66
7.4. Binary inputs I1....I4
Signal voltage range
0 ... 30VDC
Input resistance
5,4 k
Input ON (1) voltage
> 9V
Input OFF (0) voltage
0 ... 3V
7.5. Relay outputs Q1...Q4
Output type
Relay, optoisolated, NO
Maximum voltage between contacts
250VAC/300VDC
Load current
6A/230VAC, 6A/24VDC
Maximum switching current
15A/20ms
Resistance
<100m
7.6. Analogue inputs AN1, AN2
Analog/Pt100 input AN1 - temperature measurement
Sensor type
PT100, 2- or 3-wired
Wires resistance compensation
yes (applies only to 3-wire sensor)
Measurement range
-40...+200
C
Accuracy
+/-1
C
Analog/NTC input AN2 - temperature measurement
Sensor type
NTC 10k
Measurement range
-25...+55
C
Accuracy
+/-1
C (depending on used sensor)
Analog inputs AN1, AN2 - voltage measurement
Measurement range
0...5V/0...10V
Maximum input voltage
18V
Input dynamic impedance
150k
typ.
Ac/-1,5%
max.
Nonlin/-1%
max.
Analog inputs AN1, AN2 - current measurement
Measurement range
4...20mA
Maximum input current
50 mA max.
Input dynamic impedance
100
typ.
Voltage drop at 20mA
2V max.
Ac/-1,5%
max.
Nonlin/-1%
max.