International comfort products RGH072 Installation Instructions Manual Download Page 13

509 01 3808 00

13

Specifications are subject to change without notice.

Field--supplied flanges should be attached to horizontal

duct openings and all ductwork should be secured to the

flanges. Insulate and weatherproof all external ductwork,

joints, and roof or building openings with counter flashing

and mastic in accordance with applicable codes.

Do not cover or obscure visibility to the unit’s informative

data plate when insulating horizontal ductwork.

Step 8 — Install Outside Air Hood

Economizer and Two Position Damper Hood

Package Removal and Setup -- Factory Option

1. The hood is shipped in knock--down form and must be

field assembled. The indoor coil access panel is used as

the hood top while the hood sides, divider and filter are

packaged together, attached to a metal support tray

using plastic stretch wrap, and shipped in the return air

compartment behind the indoor coil access panel. The

hood assembly’s metal tray is attached to the basepan

and also attached to the damper using two plastic

tie--wraps.

2. To gain access to the hood, remove the filter access

panel. (See Fig. 8.)

3. Locate the (2) screws holding the metal tray to the

basepan and remove. Locate and cut the (2) plastic

tie--wraps securing the assembly to the damper. (See

Fig. 9.) Be careful to not damage any wiring or cut

tie--wraps securing any wiring.

4. Carefully lift the hood assembly (with metal tray)

through the filter access opening and assemble per the

steps outlined in

Economizer Hood and Two–Position

Hood,

below.

Economizer Hood and Two--Position Hood —
NOTE

: If the power exhaust accessory is to be installed

on the unit, the hood shipped with the unit will not be

used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.

1. The indoor coil access panel will be used as the top of

the hood. Remove the screws along the sides and bot-

tom of the indoor coil access panel. See Fig. 10.

2. Swing out indoor coil access panel and insert the hood

sides under the panel (hood top). Use the screws provid-

ed to attach the hood sides to the hood top. Use screws

provided to attach the hood sides to the unit. See Fig.

11.

3. Remove the shipping tape holding the economizer

barometric relief damper in place (economizer only).

4. Open the filter clips which are located underneath the

hood top. Insert the aluminum filter into the bottom

filter rack (hood divider). Push the filter into position

past the open filter clips. Close the filter clips to lock

the filter into place. See Fig. 12.

5. Insert the hood divider between the hood sides. See

Fig. 11 and 12. Secure hood divider with 2 screws on

each hood side. The hood divider is also used as the

bottom filter rack for the aluminum filter.

6. Caulk the ends of the joint between the unit top panel

and the hood top.

7. Replace the filter access panel.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

COMPRESSOR

ACCESS PANEL

C06023

Fig. 8 -- Typical Access Panel Locations

Hood Parts

Plastic Tie Wrap
Qty (2)

Screws for Metal Tray
Qty (2)

C08639

Fig. 9 -- Economizer and Two--Position Damper

Hood Parts Location

TOP

PANEL

INDOOR

COIL

ACCESS

PANEL

INDOOR

COIL

ACCESS

PANEL

CAULK

HERE

TOP

PANEL

C06025

Fig. 10 -- Indoor Coil Access Panel Relocation

Summary of Contents for RGH072

Page 1: ...stall Outside Air Hood 13 Economizer and Two Position Damper Hood Package Removal and Setup Factory Option 13 Economizer Hood and Two Position Hood 13 Step 9 Install Flue Hood 14 Step 10 Install Gas P...

Page 2: ...ability or operation FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Disconnect gas piping from unit when leak testing at pressure greater than 0 5 psig 3...

Page 3: ...Heat Exchanger Heating Capacity A Standard Static Motor B High Static Motor C Medium Static Motor Motor Options A None B Economizer w Barometric Relief OA Temp Sensor E Economizer w Barometric Relief...

Page 4: ...4 509 01 3808 00 Specifications are subject to change without notice Fig 1 RGH 072 102 Unit Dimensional Drawing sheet 1 of 2...

Page 5: ...509 01 3808 00 5 Specifications are subject to change without notice Fig 1 RGH 072 102 Unit Dimensional Drawing sheet 2 of 2...

Page 6: ...6 509 01 3808 00 Specifications are subject to change without notice Fig 2 RGH 110 120 Unit Dimensional Drawing sheet 1 of 2...

Page 7: ...509 01 3808 00 7 Specifications are subject to change without notice Fig 2 RGH 110 120 Unit Dimensional Drawing sheet 2 of 2...

Page 8: ...a tion requirements 2 Determine unit location from project plans or select unit location 3 Check for possible overhead obstructions which may interfere with unit lifting or rigging Step 1 Plan for Uni...

Page 9: ...cated ductwork at unit duct openings Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories Frame m...

Page 10: ...T WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION 1 DEC 2 DEC 3 DEC ANG MATERIAL AUTHORIZATION NUMBER TITLE 1029120 CURB ASY ROOF ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWI...

Page 11: ...cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in 458 mm of duct length from the unit basepan Insulate and weatherproof all external...

Page 12: ...ainst water from higher level runoff and overhangs UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage All panels must be in place when rigging Unit is not designed for ha...

Page 13: ...omizer Hood and Two Position Hood NOTE If the power exhaust accessory is to be installed on the unit the hood shipped with the unit will not be used and must be discarded Save the aluminum filter for...

Page 14: ...0 m above sea level The input rating for altitudes above 2000 ft 610 m must be derated by 4 for each 1000 ft 305 m above sea level For natural gas applications gas pressure at unit gas connection must...

Page 15: ...e embossed raised section of the unit basepan in the condenser section See Fig 15 LOW VOLTAGE CONDUIT CONNECTOR HIGH VOLTAGE CONDUIT CONNECTOR BRASS FITTING FOR 3 TO 6 TON UNITS C13410 Fig 15 Thru Bas...

Page 16: ...ly tape per manufacturer s instructions 4 Pressure test all gas piping in accordance with local and national plumbing and gas codes before connect ing piping to unit NOTE Pressure test the gas supply...

Page 17: ...in per 10 ft 25 mm in 3 m of run Do not use a pipe size smaller than the unit connection 3 4 in Step 12 Make Electrical Connections ELECTRICAL SHOCK HAZARD Failure to follow this warning could result...

Page 18: ...ly WARNING FIRE HAZARD Failure to follow this warning could result in personal injury death or property damage Do not connect aluminum wire between disconnect switch and RGS unit Use only copper wire...

Page 19: ...onnection and moving it to the 200 v 1 4 in male terminal on the primary side of the transformer Refer to unit label diagram for additional information Voltage to compressor terminals during operation...

Page 20: ...line side terminals on the unit mounted non fused disconnect switch this will provide service power to the unit when the unit disconnect switch is open Other connection methods will result in the conv...

Page 21: ...with the accessory Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions If the thermostat c...

Page 22: ...ise in space RH above control setpoint or a combination thermostat humidistat control device with isolated contact set for dehumidification control The humidistat is normally used in applications wher...

Page 23: ...iring for Hot Gas Re Heat Dehumidification System Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R THERMIDISTAT Unit CTB THERMOSTAT Connection not required Hot Gas Re Heat FIO...

Page 24: ...eturn Air smoke detectors require a relocation of the sensor module at unit installation See Fig 35 for the as shipped location Completing Installation of Return Air Smoke Sensor 1 Unscrew the two scr...

Page 25: ...inals marked OCCUPANCY on CTB Remove or cut jumper JMP 2 to complete the installation Step 14 Install Accessories Available accessories include Roof Curb Thru base connection kit must be installed bef...

Page 26: ...5 45 50 50 47 47 233 HIGH 45 50 47 258 48 60 51 262 460 3 60 STD 18 20 19 95 20 25 21 97 MED 19 25 20 114 21 25 22 116 HIGH 21 25 22 129 23 25 24 131 575 3 60 STD 13 15 13 77 17 20 17 81 MED 13 15 13...

Page 27: ...49 60 60 53 52 238 HIGH 49 60 52 263 53 60 57 267 460 3 60 STD 21 25 21 97 22 25 23 99 MED 21 25 22 116 23 25 24 118 HIGH 23 25 24 131 25 30 27 133 575 3 60 STD 14 15 15 79 18 20 19 83 MED 15 20 15 83...

Page 28: ...20 19 87 HIGH 16 20 16 92 19 25 21 96 RGH102 2 stage cool 208 230 3 60 STD 40 40 50 50 42 41 195 44 44 50 50 46 46 199 MED 41 41 50 50 43 43 199 45 45 50 50 47 47 203 HIGH 45 44 50 50 47 46 249 49 48...

Page 29: ...5 21 89 HIGH 17 20 18 94 21 25 23 98 RGH102 2 stage cool 208 230 3 60 STD 45 45 50 50 47 47 200 49 48 60 60 52 51 204 MED 46 46 50 50 49 48 204 50 50 60 60 53 53 208 HIGH 50 49 60 60 53 52 254 54 53 6...

Page 30: ...08 or 230 volts 3 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the percentage of voltage i...

Page 31: ...HIN SPECIFIED RANGE j CHECK GAS PIPING FOR LEAKS j CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE j CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE j VERIFY THAT UNIT IS LEVEL j CHECK FAN WHEE...

Page 32: ...ODE SUBCOOLER BY CLOSING HUMIDISTAT WITH Y1 CLOSED OBSERVE j A REDUCTION IN SUCTION PRESSURE 5 TO 7 PSI EXPECTED j B DISCHARGE PRESSURE UNCHANGED j C LIQUID TEMPERATURE DROPS TO 50 TO 55_F RANGE j D L...

Reviews: