Out of step occurs once the
unit is powered on.
Is stop time of the
compressor longer than
3 minutes?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
direction?
Connect the
wires correctly
Replace the control
panel AP1
If the fault is eliminated?
Replace the
compressor
End
Out of step occurs in
operation
Is the outdoor fan working
normally?
Is the outdoor unit blocked
by foreign objects?
Replace the
control panel AP1
If the fault is eliminated?
Replace the
compressor
End
Check if the fan terminal
OFAN is connected correctly
Remove foreign objects
Replace the fan
capacitor C1
Replace the
outdoor fan
50
Summary of Contents for C1VI-09
Page 1: ...C1VI 09 C1VO 09 C1VI 12 C1VO 12 ...
Page 2: ...a b e 2 3 3 7 7 8 8 9 10 11 12 12 12 14 16 16 19 24 24 26 27 28 ...
Page 3: ...Simply 29 30 31 31 35 39 39 62 59 43 46 44 59 ...
Page 5: ...2 ...
Page 6: ...C1VI 09 C1VO 09 C1VI 09 C1VO 09 C1VI 09 3 ...
Page 7: ...C1VO 09 4 ...
Page 8: ...C1VI 12 C1VO 12 C1VI 12 C1VO 12 C1VI 12 5 ...
Page 9: ...C1VO 12 6 ...
Page 12: ...9 ...
Page 13: ...10 ...
Page 17: ...1 2 3 4 5 6 7 8 9 10 11 12 14 ...
Page 18: ...11 10 9 8 7 6 13 12 14 5 4 3 2 1 15 ...
Page 24: ...21 ...
Page 25: ...A L B C D O 0 O 0 L1 A1 B1 C1 D1 heating angle cooling angle 22 ...
Page 26: ...23 ...
Page 27: ...24 ...
Page 28: ...25 ...
Page 33: ...Fig a filter Air filter Fig b Fig c Healthy 30 ...
Page 35: ...C1VI 09 32 ...
Page 37: ...C1VI 12 34 ...
Page 38: ...1 2 3 4 5 7 8 9 10 11 13 14 15 16 17 18 19 20 21 22 6 12 C1VO 09 35 8 2 Outdoor Unit ...
Page 39: ...C1VO 09 36 ...
Page 40: ...1 2 3 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 6 C1VO 12 37 ...
Page 41: ...C1V0 12 38 ...
Page 46: ...43 ...
Page 47: ...44 ...
Page 48: ...45 ...
Page 57: ...54 ...
Page 59: ...56 ...
Page 60: ...57 ...
Page 61: ...58 ...
Page 62: ...59 ...
Page 63: ...60 ...
Page 64: ...61 ...
Page 70: ......