32
Finally, tighten the flare nut ith tor ue rench until the rench
clicks.
2.Overlap the connection pipe insulation material and the indoor
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
After the piping has been connected to the indoor unit, perform
the air purge.
Air purging ith vacuum pump
e sure to use a vacuum pump ith counter-flo prevention
function so that oil inside the pump does not flo back into the
air conditioner pipes hen the pump stops. (If oil inside the
vacuum pump enters into the air conditioner circuit hich uses
R410A, trouble ith the refrigeration system may develop.)
1. Connect the charge hose from the manifold valve to the service
port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold
valve.
For detaching the indoor unit from the installation plate pull the
indoor unit toward you while pushing the bottom up at the speci-
fied places.
4)Run the drain hose at a downward sloped angle.
5)Put water in the drain pan and make sure that the water is
being drained outside.
Caution:
Install the drain pipe for proper drainage. Improper drainage can
result in water dripping inside the room.
7.4 INSTA
ATION OF OUTDOOR UNIT
* Holes are provided on the base plate of the outdoor unit to
ensure that the defrost water produced during heating opera-
tions is drained off efficiently.
* If a centralized drain is required when installing the unit on a
balcony or wall.
* If the drain port is covered by a mounting base or floor surface,
place additional foot bases of at least 30mm in height under the
outdoor unit’s feet.
* In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating
performance.)
Remove the Valve cover from the unit by loosening the scre .
Align the center of the pipings and sufficiently tighten the flare
nut by hand.
Push
Push
50 mm
or more
Do not rise the drain hose.
Do not form the drain hose
into the waved shape.
Do not put the
drain hose end
into water.
Do not put the drain
hose end in the
drainage ditch.
Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
Liquid side piping
Outdoor unit
Gas side piping
(Bigger diameter)
(Smaller diameter)
Torque wrench
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor
unit using a vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the vacuum pump manual.
Installation Manual
Summary of Contents for CEVI-09
Page 1: ......
Page 15: ...13 5 3 Printed Circuit Board TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 17: ...15 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 18: ...16 FRONT VIEW BOTTOM VIEW Schematic Diagram ...
Page 19: ...17 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 37: ...35 Outdoor Unit 1 Cooling Only Models Exploded Views and Parts list ...
Page 38: ...36 2 Cooling Heating Models Exploded Views and Parts list ...
Page 68: ...66 13 Remove Motor Sub Assy 14 Remove Fan Motor Remove Motor Sub Assy 1 Removal Procedure ...
Page 69: ......
Page 70: ......
Page 74: ......