SW3/SW4
–
Baud rate configuration
SW3-P7..8
SW4-P3 Description
2400bps
4800bps
9600bps (Default value)
19200bps
38400bps
57600bps
76800bps
115200bps
Table 4.2
SW3-SW4: Modbus baud rate
SW4
–
Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination
resistor.
Table 4.3
SW4: Temperature and termination resistor configuration
SW4-P1..2-4 Description
Temperature values in Modbus register are represented in degrees (x1) (Default value)
Temperature values in Modbus register are represented in decidegrees (x10)
Temperature values in Modbus register are represented in Celsius degrees (Default value)
Temperature values in Modbus register are represented in Fahrenheit degrees
EIA-485 bus without termination resistor (Default value)
Interna
l termination resistor of 120Ω connected to EIA
-485 bus