Smoke Detectors
Smoke detectors are available as factory--installed options on
RGH models. Smoke detectors may be specified for Supply
Air only without or with economizer. All components
necessary for operation are factory--provided and mounted.
The unit is factory--configured for immediate smoke detector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
Units equipped with factory--optional Return Air smoke
detectors require a relocation of the sensor module at unit
installation. See Fig. 35 for the as shipped location.
Completing Installation of Return Air Smoke Sensor:
1. Unscrew the two screws holding the Return Air
Smoke Detector assembly. See Fig. 36, Step 1. Save
the screws.
2. Turn the assembly 90 degrees and then rotate end to
end. Make sure that the elbow fitting is pointing
down. See Fig. 36, Step 2.
3. Screw the sensor and detector plate into its operating
position using screws from Step 1. See Fig. 36, Step 3.
4. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Return Air
Smoke Detector
(as shipped)
C12282
Fig. 35 -- Return Air Smoke Detector, Shipping Position
Step 1
Step 2
Step 3
C12283
Fig. 36 -- Completing Installation of Return Air Smoke Sensor