

Reserved 

P-14 

Extended Menu Access code 

65535 

Enables access to Extended and Advanced Parameter Groups. This parameter must be set to the value programmed in P-37 (default: 
101) to view and adjust Extended Parameters and value of P-37 + 100 to view and adjust Advanced Parameters. The code may be 
changed by the user in P-37 if desired. 

 
 

 

Summary of Contents for optidrive E IP20

Page 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Page 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Page 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Page 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Page 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Page 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Page 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Page 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Page 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Page 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Page 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Page 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Page 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Page 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Page 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Page 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Page 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Page 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Page 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Page 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Page 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Page 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Page 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Page 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Page 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Page 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Page 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Page 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Reviews: