4.2.2
Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
13
14
R/W
“Open Window” switch
-off timeout
11
▪
0..30 (minutes)
▪
Factory setting: 30 (minutes)
14
15
R
Modbus RTU baud-rate
▪
2400bps
▪
4800bps
▪
9600bps (Default)
▪
19200bps
▪
38400bps
▪
57600bps
▪
76800bps
▪
115200bps
15
16
R
Modbus Slave Address
▪
1..63
21
22
R
Max number of fan speeds
45
46
W
Error reset
▪
1: Reset
48
49
R
Switch value
49
50
R
Device ID: 0x0F00
50
51
R
Software version
81
82
R
Error address
▪
Provides the indoor unit number which is
providing error
99
100
W
Reset
▪
1: Reset
While the initialization is ongoing, some Modbus registers will indicate an undetermined value.
Once the normal operation starts, they will acquire its corresponding value. It is important to
keep in mind that any change done during the initialization process will not have effect until it
has been finished.
11
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.