5) SHIPPING 

COMPONENTS 

 

The unit is shipped in two separate cartons; the first 
carton is for the water heater tank. The second is for 
the burner and aquastat(s), the wiring harness, safety 
relief valve and the flue adaptor. 

 

 
6) WATER 

CONNECTIONS 

 

CAUTION 

To avoid water damage and/or scalding due to relief 
valve operation, a discharge line must be connected to 
the valve outlet and run to a drainage area. The 
discharge line shall be installed in such a way that it 
will allow for complete drainage of the valve and 
discharge line. 

 

Make the hot and cold water connections to the water 
heater. Do not apply heat to the hot water outlet and 
cold water inlet, as they contain a plastic sleeve inside. 
Pressure relief valves are installed on models CM-32, 
CMO32 and CMO50. 

 

7) FLUE 

PIPE 

 

The water heater should be connected to a chimney or 
an approved pre-fabricated flue. The flue pipe should 
be the same size as the flue outlet of the unit. It is 
preferable to maintain a pitch or rise from the heater to 
the chimney of 2.0 cm per 1 m (1/4" per foot). The flue 
pipe must not be extended past the inside wall of the 
chimney. 

 

8) DRAFT 

REGULATOR 

 

The draft regulator must be installed between the flue 
outlet of the water heater and the chimney. 
(Installation instructions are furnished with the 
regulator). 

 

9) 

BLOCKED VENT SHUT-OFF (BVSO) 
For chimney venting 

 

WARNING 

 

IT IS IMPERATIVE THAT THIS DEVICE BE 
INSTALLED BY A QUALIFIED TECHNICIAN. 

 

 

This device is designed to detect the insufficient 
evacuation of combustion gases in the event of a vent 
blockage. In such a case the thermal switch will shut 
down the oil burner. The device will then need to be 
re-armed MANUALLY. 

Refer to the wiring diagrams and the detailed 
instructions supplied with the BVSO for the installation 
and wiring procedure. The length of wires supplied 
with the unit is such that the safety device must be 
installed between the flue outlet of the appliance and 
the draft regulator, as indicated in the instructions. 

It is further imperative that the BVSO be maintained 
annually. Refer to the instructions supplied with the 
device and paragraph 24.1), p. 6 of this manual for 
more details. 

 

CAUTION 

A positive pressure venting system (Sealed 
Combustion System or Direct Vent) MUST NOT use 
the BVSO. Follow the instructions supplied with the 
venting system. 

 

10) CHIMNEY 

 

WARNING 

 

An oil-fired unit shall be connected to a flue 
having sufficient draft at all times to assure 
proper operation of the unit.

 

 

For information pertaining to chimney sizes, elevation, 
conditions, etc., see C.S.A. Standard B-139, 
"Installation code for oil burning equipment." 

 

11) CONTROLS 

 

Mount the aquastat control on the unit. Set operating 
control between 48°C (120°F) and 60°C (140°F). The 
latter being the maximum setting for models CM-32, 
CMO32 and CMO50.  

 

12)  BVSO PERFORMANCE TEST 

 

The purpose of the following test is to check that the 
electrical outlet on the furnace, designated to the BVSO, 
is functional. 

 

1. 

Start up the burner; 

2. 

Remove the three-pole plug from the BVSO outlet 
on the furnace; 

3. 

The burner must shut-off immediately. 

 

If the test is not in line with the above, call a 

QUALIFIED 

SERVICE TECHNICIAN

.

 

 

 CM-32/CMO32 

CMO50 

Sides 

5.08 cm   (2“) 

15.20 cm   (6“) 

Rear 

5.08 cm   (2“) 

15.20 cm   (6“) 

Top 

45.70 cm   (18") 

 45.70 cm   (18") 

Front 

61.00 cm   (24”) 

 61.00 cm   (24”) 

Flue 

   22.90 cm   (9") 

   22.90 cm   (9") 

Summary of Contents for CMO32

Page 1: ...its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THIS WATER HEATER AND KEEP THE DOCUMENT NEAR THE...

Page 2: ...nformation page of your manual close by in order to be able to provide the contractor with the required information such as the model and serial numbers of the water heater 2 LOCATION The water heater...

Page 3: ...uch a case the thermal switch will shut down the oil burner The device will then need to be re armed MANUALLY Refer to the wiring diagrams and the detailed instructions supplied with the BVSO for the...

Page 4: ...burner This return line must be the same size as the suction line At the beginning of every heating season have a qualified service technician check the entire oil distribution system for leaks 19 VEN...

Page 5: ...strainer cover taking care not to damage gaskets c Take out strainer cartridge and replace it annually d Re assemble strainer 25 1 BLOCKED VENT SHUT OFF BVSO CLEANING For continued safe operation the...

Page 6: ...uter liner Take off the insulation pad and remove the damaged chamber by sliding it out Install the new chamber Re install insulation outer liner access panel and burner Ensure that the insulation com...

Page 7: ...PART 2 INFORMATION Model Serial number Installation date Service telephone Day Night Dealer name and address START UP TEST RESULTS CO2 Stack temp Firing rate GPH Smoke Draft at stack Test performed b...

Page 8: ...3 8 31646 n a 3 3 8 31646 n a Nozzle Delavan 100 PSIG pump pressure 0 65 80W n a 0 65 80W n a RIELLO BURNER 40 F3 insertion tube 5 5 8 Nozzle Delavan n a 0 65 70A n a 0 65 70A Pump pressure n a 135 n...

Page 9: ...10 ELECTRICAL WIRING BECKETT BURNER DNS 0242 Rev D...

Page 10: ...11 ELECTRICAL WIRING RIELLO BURNER DNS 0769 Rev B...

Page 11: ...2 13 G14G007 GASKET 3 3 4 OD 1 ID LDPE WHITE 14 G99Z019 OVERFLOW TUBE 3 4 NPT x 42 15 G11F024 RELIEF VALVE 150 3 4x3 4 W 100XL 4 16 B10359 01 PANEL ASSEMBLY TOP FRONT 17 R02J008 WELL 3 4 NPT PLASTIC H...

Page 12: ...NTERIOR 14 B10368 HEAT CHAMBER AND INSULATION ASSEMBLY includes items 0 11 12 13 14 15 15 B10093 REFRACTORY HEAT CHAMBER 16 B10424 CASING INSULATION 17 B10366 CASING ASSEMBLY RIGHT SIDE 18 G99Z003 MAG...

Page 13: ...T PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES ULT RIEURES Attention Ne pas alt rer votre unit ou ses contr les Appeler un technicien q...

Page 14: ...s informer sur les items suivants i L interrupteur d alimentation lectrique ii La valve d arr t sur le r servoir de mazout iii Le filtre de mazout sur le conduit comment le changer une fois par ann e...

Page 15: ...OULEMENT BVSO Pour vacuation par chemin e MISE EN GARDE LE DISPOSITIF DOIT OBLIGATOIREMENT TRE INSTALL PAR UN TECHNICIEN QUALIFI Le dispositif est con u pour d tecter une mauvaise vacuation des gaz de...

Page 16: ...E Le r servoir d huile doit tre install sur un support convenable pour que celui ci ne s affaisse pas et la base doit tre d un mat riel non combustible Un robinet d arr t et un filtre l huile doivent...

Page 17: ...appelez un technicien qualifi 25 ENTRETIEN 1 Le chauffe eau et le tuyau central de celui ci devraient tre nettoy s tous les ans 2 L unit devrait tre vidang e mensuellement Si l eau est dure plus souv...

Page 18: ...r 11 Remontez le tout inversant la proc dure 27 CHAMBRE DE REMPLACEMENT Pour le remplacement de la chambre de combustion ouvrez le circuit lectrique du chauffe eau Enlevez le br leur ainsi que la port...

Page 19: ...8 31646 n a 3 3 8 31646 n a Gicleur Delavan 100 PSIG pression pompe 0 65 80W n a 0 65 80W n a BRULEUR RIELLO 40 F3 tube insertion 5 5 8 Gicleur Delavan n a 0 65 70A n a 0 65 70A Pression pompe n a 13...

Page 20: ...9 DIAGRAMME LECTRIQUE BR LEUR BECKETT DNS 0242 Rev D...

Page 21: ...10 DIAGRAMME LECTRIQUE BR LEUR RIELLO DNS 0769 Rev B...

Page 22: ...1 ID LDPE BLANC 14 G99Z019 TUBE TROP PLEIN 3 4 NPT X 42 BMI 08614 15 G11F024 VALVE SURPR 150 3 4x3 4 W 100XL 4 16 B10359 01 ASS PANNEAU DEVANT HAUT 17 R02J008 PUITS IMMER 3 4 NPT PLASTIQ HON 123870B 1...

Page 23: ...VIROLE INTERIEURE AVANT 14 B10368 ASSEMBLAGE FOYER ET ISOLATION comprend items 10 11 12 13 14 15 15 B10093 CHAMBRE EN REFRACTAIRE 16 B10424 ISOLATION CABINET 17 B10366 ASS CABINET COTE DROIT 18 G99Z00...

Reviews: