TOCSIN
650 OR
750 Series
Controller
L1
L2
Port 1 to 4
Drain Wires to Earth
Interconnecting Highway Cabling
For 2-Wire Addressable Systems:
For Safe Area Detectors Use 2
Core Cable 1.0 to 2.5mmSQ
Cable Depending on Distance.
Ensure Cable Screens are
Correctly Terminated and cables
are stripped to the enclosed
guide.
See Cable Calculator for Cable
Core Size vs Distance VS
Number of Devices
Cable Screen or
Drain Wire
Tubing 6 x 4 Polyurethane
Other Tube Options Available
Do Not Exceed 20M
A variety of End of Line Termination
Points Are Available Contact IGD For
Further Details
Refer to TOC-750 Series Sampler
Manual for Full Details
Connect screens as indicated to
ensure screen continuity
INSTALLATION REQUIREMENTS
FOR SAMPLERS