INVERTEC optidrive E IP20 User Manual Download Page 25

 Optidrive ODE-3 1Ph Output User Guide Revision 1.00 

 

www.invertekdrives.com 

25

 

 

8

 
M

od
b

u

R

TU Co

m

m

u

n

ic

ati

on

8.

 

Modbus RTU Communications 

8.1.

 

Introduction 

The Optidrive E3 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive. 

8.2.

 

Modbus RTU Specification 

Protocol 

Modbus RTU 

Error check 

CRC 

Baud rate 

9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 

Data format 

1 start bit, 8 data bits, 1 stop bits, no parity. 

Physical signal 

RS 485 (2-wire) 

User interface 

RJ45 

8.3.

 

RJ45 Connector Configuration 

For full MODBUS RTU register map 

information please refer to your Invertek 

Drives Sales Partner. Local contacts can be 

found by visiting our website 

www.invertekdrives.com 

 

When using MODBUS control the Analog and 

Digital Inputs 

can be configured as shown in section 7.5 

 

CAN - 

CAN + 

0 Volts 

-RS485 (PC) 

+RS485 (PC)  

+24 Volt 

-RS485 (Modbus RTU) 

+RS485 (Modbus RTU) 

 

 

 

 

 

 

 

Warning: 

This is not an Ethernet 
connection. Do not connect 
directly to an Ethernet port.

 

 

8.4.

 

Modbus Telegram Structure 

The Optidrive ODE-3 supports Master / Slave Modbus RTU communications, using the 03 Read Holding Registers and 06 Write Single Holding 
Register commands. Many Master devices treat the first Register address as Register 0, therefore it may be necessary to convert the Register 
Numbers detail in section 8.5 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:- 
 

Command 03 – Read Holding Registers 

 

Command 06 – Write Single Holding Register 

Master Telegram 

Length 

 

Slave Response 

Length 

 

Master Telegram 

Length 

 

Slave Response 

Length 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

 

Slave Address 

1  Byte 

Function Code (03) 

1  Byte 

 

Starting Address 

1  Byte 

 

Function Code (06) 

1  Byte 

 

Function Code (06) 

1  Byte 

1

st

 Register Address 

2  Bytes 

 

1

st

 Register Value 

2  Bytes 

 

Register Address 

2  Bytes 

 

Register Address 

2  Bytes 

No. Of Registers 

2  Bytes 

 

2

nd

 Register Value 

2  Bytes 

 

Value 

2  Bytes 

 

Register Value 

2  Bytes 

CRC Checksum 

2  Bytes 

 

Etc... 

 

 

 

CRC Checksum 

2  Bytes 

 

CRC Checksum 

2  Bytes 

 

 

 

 

CRC Checksum 

2  Bytes 

 

 

 

 

 

 

 

 

8.5.

 

Modbus Register Map 

Register 
Number 

Par. 

Type 

Supported 

Commands 

Function 

Range 

Explanation 

Low Byte 

High Byte 

R/W 

03,06 

Drive Control Command 

0..3 

16 Bit Word.  
Bit 0 : Low = Stop, High = Run Enable 
Bit 1 : Low = Decel Ramp 1 (P-04), High = Decel 
Ramp 2 (P-24) 
Bit 2 : Low = No Function, High = Fault Reset 
Bit 3 : Low – No Function, High = Coast Stop 
Request 

R/W 

03,06 

Modbus Speed reference setpoint 

0..1200 

Setpoint frequency x10, e.g. 100 = 10.0Hz 

R/W 

03,06 

Acceleration and Deceleration Time 

0..60000 

Ramp time in seconds x 100, e.g. 250 = 2.5 seconds 

03 

Error code 

Drive status 

 

Low Byte = Drive Error Code, see section 10.1 
High Byte = Drive Status as follows :- 
0 : Drive Stopped 
1: Drive Running 
2: Drive Tripped 

 

03 

Output Motor Frequency 

 

Output frequency in Hz x10, e.g. 100 = 10.0Hz 

 

03 

Output Motor Current 

 

Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps 

11 

03 

Digital input status 

0..15 

Indicates the status of the 4 digital inputs 
Lowest Bit = 1 Input 1 

20 

P00-01 

03 

Analog Input 1 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

21 

P00-02 

03 

Analog Input 2 value 

0..1000 

Analog input % of full scale x10, e.g. 1000 = 100% 

22 

P00-03 

03 

Speed Reference Value 

0..1000 

Displays the setpoint frequency x10, e.g. 100 = 10.0Hz 

23 

P00-08 

03 

DC bus voltage 

0..1000 

DC Bus Voltage in Volts 

24 

P00-09 

03 

Drive temperature 

0..100 

Drive heatsink temperature in ºC 

All user configurable parameters are accessible as Holding Registers, and can be Read from or Written to using the appropriate Modbus 
command. The Register number for each parameter P-04 to P-60 is defined as 128 + Parameter number, e.g. for parameter P-15, the register 
number is 128 + 15 = 143. Internal scaling is used on some parameters, for further details, please contact your Invertek Drives Sales Partner. 
 
 

 

Bardac

www.bardac.com

Bardac

Summary of Contents for optidrive E IP20

Page 1: ...h Output User Guide Revision 1 00 www invertekdrives com 1 1 Quick Start Up User Guide Single Phase Output IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 1 1kW 0 5 1 5HP 110 230V Installation and Oper...

Page 2: ...ection Diagram 13 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 14 4 10 Control Terminal Connections 14 5 Operation 15 5 1 Managing the Keypad 15 5 2 Changing Parameters 15 5 3 Read On...

Page 3: ...h EMC standards is dependent on a number of factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted Compliance...

Page 4: ...t which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work...

Page 5: ...4X Enclosed Units Guidelines for mounting IP66 Units 8 8 8 9 5 Select the correct power and motor cables according to local wiring regulations or code noting the maximum permissible sizes 9 2 Rating T...

Page 6: ...to Start Open to Stop Connect a potentiometer 5k 10k between terminals as shown to vary the speed from P 2 0Hz default to P 01 50 60 Hz default 0 10V 0 50 60Hz Quick Start IP66 Switched Switch the uni...

Page 7: ...c Brake Transistor 1 Not Fitted 4 Internal Transistor Frame Size Filter Type 0 No Filter F Internal EMC Filter Input Voltage 1 110 115 2 200 240 No Of Input Phases Output Current x 10 2 2 Drive Model...

Page 8: ...environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution deg...

Page 9: ...t be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should be sufficient to support t...

Page 10: ...conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On t...

Page 11: ...der joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to on...

Page 12: ...mains supply for motors which have been wound for operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor...

Page 13: ...ons A Incoming Power Supply B External Isolator Disconnect C External MCB or Fuse D Optional Input Choke E Optional Input Filter F Optional Brake Resistor G Shielded Motor Cable H Analog Digital Outpu...

Page 14: ...d 1 STOP Run PI Control 5 6 0 Selectable PI control or preset speed Run Pot STOP Run PI Control 5 6 0 Selectable PI control or Pot speed control Enable STOP Enable 7 8 0 Control from CAN interface Run...

Page 15: ...Read Only Parameter Access 5 4 Resetting Parameters Press and hold the Navigate key 2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings pre...

Page 16: ...um Speed Preset Speeds etc will also be displayed in RPM Note If P 09 value is changed P 10 value is reset to 0 P 11 Start Boost Voltage 0 0 100 0 3 0 This parameter sets the initial voltage applied t...

Page 17: ...mit set in P 19 9 Drive Ready to Run Logic 1 when the drive is ready to run no trip present P 19 Relay Threshold Level 0 0 200 0 100 0 Adjustable threshold level used in conjunction with settings 4 to...

Page 18: ...inal Enable 3 Previous Speed Terminal Enable 4 Current Speed Keypad Start 5 Preset Speed 4 Keypad Start 6 Current Speed Terminal Start 7 Preset Speed 4 Terminal Start P 32 Starting Boost Frequency 0 0...

Page 19: ...for the PID Reference Setpoint 0 Digital Preset Setpoint P 45 is used 1 Analog Input 1 Setpoint Analog input 1 signal level readable in P00 01 is used for the setpoint P 45 PI Digital Setpoint 0 0 10...

Page 20: ...process data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of...

Page 21: ...Set the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the mot...

Page 22: ...reference selected according to other digital input status FAST STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which mu...

Page 23: ...9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 1 1 STOP ENABLE PI Speed Reference 5 3 STOP ENABLE FB R...

Page 24: ...llowing protection features in the drive O t Heat sink Over Temperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance...

Page 25: ...2 Bytes Register Address 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Che...

Page 26: ...er a 24 hour period for 200 240V 2 2kW and 3HP IP20 drives is 45 C 9 2 Rating Tables Frame Size kW HP Input Current Fuse MCB Type B Maximum Cable Size Output Current Recommended Brake Resistance Non U...

Page 27: ...stated in section 9 1 For IP20 units installation is required in a pollution degree 1 environment For IP66 Nema 4X units installation in a pollution degree 2 environment is permissible Electrical Ins...

Page 28: ...the drive and that the bottom entry and top exit vents are not blocked or obstructed 09 Under temperature Trip occurs when ambient temperature is less than 10 C Temperature must be raised over 10 C i...

Reviews: