![inverSOL Lumen User Manual Download Page 8](http://html.mh-extra.com/html/inversol/lumen/lumen_user-manual_2085043008.webp)
www.inversolpr.com
User Manual Lumen and inverSOL 5000 8
Conduct in Case of a Fire
Fire may occur with electrical equipment despite its careful design. Additionally, a fire in the vicinity
of the equipment can cause the storage system to catch fire, releasing the contents of the battery
modules.
In the event of a fire in the vicinity of the product or in the storage system itself, proceed as follows:
1. Only firefighters with appropriate protective equipment (safety gloves, safety clothing, face guard,
breathing protection) should enter the room where the burning storage system is located.
2. There is a danger of electrocution when extinguishing fire while the storage system is switched on.
1. Switch off the storage system to electrically isolate it (see Switching the storage system off
to electrically isolate it).
2. Switch off the main circuit protection device in the building.
3. If the storage system and/or mains fuses cannot be safely switched off:
1. Observe the minimum distances specified for the extinguishing agent used.
4. The storage system works with an output voltage of 240 V (AC) and is therefore considered a low-
voltage system.
1. A storage system fire can be extinguished using conventional extinguishing agents.
2. Water is recommended as an extinguishing agent in order to cool the battery modules and
prevent thermal runaway in battery modules which are still intact.
Information on the battery modules:
• The battery modules have a nominal voltage of 24 V (DC) and therefore fall into the range of
protected extra-low voltage (under 60 V DC).
• The battery modules in the Lumen is LiNMC
Safety