background image

22

137750_Rev_L    11.16.12

System Check

1.  PURGING THE GAS LINE: 

 When lighting the appliance 

for the first time, it will take a few moments to clear 

the gas line of air. Once this purge is complete, the 

appliance will operate as described in the lighting 

instructions. See the inside back cover of this manual 

or the stove Rating Plate attached the bottom of the 

stove. Subsequent burner starts will not require purg-

ing the gas line unless the supply line is shut off.  

2.  PILOT FLAME: 

 You can monitor the pilot flame 

through the view port located at the rear of the Right 

Log. The pilot flame should be steady - not lifting or 

floating. The flame should be blue in color around 

the pilot hood, with traces of yellow toward the outer 

edges. 

  The pilot flame should engulf the top 3/8” of the 

thermopile (to generate millivolt current) and the 

top 1/8” of the thermocouple. The pilot flame should 

project out of all three pilot hood ports 1” and project 

over to the burner plate carry-over ports.  See fig. 38 

and 38a.

 Figure 39. Flame appearance on the “high” setting after 

approximately 15 to 20 minutes burning.

WARNING:  

AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE PER-

FORMED BY A QUALIFIED PROFESSIONAL SERVICE 

TECHNICIAN.

Figure 38.  Proper pilot flame appearance.

3.  BURNER ADJUSTMENT: 

 This stove is equipped with a 

variable gas control valve that allows easy adjustment 

of the flame height appearance and heat output. To ad-

just the flame between the HI and LOW setting, rotate 

the HI/LOW knob, located in the center of the valve 

face. 

 Flame height will adjust approximately 1” to 2” 

between the LOW and HIGH settings.  See fig. 39.

  NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK 

LOG PLACEMENT IF ANY SOOT OR SMOKE IS PRESENT. 

IF SOOT OR SMOKE PERSISTS, THE AIR SHUTTER MAY 

NEED TO BE ADJUSTED.  

  See Air Shutter/Flame Appearance section of this man

-

ual for proper air shutter settings and adjustments.  

Note: the more offsets there are in the vent system, 

the greater the need for an air shutter adjustment. See 

page 20.

Figure 38a.  Proper pilot flame appearance relative to 

burner carry-over porting.

CAUTION:

DO NOT ATTEMPT TO ALTER THE FLAME APPEARANCE 

BY POSITIONING THE GAS VALVE CONTROL IN ANY 

OTHER THAN THE FULL “ON” POSITION.

Carry-over 

Ports

Summary of Contents for Jotul GF 400 DV Sebago

Page 1: ...r future reference QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez Appe...

Page 2: ...used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the completion of the instal...

Page 3: ...634 Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin to ANSI Z21 88 2009 ANSI Z21 88 CSA 2 33 2009 CAN...

Page 4: ...m input Propane 32 000 BTU hr maximum input 16 000 BTU hr minimum input Inlet Pressure MIN MAX Natural Gas 5 0 WC 1 24 kPa 7 0 WC 1 74 kPa Propane 12 0 WC 2 99 kPa 14 9 WC 3 71 kPa Manifold Pressure M...

Page 5: ...tion that is not specifi cally addressed in this manual defaults to local code In the absence of local codes the installation require ments must comply with the current National codes In the U S these...

Page 6: ...adultes doivent tre avertis des dangers des temp ratures de surface lev es et devraient rester l cart pour viter les br lures ou l inflammation des v tements Young children should be supervised while...

Page 7: ...Alcove dimensions result from test configurations not stove clearance specifications Minimum Clearances from the Vent Pipe to Combustibles Horizontal Run Off the top of the pipe 2 51 mm Off the sides...

Page 8: ...ig 7 3 Tighten the lock nut and replace the Top Plate Venting Requirements This appliance may be installed with a vertical or horizon tal termination and must conform to the configuration requirements...

Page 9: ...run at three feet intervals to avoid excessive stress on the offsets Elbows Four 45 or two 90 elbows may be used Do not include the 45 elbow attached to the stove When ever possible use 45 elbows inst...

Page 10: ...cled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove First determine which vent termination zone is appropriate for your installation and fuel type th...

Page 11: ...TICAL TEMINATIONS ONLY SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT COR RESPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND UNDER SEE FI...

Page 12: ...the unit and the termination cap A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM Co...

Page 13: ...UL 103 or ULC S 629 listed and have a minimum INSIDE diameter of 6 inch es 150 mm Prefabricated chimneys must be listed for the specific Chimney Conversion Kit you choose Figure 15 Vent System through...

Page 14: ...NWARD FROM STOVE TO TERMINATION DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE Install a Vinyl Siding Standoff between the vent termi natio...

Page 15: ...ly within 3 feet 90 cm horizontally from the center line of the regulator I Clearance to service regulator vent outlet 3 feet 91 cm minimum J Clearance to nonmechanical air supply inlet to building or...

Page 16: ...HIBITED BY LOCAL CODES THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PROVIDED WITH THE GF 400 SEBAGO DIRECT VENT GAS STOVE C...

Page 17: ...low replacement of the Burner Plate 10 Replace the Burner Plate Engage the Air Inlet Tube with the Air Shutter and burner orifice Properly seated the burner plate will be engaged at its front corners...

Page 18: ...d and tighten screws securely 16 Install the identification labels to the stove so that they can be seen by any person that may be servicing the stove Label A apply to back of stove Label B apply to s...

Page 19: ...ons on the inside back cover of this manual or on the stove s rating plate 3 Brush or spray all joints and connections with the soapy water solution 4 If bubbles appear at any connection or seam or a...

Page 20: ...to burn natural gas with the air shutter set half open Be aware however that this initial setting may not provide the optimal flame picture in your particular installation No single setting will be ap...

Page 21: ...Middle Log Figure 37 Install Ember Stones Figure 36 Install Crossover Log PILOT OPENING DO NOT OBSTRUCT The ember stones realistically simulate glow ing coals when the burner is operating These shoul...

Page 22: ...igure 39 Flame appearance on the high setting after approximately 15 to 20 minutes burning WARNING AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE PER FORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN Figu...

Page 23: ...is vacuum this area frequently Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids If a vacuum is used during any service on the stove ALWAYS...

Page 24: ...bled for any reason it should be reassembled and sealed according to the manufac turer s instructions provided at the initial installation Burner and Logset Periodically inspect the Firebox Valve Comp...

Page 25: ...he Blower Bracket to the stove using the two M6 flange head hex bolts as shown in fig 44 4 Attach the Duct Deflectors using the two 7 x 1 2 screws together with the finger guard mounting screws alread...

Page 26: ...nually adjusted with the rheostat knob If the burner turns off the blower will be shut off automatically when the stove cools down If automatic blower circulation is not desired place the blower contr...

Page 27: ...their own against the wall Push them back against the Rear Panel Fig 51 6 Reinstall the Logset See page 21 BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT ASSEMBLY OPENING 7 Replace the Glass Frame...

Page 28: ...Rev_L 11 16 12 Figure 52 Illustrated Parts Breakdown GF 400 DV Sebago GF 400 DV Sebago Illustrated Parts Breakdown Center mount Valve shown used on models after SN 30000 Side mounted Valve uses same c...

Page 29: ...mostat 750003 Remote Control 750002 Floor Bracket Kit 750304 Fuel Conversion Kit to Propane 155351 Fuel Conversion Kit to Natural Gas 155352 37 Firebox Assembly 221960 38 Latch Assembly 220091 39 Reli...

Page 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Page 31: ...knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this app...

Page 32: ...beginning the installation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specif...

Reviews: