11. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibrated.(Detection equipment shall
be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source
of ignition and is suitable for the refrigerant used. Leak detection equipment shall be
set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant
employed and the appropriate percentage of gas(25% maximum )is confirmed .
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine shall be avoided as the chlorine may
react with the refrigerant and corrode the copper pipe work.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall
be recovered from the system, or isolated (by means of shut off valves) in a part of the
system both before and during the brazing process.
12. Removal and evacuation
When breaking into the refrigerant circuit to make repairs- or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is
followed since flammability is a consideration. The following procedure shall be adhered
to:
remove refrigerant;
purge the circuit with inert gas;
evacuate;
purge again with inert gas;
open the circuit by cutting or brazing;
The refrigerant charge shall be recovered into the correct recovery cylinders. The system
shall be “flushed’ with OFN to render the unit safe. This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing
to fill until the working pressure is achieved, then venting to atmosphere, and finally
pulling down to a vacuum. This processing shall be repeated until no refrigerant is
within the system. When the final OFN charge is used, the system shall be vented down
to atmospheric pressure to enable work to take place. This operation is absolutely vital
if brazing operations on the pipe-work are to take place. Ensure that the outlet for the
vacuum pump is not close to any ignition sources and there is ventilation available.
13. Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
-Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of
refrigerant contained in them.
-Cylinders shall be kept upright.
-Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
-label the system when charging is complete (if not already)
-Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system is shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak test
shall be carried out prior to leaving the site.
14. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample
Summary of Contents for PWR-50L
Page 1: ...MODEL PWR 50L USER S MANUAL MANUAL UTILIZATORULUI ENGLISH ROMANA DEHUMIDIFIER...
Page 2: ...2...
Page 3: ...3 EN LANGUAGES ENGLISH 3 27 ROMANA 52...
Page 27: ...27 GR Power 1 28 2 31 3 R290 R32 32 4 38 5 40 6 41 7 44 8 46 9 46 10 47...
Page 28: ...28 GR 1 l l...
Page 29: ...29 GR 8...
Page 30: ...30 GR 1 l...
Page 31: ...31 GR l PCB T 3 15A 250V 350V CO2 24 2 l 2002 96 EC 27 2003 l CO2 l A B...
Page 32: ...32 GR 3 R290 R32 4m2 R32 R290 R32 290...
Page 33: ...33 GR R290 R32 1 2 3 4 5 6 1 2 3 4 5 CO2 6...
Page 34: ...34 GR 7 8 9 7...
Page 35: ...35 GR 8 9 10 11 O LFL 25 12...
Page 36: ...36 GR 13 14 80...
Page 37: ...37 GR 15 16...
Page 38: ...38 GR A 4 SN D2002255780115715200209 SN D2002255780115715200209 SN...
Page 39: ...39 GR 1 40cm 2 5 C 5 C 3 4 2 5...
Page 40: ...40 GR 5 4...
Page 43: ...43 GR FILTER FILTER FILTER 250 FILTER...
Page 44: ...44 GR 7 1 P2 P2 2...
Page 45: ...45 GR x...
Page 46: ...46 GR 15 8 l M l 2 9 24...
Page 47: ...47 GR 10 HEPA 45 55...
Page 48: ...48 GR Mode Cont Comfort Cont Comfort 3 l l l l l l l l l l l...
Page 49: ...49 GR l l l l l l l l l l l l AS ES EC EC 3 P2...
Page 50: ...50 GR 211 300 3300 www inventoraircondition gr media library...
Page 76: ...DEHUMIDIFIER v 1 0...