Outdoor Unit Installation

5

ev

ob

a )

ni

42(

 

mc

06

60cm (24in) 

on righ

t

30cm (12in) 

on left

200cm (79in) 

in fron

t

30cm (12in) 

from back wall

Installation Instructions 

– Outdoor Unit 

Step 1: Select installation location

Before installing the outdoor unit, you must 

choose an appropriate location. The following 

are standards that will help you choose an 

appropriate location for the unit.

Proper installation locations meet the 

following standards:

o

 

Meets all spatial requirements shown in 

Installation Space Requirements (

Fig. 4.1

)

o

 

Good air circulation and ventilation

o

 

Firm and solid—the location can support the 

unit and will not vibrate

o

 

Noise from the unit will not disturb others 

o

 

Protected from prolonged periods of direct 

sunlight or rain

 

DO NOT

 install unit in the following locations:

 

Near an obstacle that will block air inlets 

and outlets

 

Near a public street, crowded areas, or 

where noise from the unit will disturb others 

 

Near animals or plants that will be harmed 

by hot air discharge

 

Near any source of combustible gas

 

In a location that is exposed to large 

amounts of dust

 

In a location exposed to a excessive amounts 

of salty air

Fig. 4.1

Summary of Contents for P9MVI32-09WiFi

Page 1: ...ALLATION MANUAL MANUAL DE INSTALARE ENGLISH ROMANA MODELS P9MVI32 09WiFi P9MVO32 09 P9MVI32 12WiFi P9MVO32 12 P9MVI32 18WiFi P9MVO32 18 P9MVI32 24WiFi P9MVO32 24 WALL MOUNTED UNIT AIR CONDITIONING SYS...

Page 2: ...4 Prepare refrigerant piping 14 5 Connect drain hose 15 6 Connect signal cable 17 7 Wrap piping and cables 18 8 Mount indoor unit 18 Outdoor Unit Installation 20 8 1 Select installation location 20 2...

Page 3: ...25 2 Remove burrs 26 3 Flare pipe ends 26 4 Connect pipes 27 Air Evacuation 29 1 Evacuation Instructions 29 2 Note on Adding Refrigerant 30 Electrical and Gas Leak Checks 31 Test Run 32 European Disp...

Page 4: ...e electrical shock or fire 2 Installation must be performed according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installat...

Page 5: ...the unit it may cause fire Do not operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit 1 The produc...

Page 6: ...0 Remote controller holder Dry battery AAA LR03 Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation parts and acc...

Page 7: ...that space is smaller than 4m2 For R290 refrigerant models the minimum room size needed 9000Btu h units 13m 9000Btu h and 12000Btu h units 17m 12000Btu h and 18000Btu h units 26m 18000Btu h and 24000B...

Page 8: ...llation Summary Indoor Unit 2 Select Installation Location Page 11 Attach Mounting Plate Page 12 Drill Wall Hole Page 12 Determine Wall Hole Position Page 12 1 2 3 4 12cm 4 75in 2 3m 90 55in 12cm 4 75...

Page 9: ...Page 9 Mount Indoor Unit Page 19 STEP8 Wrap Piping and Cable not applicable for some locations in the US Page 19 Connect Piping Page 25 Connect Wiring Page 17 Prepare Drain Hose Page 16 5 6 7 8 9...

Page 10: ...ed in accordance with the requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal...

Page 11: ...ill not vibrate o Strong enough to support the weight of the unit o A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the following locations...

Page 12: ...all by tightening the screws directly into the clip anchors Step 3 Drill wall hole for connective piping You must drill a hole in the wall for refrigerant piping the drainage pipe and the signal cable...

Page 13: ...43 5in 599mm 23 6in 342mm 13 5in Model C 964mm 37 9in 482mm 19in 325mm 12 8in 406 4mm 16in 452 7mm 17 8in 249mm 9 8in 153mm 6in 102mm 4in 39mm 1 5in pipe hole 65mm 2 56 in pipe hole 65mm 2 56 in pipe...

Page 14: ...g while bending them away from the unit Any dents in the piping will affect the unit s performance Step 4 Prepare refrigerant piping The refrigerant piping is inside an insulating sleeve attached to t...

Page 15: ...ition of the wall hole relative to the mounting plate choose the side from which the piping will exit the unit 2 If the wall hole is behind the unit keep the knock out panel in place If the wall hole...

Page 16: ...of drain hose 3 Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks 4 For the portion of the drain hose that will remain indoors wrap it with foam pipe insula...

Page 17: ...properly ground the air conditioner 9 Every wire must be firmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire 10 Do not let wires touch...

Page 18: ...e box cover to connect the cable WARNING 4 Unscrew the cable clamp below the terminal block and place it to the side 5 Facing the back of the unit remove the plastic panel on the bottom left hand side...

Page 19: ...P ENDS OF PIPING When wrapping the bundle keep the ends of the piping unwrapped You need to access them to test for leaks at the end of the installation process refer to Electrical Checks and Leak Che...

Page 20: ...ts shown in Installation Space Requirements Fig 4 1 o Good air circulation and ventilation o Firm and solid the location can support the unit and will not vibrate o Noise from the unit will not distur...

Page 21: ...on the type of outdoor unit If the drain joint comes with a rubber seal see Fig 4 4 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit 2 Inse...

Page 22: ...en their mounting feet Prepare the installation base of the unit according to the dimensions below A W B D Air inlet Air outlet Air inlet A W B D Air inlet Air outlet Air inlet Fig 4 5 WHEN DRILLING I...

Page 23: ...national electrical codes and must be installed by a licensed electrician 2 All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the ind...

Page 24: ...cable clamp below the terminal block and place it to the side 4 Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding termina...

Page 25: ...1 Maximum Length and Drop Height of Refrigerant Piping per Unit Model Model Capacity BTU h Max Length m Max Drop Height m R410A Inverter Split Air Conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000...

Page 26: ...ds with PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right direction...

Page 27: ...that you will connect SeeFig 5 7 Indoor unit tubing Flare nut Pipe 2 Tighten the flare nut as tightly as possible by hand 3 Using a spanner grip the nut on the unit tubing 4 While firmly gripping the...

Page 28: ...y hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNE R TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut can snap...

Page 29: ...Piping Connection section of this manual o Check to make sure all wiring is connected properly Evacuation Instructions Before using the manifold gauge and vacuum pump read their operation manuals to...

Page 30: ...topper Do not try to force the valve to open further Note on Adding Refrigerant ADDITIONAL REFRIGERANT PER PIPE LENGTH Fig 6 2 Some systems require additional charging depending on pipe lengths The st...

Page 31: ...etected turn off the unit immediately and call a licensed electrician to nd and resolve the cause of the leakage Note This may not be required for some locations in the US Gas Leak Checks There are tw...

Page 32: ...troller to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each functi...

Page 33: ...ASSED do the following a Using remote control return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor...

Page 34: ...following options Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The man...

Page 35: ...osion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant ca...

Page 36: ...ies are advised Initial safety checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking that there no live electrical components and wir...

Page 37: ...be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This process sh...

Page 38: ...ot exceed the maximum working pressure of the cylinder even temporarily j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are rem...

Page 39: ...ated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut of...

Page 40: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Page 41: ......

Page 42: ...E 11 20 4 0 1 5 6 2 4 Componente aparat 10 3 8 1 20 2 21 3 22 4 23 1 11 2 12 3 12 4 14 5 15 6 16 7 18 8 18...

Page 43: ...25 29 6 7 8 9 10 34 11 MC MC R32 R290 31 32 34 1 29 2 30 25 B 25 1 25 2 26 3 26 4 27...

Page 44: ...4 Page 4 1 2 C C C 3 4 5 6 7 8 9 10 7 10 R32 R290...

Page 45: ...5 Page 5 11 12 13 14 15 16 8 1 3 1 2 3 4 1 2 3 4 12 5...

Page 46: ...6 1 1 1 1 5 5 2 1 2 Page 6 ST3 9 X 25 M LR03 ST2 9 x 10...

Page 47: ...VO32 09 P9MVI32 12WiFi P9MVO32 12 P9MVI32 18WiFi P9MVO32 18 P9MVI32 24WiFi P9MVO32 24 WALL MOUNTED UNIT AIR CONDITIONING SYSTEMS USER S MANUAL MANUAL UTILIZATORULUI ENGLISH ROMANA WALL MOUNTED UNIT MO...

Page 48: ...8 8 11 12 12 12 1 2 3 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in 2...

Page 49: ...9 9 STEP 8 1 2 3 5 6 7 8 9 25 17 19 16 19...

Page 50: ...10 Page 10 3 2 1 1 2 3 4 5 6 7 8 9 10 11 1 2 1 2 3 4 6 7 8 9 10 11 Air break switch 3 1 2 4 5 6 7 8 11 5...

Page 51: ...11 Page 11 4 Fig 3 1 a 1 o o o o o o 1 c c c...

Page 52: ...12 2 1 2 3 4 5 0 2in 3 1 65mm 2 5in 2 65mm 5mm 7mm 0 2 0 275in 3 2 3 Page 12 Fig 3 1 b 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in 3 1 b...

Page 53: ...wing dimensions Width of mounting plate Height of mounting plate Width of indoor unit relative to plate Height of indoor unit relative to plate Recommended position of wall hole both to the left and r...

Page 54: ...14 Page 14 Fig 3 5 30 50mm 1 2 1 95in 30 50mm 1 2 1 95in Fig 3 3 Fig 3 4 4 1 1 30 55mm 1 25 1 95in 3 4 2 3 6 2 1 4 3 3 3 3 3 5 3 4...

Page 55: ...15 Page 15 Fig 3 6 Fig 3 7 Fig 3 8 3 3 15cm 6in 2 3 4 5 6 7 1 2 3 8 3 6 3 7 3 8...

Page 56: ...16 Page 16 Fig 3 9 Fig 3 10 Fig 3 11 Fig 3 12 4 5 6 7 5 1 2 3 Teflon 4 5 3 9 3 9 3 10 3 12 3 11...

Page 57: ...17 3 6 6 101 10 161 16 252 25 324 32 406 10 18 13 16 18 14 25 12 30 10 Page 17 1 2 3 4 90 100 5 1 5 6 1 8in 3mm 7 8 9 10 11 1 40in 6 05V2V2 F 07RN F H07RN F AWG mm 0 75 1 1 5 2 5 4 6...

Page 58: ...18 Page 18 Fig 3 13 4 5 6 7 2 4 7 3 8 9 T5A 250VAC R32 R290 T20A 250VAC 18000Btu h T30A 250VAC 18000Btu h 1 A 15 cm 6in U 3 13...

Page 59: ...19 Page 19 Fig 3 14 7 1 3 14 2 3 3 14 8 1 4 2 3 4 5 6 7 3 14...

Page 60: ...20 Page 20 5 n i 4 2 m c 0 6 60cm 24in 30cm 12in 200cm 79in 30cm 12in Fig 4 1 1 o 4 1 o o o o 4 1...

Page 61: ...21 Page 21 A B Fig 4 2 Fig 4 3 Fig 4 4 90 4 2 4 3 4 4 1 2 3 90 4 4 4 1 2 4 3 4 2 4 4 2...

Page 62: ...310 31 9 x22 x12 2 549 21 6 325 12 8 900x860x315 35 4 x33 85 x12 4 590 23 2 333 13 1 945x810x395 37 2 x31 9 x15 55 640 25 2 405 15 95 946x810x420 37 21 x31 9 x16 53 673 26 5 403 15 87 946x810x410 37 2...

Page 63: ...23 Page 23 1 2 3 4 5 6 7 8 4 1 2 3 4 90 100 5 1 5 6 1 8in 3mm 7 8 9 10 11 1 40in...

Page 64: ...24 Page 24 Fig 4 6 1 H05VV F H05V2V2 F H07RN F H07RN F 15cm 6in 10 18 13 16 18 14 25 12 30 10 AWG 3 6 6 101 10 161 16 252 25 324 32 406 0 75 1 1 5 2 5 4 6 i i i i i i mm2 2 3 4 5 6 7 PVC 8 4 6...

Page 65: ...33ft 15 000 24 000 30 98 5ft 20 66ft 24 000 36 000 50 164ft 25 82ft 36 000 60 000 65 213ft 30 98 5ft R410A Inverter Split Air Conditioner 1 R32 R290 1 BTU h Lungime max m n l ime maxim de c dere m i i...

Page 66: ...2 Fig 5 3 Fig 5 4 A mm 6 35 0 25 0 7 0 0275 1 3 0 05 9 52 0 375 1 0 0 04 1 6 0 063 12 7 0 5 1 0 0 04 1 8 0 07 16 0 63 19 0 75 2 0 0 078 2 2 0 086 2 0 0 078 2 4 0 094 A Fig 5 5 2 1 2 3 1 2 3 5 3 4 5 m...

Page 67: ...1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 19 0 75 4 500 33 19lb ft 6 500 47 94lb ft 4 700 34 67lb ft 6 700 49 42lb ft...

Page 68: ...28 Page 28 Fig 5 9 Fig 5 10 5 6 7 3 6 5 9 5 10 1 5 9 2 3 4...

Page 69: ...29 Page 29 7 76cmHg MC MC Fig 6 1 o o 1 2 3 4 5 15 76cmHG 105Pa 6 1...

Page 70: ...R32 x 12g m x 0 13oZ ft R290 x 10g m x 0 10oZ ft R410A x 15g m x 0 16oZ ft Partea lichid 9 52 0 375 R32 x 24g m x 0 26oZ ft R290 x 18g m x 0 19oZ ft R410A x 30g m x 0 32oZ ft R290 387g 9000Btu h 447g...

Page 71: ...31 Page 31 8 4...

Page 72: ...32 Page 32 9 30 1 2 ON OFF 3 MODE 4 5 2 2...

Page 73: ...33 Page 33 Fig 8 1 5 17O C 63 F 17 C MANUAL CONTROL 1 MANUAL CONTROL 8 1 2 2 COOL 4 Manual Control 8 1...

Page 74: ...34 Page 34 10...

Page 75: ...35 Page 35 11 R32 R290 1 2 3 4 5 6 7 8 l...

Page 76: ...36 l l l l O 9 l l 10 10 1 10 2 l l...

Page 77: ...37 11 12 13 14 LFL 25 OFN 15 l l l l l OFN OFN...

Page 78: ...38 OFN 16 l l l l l l OFN 17 l l l l 80...

Page 79: ...39 18 19 l l l l l l l 20 1 2 3 4 5...

Page 80: ...alare 11 2 Ata are plac de montare pe perete 12 3 Realizare orificiu perete pentru conducte 12 4 Preg tire conducte de agent frigorific 14 5 Conectare furtun de scurgere 15 6 Conectare cablu pentru se...

Page 81: ...vice 34 11 MC MC ATENTIE Pericol de incendiu avertisment valabil pentru agent frigorific R32 R290 A Not cu privire la lungimea conductei 25 B Instruc iuni de conectare Conducte agent frigorific 25 1 T...

Page 82: ...ului ntotdeauna 1 Instala ia trebuie realizat de c tre un dealer autorizat sau un specialist O instala ie defectuoas poate duce la scurgeri de ap electrocutare sau incendiu 2 Instalarea trebuie realiz...

Page 83: ...fi facuta de catre copii fara supraveghere Pentru aparatele care au un radiator suplimentar nu instala i aparatul la o distan mai mic de 1 m 3 picioare de orice materiale combustibile Nu instala i ap...

Page 84: ...i de aer condi ionat O instalare neadecvat poate duce la scurgeri de ap electrocutare i incendiu sau poate cauza defectarea echipamentului Plac de montare Diblu pentru ancorare urub de fixare plac mon...

Page 85: ...re nu este ventilata cu o suprafata mai mica de 4mp Informatii cu privire la cerintele de spatiu pentru aparatele cu agent frigorific R290 Unitati cu capacitate 9000 Btu h 13mp Unitati 9000 12000Btu h...

Page 86: ...erioar 2 Alege i loca ia pentru instalare pagina 11 Ata a i placa de montare pagina 12 Realiza i orificiul din perete pagina 12 Stabili i pozi ia orificiului din perete pagina 12 1 2 3 4 12cm 4 75in 2...

Page 87: ...r pagina 19 STEP8 nveli i conductele i cablurile conditie neaplicabila in anumite zone din Statele Unite ale Americii pagina 19 Conecta i eava pagina 25 Conecta i cablurile pagina 17 Preg ti i furtunu...

Page 88: ...conformitate cu standardele normele si reglementarile locale Conditiile de instalare pot diferi in functie de zona Plac de montare pe perete Cablu de alimentare la unele modele eav agent frigorific C...

Page 89: ...paratului oO loca ie la cel pu in 1 m distan de toate dispozitivele electrice de exemplu televizor aparat radio calculator NU instala i aparatul n urm toarele loca ii n apropierea unei surse de c ldur...

Page 90: ...rete pentru conducte Trebuie s realiza i gaura din perete pentru conducta de agent frigorific conducta de scurgere i cablul de semnal ce vor lega unitatea interioar de cea exterioar 1 Stabili i loca i...

Page 91: ...nit ii interioare schi ele din dreapta arat diferite tipuri de plac de montare mpreun cu urm toarele dimensiuni L imea pl cii de montare n l imea pl cii de montare L imea unit ii interioare comparativ...

Page 92: ...ai mici dec t orificiile din spatele unit ii Dac vede i c nu ave i suficient spa iu pentru a conecta conductele incluse ale unit ii interioare unitatea poate fi ajustat la st nga sau la dreapta cu 30...

Page 93: ...ta i capitolul Verific ri Electrice i Verific ri pentru Scurgeri din prezentul manual Etapa 5 Dup testul de scurgeri nf ura i punctul de conexiune cu band izolatoare Etapa 6 ndep rta i consola sau man...

Page 94: ...i de scurgere 3 Str nge i ferm punctul de leg tur cu band de teflon pentru a asigura o etan are bun i pentru a preveni scurgerile 4 Pentru partea din furtunul de scurgere care va r m ne la interior fo...

Page 95: ...a i alte aparate la aceea i priz 8 Asigura i v de mp m ntarea adecvat a aparatului de aer condi ionat 9 Fiecare cablu trebuie conectat bine Cablurile conectate slab pot duce la supra nc lzirea termina...

Page 96: ...tru a conecta cablul 8 Dup verificarea pentru a v asigura c fiecare conexiune este sigur utiliza i clema pentru cabluri pentru a str nge cablul de semnal al unit ii Str nge i ferm clema pentru cabluri...

Page 97: ...acces la ele pentru a testa mpotriva scurgerilor la finalul procesului de instalare consulta i capitolele Verificarea Electric i Verificarea pentru scurgeri din acest manual Etapa 8 Montare unitate i...

Page 98: ...g 4 1 oO circula ie bun a aerului oUn loc ferm i solid loca ia va putea sus ine unitatea i nu va vibra oZgomotul produs de aparat nu va deranja al i oameni oO loca ie ferit de perioadele lungi de expu...

Page 99: ...scurgere nu este prev zut cu garnitur din cauciuc consulta i Fig 4 4 B urma i urm toarele etape 1 Introduce i racordul de scurgere n orificiul din tava de colectare de la baza unit ii Racordul de scu...

Page 100: ...abel reprezint o list cu diversele dimensiuni ale unit ii exterioare i distan a dintre picioarele de montare Preg ti i baza de instalare a unit ii conform cu dimensiunile de mai jos Dac instala i unit...

Page 101: ...oare 3 Dac exist o problem serioas de siguran cu alimentarea electric opri i lucr rile imediat Explica i acest motiv clientului i refuza i instalarea unit ii p n ce problema legat de siguran este rezo...

Page 102: ...de cablare unitate exterioar se afl la interiorul capacului cablurilor din unitatea exterioar Capac INE I CONT DE CABLURILE ALIMENTATE n opera iunea de ambutisare ave i grij la diferen ierea clar a c...

Page 103: ...axim de c dere m i i i 2 Utiliz nd un cle te de t iat evi t ia i conducta pu in mai lung dec t distan a m surat 3 Asigura i v c eava este t iat la un unghi perfect de 90o Consulta i Fig 5 1 pentru exe...

Page 104: ...partea t iat a conductei Etapa 3 Capete conduct expandat O expandare este esen ial pentru a avea o etan are bun 1 Dup ndep rtarea bavurii din eava t iat etan a i capetele cu band din PVC pentru a prev...

Page 105: ...ei mm Cuplu de torsiune N cm Cuplu de torsiune suplimentar N m CERIN E CUPLU DE TORSIUNE RAZ MINIM DE NDOIRE Atunci c nd ndoi i conductele de agent frigorific raza minim de ndoire este de 10 cm Consul...

Page 106: ...nd o cheie de buloane apuca i corpul supapei Nu apuca i piuli a ce deta eaz supapa de service consulta i Fig 5 10 5 Atunci c nd apuca i ferm corpul supapei folosi i o cheie dinamometric pentru a str n...

Page 107: ...ei de agent frigorific din acest manual oVerifica i pentru a v asigura c toate cablurile sunt conectate adecvat Instruc iuni evacuare nainte de utilizarea supapei colectoare i a pompei de vid citi i m...

Page 108: ...gorific suplimentar ce trebuie nc rcat poate fi calculat utiliz nd urm toarea formul 12 Utiliza i o cheie hexagonala deschide i at t supapa de presiune crescut c t i supapa de presiune sc zut 13 Str n...

Page 109: ...ratul i apela i la un electrician autorizat pentru a g si i a rezolva cauza pierderilor Not Acest lucru poate s nu fie cerut n unele loca ii din SUA AVERTIZARE RISC DE ELECTROCUTARE TOATE CABLURILE TR...

Page 110: ...ni aparatul 3 Ap sa i butonul MODUL MODE pentru a alege una din urm toarele func ii c te una pe r nd R CIRE COOL alege i cea mai mic temperatur posibil NC LZIRE HEAT alege i cea mai mare temperatur po...

Page 111: ...verificare de pe lista de verificare au fost trecute face i urm toarele a Utiliz nd telecomanda seta i aparatul pe temperatura normal de func ionare b Utiliz nd band izolatoare izola i conexiunile co...

Page 112: ...p iuni Elimina i aparatul n cadrul institu iei specializate de colectare a de eurilor electronice din municipiu La achizi ionarea unui nou produs v nz torul va lua la schimb vechiul produs f r costuri...

Page 113: ...sursele de scanteie In timpul lucrarilor la traseele frigorifice ce presupun expunerea conductelor este interzisa folosirea oricarui produs ce poate genera scanteie Toate sursele de scanteie incluzan...

Page 114: ...a face cu evitarea oricarei situati care poate produce o scanteie l Nici un component electric nu va fi alimentat si expus in timpul lucrarilor de incarcare recuperare sau eliminare a agentului frigor...

Page 115: ...pentru detectia agentilor frigorifici inflamabili Echipamentului ii va fi setat un procentaj minim de detectie si va fi calibtrat in functie de tipul agentului frigorifici si concentratia de gaz maxi...

Page 116: ...re a freonului este supravegheat in permanenta de catre personal calificat l Echipamentul pentru recuperare si cilindrii de depozitare sunt conforme cu standardele d Pompati freonul daca este posibil...

Page 117: ...eon inainte de returnarea catre producator Pentru a accelera procesul puteti folosi DOAR incalzirea electrica 20 Transportul etichetarea si depozitarea aparatelor 1 Transportul echipamentelor care con...

Page 118: ...NOTES...

Page 119: ......

Page 120: ...D UNIT Scan here to download the latest version of this manual Please check the applicable models F GAS and manufacturer information from the Owner s Manual Product Fiche in the packaging of the outdo...

Reviews: