Page 28
Instructions for Connecting Piping
to Outdoor Unit
1.
Unscrew the cover from the packed valve on
the side of the outdoor unit. (See
Fig. 5.9
)
2.
Remove protective caps from ends of valves.
3.
Align flared pipe end with each valve, and
tighten the flare nut as tightly as possible by
hand.
4.
Using a spanner, grip the body of the valve.
Do not grip the nut that seals the service
valve. (See
Fig. 5.10
)
USE SPANNER TO GRIP MAIN
BODY OF VALVE
Torque from tightening the flare nut can snap
off other parts of valve.
5.
While firmly gripping the body of the valve,
use a torque wrench to tighten the flare nut
according to the correct torque values.
6.
Loosen the flaring nut slightly, then tighten
again.
7.
Repeat Steps 3 to 6 for the remaining pipe.
Fig. 5.9
Fig. 5.10
Valve cove
Page 29
Air Evacuation
7
Preparations and Precautions
Air and foreign matter in the refrigerant circuit
can cause abnormal rises in pressure, which
can damage the air conditioner, reduce its
efficiency, and cause injury. Use a vacuum pump
and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and
moisture from the system.
Evacuation should be performed upon initial
installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
o
Check to make sure that both high-
pressure and low-pressure pipes between
the indoor and outdoor units are
connected properly in accordance with the
Refrigerant Piping Connection section of
this manual.
o
Check to make sure all wiring is connected
properly.
Evacuation Instructions
Before using the manifold gauge and vacuum
pump, read their operation manuals to familiarize
yourself with how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure
valve
Pressure hose /
Charge hose
Charge hose
Vacuum
pump
Pressure gauge
Low pressure valve
1.
Connect the charge hose of the manifold
gauge to service port on the outdoor unit’s
low pressure valve.
2.
Connect another charge hose from the
manifold gauge to the vacuum pump.
MC
MC
Fig. 6.1
3.
Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
4.
Turn on the vacuum pump to evacuate the
system.
5.
Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-10 Pa).
5
Summary of Contents for P9MVI32-09WiFi
Page 41: ......
Page 43: ...25 29 6 7 8 9 10 34 11 MC MC R32 R290 31 32 34 1 29 2 30 25 B 25 1 25 2 26 3 26 4 27...
Page 44: ...4 Page 4 1 2 C C C 3 4 5 6 7 8 9 10 7 10 R32 R290...
Page 45: ...5 Page 5 11 12 13 14 15 16 8 1 3 1 2 3 4 1 2 3 4 12 5...
Page 46: ...6 1 1 1 1 5 5 2 1 2 Page 6 ST3 9 X 25 M LR03 ST2 9 x 10...
Page 48: ...8 8 11 12 12 12 1 2 3 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in 2...
Page 49: ...9 9 STEP 8 1 2 3 5 6 7 8 9 25 17 19 16 19...
Page 51: ...11 Page 11 4 Fig 3 1 a 1 o o o o o o 1 c c c...
Page 55: ...15 Page 15 Fig 3 6 Fig 3 7 Fig 3 8 3 3 15cm 6in 2 3 4 5 6 7 1 2 3 8 3 6 3 7 3 8...
Page 59: ...19 Page 19 Fig 3 14 7 1 3 14 2 3 3 14 8 1 4 2 3 4 5 6 7 3 14...
Page 61: ...21 Page 21 A B Fig 4 2 Fig 4 3 Fig 4 4 90 4 2 4 3 4 4 1 2 3 90 4 4 4 1 2 4 3 4 2 4 4 2...
Page 63: ...23 Page 23 1 2 3 4 5 6 7 8 4 1 2 3 4 90 100 5 1 5 6 1 8in 3mm 7 8 9 10 11 1 40in...
Page 68: ...28 Page 28 Fig 5 9 Fig 5 10 5 6 7 3 6 5 9 5 10 1 5 9 2 3 4...
Page 69: ...29 Page 29 7 76cmHg MC MC Fig 6 1 o o 1 2 3 4 5 15 76cmHG 105Pa 6 1...
Page 71: ...31 Page 31 8 4...
Page 72: ...32 Page 32 9 30 1 2 ON OFF 3 MODE 4 5 2 2...
Page 74: ...34 Page 34 10...
Page 75: ...35 Page 35 11 R32 R290 1 2 3 4 5 6 7 8 l...
Page 76: ...36 l l l l O 9 l l 10 10 1 10 2 l l...
Page 77: ...37 11 12 13 14 LFL 25 OFN 15 l l l l l OFN OFN...
Page 78: ...38 OFN 16 l l l l l l OFN 17 l l l l 80...
Page 79: ...39 18 19 l l l l l l l 20 1 2 3 4 5...
Page 118: ...NOTES...
Page 119: ......