11
EN
period that the work is carried out. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and
to the correct specification. At all times the manufacturer’s maintenance and service
guidelines shall be followed. If in doubt consult the manufacturer’s technical department
for assistance.
The following check shall be applied to installations using flammable refrigerants:
--the charge size is in accordance with the room size within which the refrigerant
containing parts are installed;
--the ventilation machinery and outlets are operating adequately and are not obstructed;
9. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then
no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If
the fault cannot be corrected immediately but it is necessary to continue operation, an
adequate temporary solution shall be used . This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
--that capacitors are discharged; this shall be done in a safe manner to avoid possibility of
sparking;
--that there no live electrical components and wring are exposed while charging,
recovering or purging the system;
--that there is continuity of earth bonding.
7. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed covers, etc. If it is
absolutely necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical point to
warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working in electrical
components, the casing is not altered in such a way that level of protection is affected.
This shall include damage to cables, excessive numble of connection, terminals not made
to original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that seals or sealing materials have not degraded such that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts
shall be in accordance with the manufacturer’s specifications,
NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to
working on them.
8. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for the
equipment in use.
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual leaks. A halide torch (or any other detector using
a naked flame) shall not be used
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
Summary of Contents for PWR-50L
Page 1: ...MODEL PWR 50L USER S MANUAL MANUAL UTILIZATORULUI ENGLISH ROMANA DEHUMIDIFIER...
Page 2: ...2...
Page 3: ...3 EN LANGUAGES ENGLISH 3 27 ROMANA 52...
Page 27: ...27 GR Power 1 28 2 31 3 R290 R32 32 4 38 5 40 6 41 7 44 8 46 9 46 10 47...
Page 28: ...28 GR 1 l l...
Page 29: ...29 GR 8...
Page 30: ...30 GR 1 l...
Page 31: ...31 GR l PCB T 3 15A 250V 350V CO2 24 2 l 2002 96 EC 27 2003 l CO2 l A B...
Page 32: ...32 GR 3 R290 R32 4m2 R32 R290 R32 290...
Page 33: ...33 GR R290 R32 1 2 3 4 5 6 1 2 3 4 5 CO2 6...
Page 34: ...34 GR 7 8 9 7...
Page 35: ...35 GR 8 9 10 11 O LFL 25 12...
Page 36: ...36 GR 13 14 80...
Page 37: ...37 GR 15 16...
Page 38: ...38 GR A 4 SN D2002255780115715200209 SN D2002255780115715200209 SN...
Page 39: ...39 GR 1 40cm 2 5 C 5 C 3 4 2 5...
Page 40: ...40 GR 5 4...
Page 43: ...43 GR FILTER FILTER FILTER 250 FILTER...
Page 44: ...44 GR 7 1 P2 P2 2...
Page 45: ...45 GR x...
Page 46: ...46 GR 15 8 l M l 2 9 24...
Page 47: ...47 GR 10 HEPA 45 55...
Page 48: ...48 GR Mode Cont Comfort Cont Comfort 3 l l l l l l l l l l l...
Page 49: ...49 GR l l l l l l l l l l l l AS ES EC EC 3 P2...
Page 50: ...50 GR 211 300 3300 www inventoraircondition gr media library...
Page 76: ...DEHUMIDIFIER v 1 0...