PELLISTOR (CATALYTIC) FLAMMABLE
GAS DETECTOR INTERFACE
P
Y
W
The Detector Node PCB is equipped with a Pellistor or Catalytic flammable gas detector
interface. This supports all IGD manufactured pellistors as indicated below. Note that the
correct pellistor option must be selected in the setup software routine for the pellistor to operate
correctly.
The Pellistor can be mounted remotely from the PCB. When doing so do not exceed the
indicated cable length.
For remote mounting use 1.5mmSQ Cable. Do not exceed 10M
V DC
Volts
Com
2.20
IGD Pellistors Supported
Type Head Head
Current Volts
MK3 ATEX EXD IIC T6 360mA 2.2V
MK6 Safe Area 170mA 2.5V
MK7 Safe Area 170mA 2.5V
MK8 ATEX 170mA 2.5V
In operation and with zero air applied correctly to the detector the ‘balance’ between the two detector
‘beads’ as measured P-Y and Y-W should not show a difference of more than 70mV. If the difference
is larger than this then it could be an indication of aging or damage and the detector should be
replaced.
This cable to the pellistor needs to
be screened cable type, typically FP
or CY. Use the commoning blocks
provided for cable screens
Summary of Contents for TOC-635
Page 4: ...SECTION 1 MOUNTING DETAILS FOR EQUIPMENT...
Page 10: ...SECTION 2 SITING GAS DETECTORS...
Page 17: ...SECTION 3 GENERAL CABLING PRINCIPLES CABLE TYPES AND CABLE SIZING...
Page 24: ...SECTION 4 MAKING DEVICE CONNECTIONS TO DETECTOR NODES...
Page 43: ...SECTION 5 Control Panel Interfaces and Connections...
Page 67: ...Notes...