background image

 

           

       

 

 

 

                         
 
                                      

 

 

 

 

IntesisBox

®

 KNX - Modbus RTU master 

 

Doc. Rev.2 

Installation Manual

 

URL

email

tel

http://www.intesis.com                                         
[email protected] 
+34 938047134 
 

    4 / 5

This information is subject to change without notice.

 

 

 
 
 

Enclosure 

Plastic, type PC (UL 94 V-0).  
Dimensions: 107mm x 105mm x 58mm. 

Colour 

Light Grey. RAL 7035. 

Power 

9 to 30Vdc +/-10%, Max.: 125mA. 
24Vac +/-10% 50-60Hz, Max.: 127mA 
Must use a NEC Class 2 or Limited Power Source (LPS) and SELV 
rated power supply. 
Plug-in terminal block for power connection (2 poles). 

Terminal wiring 
(for power supply 
and low-voltage 
signals) 

Per terminal: solid wires or stranded wires  (twisted or with ferrule) 
1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

Modbus RTU ports 

1 x EIA485. Plug-in screw terminal block (2 poles). SELV 
1 x EIA232. DB9 male connector (DTE). SELV 

KNX port 

1  x  KNX  TP1  (EIB)  port  opto-isolated.  Plug-in  terminal  bloc  (2 
poles). TNV-1 

LED indicators 

1 x Power. 
2 x KNX port activity (Tx, Rx). 
2 x Modbus RTU port activity (Tx, Rx). 
1 x KNX programming/bus.

1

 

Push buttons 

1 x KNX programming.

1

 

Console port 

EIA232. DB9 female connector (DCE). SELV 

Configuration 

Via console port.

2

  

Firmware 

Allows upgrades via console port.  

Operational 
temperature 

-40°C to +70°C

 

Operational 
humidity 

5% to 95%, non condensing 

Protection  

IP20 (IEC60529). 

RoHS conformity 

Compliant with RoHS directive (2002/95/CE). 

Norms and 
standards 

CE conformity to EMC directive (2004/108/EC) and Low-voltage 
directive (2006/95/EC) 
EN 61000-6-2 
EN 61000-6-3 
EN 60950-1 
EN 50491-3 

 

1

   Not operational for the moment. Reserved for future use. 

 

2

   Standard  cable  DB9male-DB9female  1,8  meters  long  is  supplied  with  the  device  for  connection  to  a  PC  COM  port  for 

configuring  and  monitoring  the  device.  The  configuration  software,  compatible  with  Windows

®

  operating  systems,  is  also 

supplied.

 

 

Technical characteristics 

 

Reviews: