background image

8

137750_Rev_L    11.16.12

Vent Restriction

This appliance is equipped with Restrictor Plates which 

enable you to regulate the flow of incoming combustion 

air and exhaust gas. The plates prevent overly strong draft 

that can cause poor combustion and weak flame picture. 

Follow the guidelines below, and on the following pages, 

to determine the correct restrictor plate setting for your 

particular installation configuration

.

Intake Air Restrictor

This plate is located at the rear of the firebox behind the 

burner plate. It is set in a CLOSED position at the factory 

and should be left there for most vent configurations.  

It should be opened only for snorkel terminations and 

some short run horizontal terminations as specified on 

the following pages. To adjust the Air Restrictor to the 

OPEN position, locate and loosen the wing nut under the 

burner and push it back as far as it will go. See Fig. 6.

Exhaust Restrictor

The Exhaust Restrictor is an adjustable shutter located at 

the top of the firebox. It is adjusted by moving a pivot pin 

into one of four positions. It is set in the FULLY OPEN posi-

tion at the factory. See Fig. 7.

Use the chart in Table 1 to determine the correct 

position for your installation and follow the instructions 

below to adjust it if necessary.

Additional restriction may be needed depending the 

overall vent height. Use Simpson Dura-Vent Restrictor 

Disk #929.

Adjusting Exhaust Restrictor Plate:  

1. Remove the Top Plate.
2. Locate the pivot pin at the left side of the firebox top. 

Loosen the wing nut on the pivot pin and push the 

pin to the left to disengage it from the current setting 

position. Move the pin toward the rear and then right 

to engage it in the appropriate position indicated on 

the firebox. See fig. 7.

3. Tighten the lock nut and replace the Top Plate.

Venting Requirements

This appliance may be installed with a vertical or horizon-

tal termination and must conform to the configuration 

requirements described below.

This appliance is approved for use with vent systems 

from the following manufacturers: 

•  Simpson Dura-Vent GS    

           

 

•  Metal-Fab Sure-Seal DV   

 

•  Amerivent Corporation          

 

•  Security Vent Ltd.

 

•  Selkirk Metalbestos

 

•  International Chimney Corp. (ExcelDirect)    

 

•  Bernard Delsin Mfg. (Pro Form)

Use parts of one manufacturer only - DO NOT MIX 

VENT COMPONENTS FROM DIFFERENT MANUFACTURERS 

IN THE SAME SYSTEM.

Installation of any components not manufactured or 

approved by Jøtul or failure to meet all clearance require

-

ments will void all warranties and could result in property 

damage, bodily injury, or serious fire.

The approved vent configurations described in this 

manual are derived from extensive testing under con-

trolled laboratory conditions. Gas appliance performance 

can be negatively affected by variables present in the 

installation environment, i.e: atmospheric pressure, strong 

prevailing winds, adjacent structures and trees, snow 

accumulation, etc. These conditions should be taken into 

consideration by the installer and stove owner when plan-

ning the vent system design.

IMPORTANT

• 

JOINT SEALING REQUIREMENT: 

 APPLY A 1/8” BEAD OF 

HIGH- 

TEMPERATURE (750°F) SEALANT TO THE MALE SEC

-

TION OF THE INNER VENT PIPE.  THE 

CEMENT SHOULD FORM A SEAL 

BETWEEN THE INNER AND OUTER 

PIPES.

•  NEVER MODIFY ANY VENTING 

COMPONENT, OR USE ANY DAM

-

AGED VENTING PRODUCT.

•  THE GAS APPLIANCE AND 

VENT SYSTEM MUST BE 

VENTED DIRECTLY TO THE 

OUTSIDE OF THE BUILDING 

AND NEVER ATTACHED TO 

A CHIMNEY SERVING A SOLID FUEL OR GAS BURNING 

APPLIANCE.  EACH DIRECT VENT GAS APPLIANCE MUST 

HAVE ITS OWN SEPARATE VENT SYSTEM.  

 

COMMON VENT SYSTEMS ARE PROHIBITED.

•  IF VENTING SYSTEM IS DISASSEMBLED FOR ANY REA

-

SON, REINSTALL PER THE INSTRUCTIONS PROVIDED FOR 

THE INITIAL INSTALLATION.

Fig. 5.

Summary of Contents for Jotul GF 400 DV Sebago

Page 1: ...r future reference QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez Appe...

Page 2: ...used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the completion of the instal...

Page 3: ...634 Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin to ANSI Z21 88 2009 ANSI Z21 88 CSA 2 33 2009 CAN...

Page 4: ...m input Propane 32 000 BTU hr maximum input 16 000 BTU hr minimum input Inlet Pressure MIN MAX Natural Gas 5 0 WC 1 24 kPa 7 0 WC 1 74 kPa Propane 12 0 WC 2 99 kPa 14 9 WC 3 71 kPa Manifold Pressure M...

Page 5: ...tion that is not specifi cally addressed in this manual defaults to local code In the absence of local codes the installation require ments must comply with the current National codes In the U S these...

Page 6: ...adultes doivent tre avertis des dangers des temp ratures de surface lev es et devraient rester l cart pour viter les br lures ou l inflammation des v tements Young children should be supervised while...

Page 7: ...Alcove dimensions result from test configurations not stove clearance specifications Minimum Clearances from the Vent Pipe to Combustibles Horizontal Run Off the top of the pipe 2 51 mm Off the sides...

Page 8: ...ig 7 3 Tighten the lock nut and replace the Top Plate Venting Requirements This appliance may be installed with a vertical or horizon tal termination and must conform to the configuration requirements...

Page 9: ...run at three feet intervals to avoid excessive stress on the offsets Elbows Four 45 or two 90 elbows may be used Do not include the 45 elbow attached to the stove When ever possible use 45 elbows inst...

Page 10: ...cled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove First determine which vent termination zone is appropriate for your installation and fuel type th...

Page 11: ...TICAL TEMINATIONS ONLY SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT COR RESPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND UNDER SEE FI...

Page 12: ...the unit and the termination cap A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM Co...

Page 13: ...UL 103 or ULC S 629 listed and have a minimum INSIDE diameter of 6 inch es 150 mm Prefabricated chimneys must be listed for the specific Chimney Conversion Kit you choose Figure 15 Vent System through...

Page 14: ...NWARD FROM STOVE TO TERMINATION DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE Install a Vinyl Siding Standoff between the vent termi natio...

Page 15: ...ly within 3 feet 90 cm horizontally from the center line of the regulator I Clearance to service regulator vent outlet 3 feet 91 cm minimum J Clearance to nonmechanical air supply inlet to building or...

Page 16: ...HIBITED BY LOCAL CODES THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PROVIDED WITH THE GF 400 SEBAGO DIRECT VENT GAS STOVE C...

Page 17: ...low replacement of the Burner Plate 10 Replace the Burner Plate Engage the Air Inlet Tube with the Air Shutter and burner orifice Properly seated the burner plate will be engaged at its front corners...

Page 18: ...d and tighten screws securely 16 Install the identification labels to the stove so that they can be seen by any person that may be servicing the stove Label A apply to back of stove Label B apply to s...

Page 19: ...ons on the inside back cover of this manual or on the stove s rating plate 3 Brush or spray all joints and connections with the soapy water solution 4 If bubbles appear at any connection or seam or a...

Page 20: ...to burn natural gas with the air shutter set half open Be aware however that this initial setting may not provide the optimal flame picture in your particular installation No single setting will be ap...

Page 21: ...Middle Log Figure 37 Install Ember Stones Figure 36 Install Crossover Log PILOT OPENING DO NOT OBSTRUCT The ember stones realistically simulate glow ing coals when the burner is operating These shoul...

Page 22: ...igure 39 Flame appearance on the high setting after approximately 15 to 20 minutes burning WARNING AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE PER FORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN Figu...

Page 23: ...is vacuum this area frequently Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids If a vacuum is used during any service on the stove ALWAYS...

Page 24: ...bled for any reason it should be reassembled and sealed according to the manufac turer s instructions provided at the initial installation Burner and Logset Periodically inspect the Firebox Valve Comp...

Page 25: ...he Blower Bracket to the stove using the two M6 flange head hex bolts as shown in fig 44 4 Attach the Duct Deflectors using the two 7 x 1 2 screws together with the finger guard mounting screws alread...

Page 26: ...nually adjusted with the rheostat knob If the burner turns off the blower will be shut off automatically when the stove cools down If automatic blower circulation is not desired place the blower contr...

Page 27: ...their own against the wall Push them back against the Rear Panel Fig 51 6 Reinstall the Logset See page 21 BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT ASSEMBLY OPENING 7 Replace the Glass Frame...

Page 28: ...Rev_L 11 16 12 Figure 52 Illustrated Parts Breakdown GF 400 DV Sebago GF 400 DV Sebago Illustrated Parts Breakdown Center mount Valve shown used on models after SN 30000 Side mounted Valve uses same c...

Page 29: ...mostat 750003 Remote Control 750002 Floor Bracket Kit 750304 Fuel Conversion Kit to Propane 155351 Fuel Conversion Kit to Natural Gas 155352 37 Firebox Assembly 221960 38 Latch Assembly 220091 39 Reli...

Page 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Page 31: ...knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this app...

Page 32: ...beginning the installation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specif...

Reviews: