30
INSTALLATION AND ASSEMBLY
aV100 extract air system – Avio N 100
•
Installation and operating instructions
Install aV100 weather protection hood
NOTE
Install on unfinished exterior wall.
Damage to the exterior wall!
►
Do not install the weather protection hood until the exterior wall is completed and fully cured.
Requirements:
The exterior wall is completed and even.
The wall sleeve is installed.
The styrofoam protective disc is removed from the exterior wall.
NOTE
Algae accumulation around the weather protection hood.
Discolouration of the facade!
►
Secure all sealing tapes circumferentially before installing the weather protection hood.
►
In vulnerable areas, apply a biocidal/water repellent treatment to the plaster surface around
the weather protection hood before installing.(Consult your planner!)
TIP
Before installing the weather protection hood base plate, remove the styrofoam disc
from the wall sleeve (from the exterior wall side) to ensure adequate air flow.
►
From the exterior wall side, secure the sealing
tape, 9 mm, (1) circumferentially along the
weather protection hood base plate (2).
Ensure that
the sealing tape (1) has a clear-
ance of about 7 mm to the outer edge of the
base plate on both the left and right.
7
2
1
►
Secure the sealing tape, 9 mm, (4) to the top
edge inside the weather protection hood base
plate (3).
3
4