Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
23
24
R
▪
When the mechanism for “Virtual
temperature” is not being applied
, the value
will be the one in the register 5 (PLC
addressing).
▪
16..31ºC (ºC/x10ºC)
▪
60..90ºF
24
25
R
▪
-32768 (Initialization value)
▪
Ranges are specific from Manufacturer
25
26
R
▪
-32768 (Initialization value)
▪
Ranges are specific from Manufacturer
31
32
R
Status (feedback)
▪
0: Not active (Default value)
▪
1: Active (A window is open)
46
47
R
Center/Remote
8
▪
0: Remocon unlock (Center/Remote)
▪
1: Remocon lock On/Off (Center)
▪
2: Remocon lock All (Center)
▪
3: Remocon Only (Remote)
55
56
R/W Under voltage counter
▪
0..300(hours)
60
61
R
▪
-32768d: (Initialization value)
No temperature’s value is being provided
outdoor. No virtual temperature is applied.
▪
Any other: (ºC/x10ºC/ºF)
65
66
R
▪
-32768: (Initialization value). No
temperature’s value is being provided from
an external sensor. No virtual temperature is
applied.
▪
Any other: (ºC/x10ºC/ºF)
66
67
R
▪
-32768 (Initialization value)
▪
Any: (ºC/x10ºC/ºF)
97
98
R/W
5,9,10
▪
0: Non-blocked (Default value)
▪
1: Blocked
98
99
R/W
Master/Slave (gateway)
▪
0: Slave
▪
1: Master
8
See section 4.2.4 for more information
9
If the register is configured as
“0:Non
-
blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value.
10
This register applies to firmware version 0.14 onwards