Operating Instructions CP MULTITHERM D.A HI

HOM161009163Ien-1

Page 5 / 8

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   [email protected]

NOTICE

Carefully remove

When removing from the packaging and during trans-
port, the connection line must not be stressed or bent.

For free convection, the heater needs to be installed with
ribs  standing  vertically.  The  minimum  distances  to  the
floor and to devices above it must be complied with. The
label needs to remain legible.

If  an  additional  TAE  thermostat  is  switched  in  series,
then  it  can  be  attached  to  the  surface  of  the  heater
(thermal coupling). The minimum distance also needs to
be adhered to here. Refer to the following drawing.

To  ensure  operational  safety,  the  heater  must  operate
under temperature conditions which will NOT exceed the
trigger temperature of the limiter.

The operating temperatures must be adhered to.

The  connection  cable  must  be  permanently  installed  up
to  the  inlet  into  the  on-site  junction  box,  taking  the  per-
missible bending radius = 5 x outer diameter into consid-
eration.

In  the  dust  Ex  area,  the  applicable  requirements  of  EN
60079-14 must be complied with.

Illustration 2: 

Installation example MULTITHERM with TAE or

TS and clearance

Additional  installation  material,  such  as  rails  or  panels
and also junction boxes, are not included in the standard
scope of delivery (see 

Installation accessories [

}

Page 4]

)

and must be ordered additionally.

8

Connection

 INFO

The device may only be connected up and secured by a
trained person, taking into account the "rated voltage"
and "rated current" specified on the nameplate.

Where  operating  voltage  =  measured  voltage  (rated
voltage),  then  the  heater  is  at  its  rated  output.  Mains
voltage fluctuations up to 10 % are then permissible.

For  protection  against  short  circuit  and  line  protection
you can use circuit breakers up to 10 A.

Additional  equipotential  bonding  is  required.  The  ter-
minal  block  designated  for  this  purpose  has  the  ground
sign.

Summary of Contents for CP MULTITHERM D.A HI

Page 1: ...Operating Instructions CP MULTITHERM D A HI HOM161009163Ien 1 01 06 2017...

Page 2: ...contents 1 General 3 2 Use 3 3 Explanation of symbols for warnings and signal words 3 4 Safety information 3 5 Installation accessories 4 6 Technical Data 4 7 Installation 4 8 Connection 5 9 Commissi...

Page 3: ...The SMART HEATER HI SYSTEM is used for demand ing heating tasks in explosive areas to maintain high temperatures in analytical instruments The temperature controller TC connected to the electrical hea...

Page 4: ...2 hexagon bolts 2 T head bolt type 28 15 M 6x15 4 M6 flat square nut 2 Washer shape A 6 4 4 Lock washers shape I 6 4 2 M6 hex nut If one of the components listed here is not included in the scope of d...

Page 5: ...es must be adhered to The connection cable must be permanently installed up to the inlet into the on site junction box taking the per missible bending radius 5 x outer diameter into consid eration In...

Page 6: ...versible damage to the heater and this would mean that the explosion protection can no longer be warranted The illustration may deviate from the heater 1 2 3 4 5 6 7 8 9 10 11 12 13 L N PE NTC RS 485...

Page 7: ...from bracket and remove it 13 Disposal Disassemble the components of the product taking the applicable local labour protection and environmental reg ulations into consideration and make sure that the...

Page 8: ...ir ectly contact INTERTEC Hess GmbH Raffineriestr 8 93333 Neustadt Donau Germany Phone 49 9445 9532 0 e mail info intertec info Website www intertec info Warranty The legally defined warranties and wa...

Reviews: