![International Gas Detectors TOC-635 Installer'S Manual Download Page 63](http://html1.mh-extra.com/html/international-gas-detectors/toc-635/toc-635_installers-manual_2079900063.webp)
GAS ALARM
TAG PLATE
20mm Plastic Conduit Mounted
Using Metal Saddles and Fixings
to be Compliant With BS7671
amendment 3 Reg 521.11.201
Note Conduit Size Large Enough
For One FP200 Cable Run and
Accessory Cable Type 4502 FE
DO NOT Attempt to Enlarge
20mm Entries, This Will
Invalidate Warranty and
Damage Enclosure Sealing.
IGD Supplied Beacon Sounders
PN 5083101Supplied With GAS
ALARM Legend. 2 off Can be
Run From Each Detector Node
Tag Plate Available as an
Option to Match Control
Panel Screen Display
Location Tags. If
Required Order as TOC-
TAG-A and supply Table
of Required Tag
Descriptions
Cabling Fitted to Tray
Using Stainless Steel
Cable Ties
Gas Detection Cabling Mounted to Existing
Containment For Fire/Security System
Accessory Cables
Typically Belden Style
Security Cable 4502
FE, Foil Screen, 4
Core and Drain Wire
0.33mmSQ
Preferred Cable Type 2 Core FP200
Min 1.5mmSQ, Check Cable Sizing to
IGD Guide
Suspended Ceiling Line
Installation to be in Accordance with BS6761 amendment 3 Reg 521.11.201,
BS EN 7671:2008, BS EN 50174-2, BS EN 6701:2016 and BS6739:2009
TYPICAL ROOM INSTALLATION
SCHEME F
Typical of Laboratories and Similar
Summary of Contents for TOC-635
Page 4: ...SECTION 1 MOUNTING DETAILS FOR EQUIPMENT...
Page 10: ...SECTION 2 SITING GAS DETECTORS...
Page 17: ...SECTION 3 GENERAL CABLING PRINCIPLES CABLE TYPES AND CABLE SIZING...
Page 24: ...SECTION 4 MAKING DEVICE CONNECTIONS TO DETECTOR NODES...
Page 43: ...SECTION 5 Control Panel Interfaces and Connections...
Page 67: ...Notes...