International comfort products PH4E Series Installation Instructions Manual Download Page 15

15

513 01 3402 02

Indoor Airflow and Airflow Adjustments

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit

damage.
For heating and cooling operation, the recommended

airflow is 350 to 450 cfm for each 12,000 Btuh (165

L/s to 212 for each 3.5 kW) of rated cooling capacity.

For units with optional electric heat, the airflow must

not be reduced below the levels stated in Table 1.

CAUTION

!

NOTE

: Be sure that all supply

and return

air grilles are open,

free from obstructions, and adjusted properly.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Disconnect electrical power to the unit and install

lockout tag before changing blower speed.

!

WARNING

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Blue = Med Speed (if available)

Red = Low Speed

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Disconnect electrical power to the unit and install

lockout tag before changing blower speed.

!

WARNING

To change the speed of the indoor fan motor, remove the fan

lead from the splice connection. Replace with the desired fan

speed  lead. Insulate the unused lead to prevent shorting.

Table 4 – Wet Coil Air Delivery

ENGLISH
400 VOLT

UNIT

MOTOR

SPEED

EXTERNAL STATIC PRESSURE (in. W.C)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

PH4E24

Low

Watts

303

305

306

300

Cfm

969

879

785

687

High

Watts

435

428

428

422

Cfm

963

833

758

676

PH4E30

Low

Watts

1002

954

921

889

853

814

Cfm

1189

1115

1041

971

903

833

High

Watts

700

683

688

755

Cfm

1223

1142

1075

1058

PH4E36

Low

Watts

552

540

529

523

514

480

Cfm

1296

1237

1167

1097

1029

952

High

Watts

782

765

736

721

780

1002

Cfm

1467

1398

1321

1237

1165

1137

PH4E48

Low

Watts

692

686

678

664

652

664

736

Cfm

1571

1509

1444

1370

1295

1240

1237

High

Watts

1112

930

856

834

825

811

793

Cfm

1693

1670

1601

1521

1447

1378

1294

SI

400 VOLT

UNIT

MOTOR

SPEED

EXTERNAL STATIC PRESSURE (Pa)

0

25

50

75

100

125

150

175

200

225

250

PH4E24

Low

Watts

303

305

303

300

L/s

458

415

371

324

High

Watts

435

428

428

422

L/s

455

393

358

319

PH4E30

Low

Watts

1002

954

921

889

853

814

L/s

561

526

491

458

426

393

High

Watts

700

683

688

755

L/s

577

539

508

499

PH4E36

Low

Watts

552

540

529

523

514

480

L/s

612

584

551

518

486

449

High

Watts

782

765

736

721

780

1002

L/s

693

660

624

584

550

536

PH4E48

Low

Watts

692

686

678

664

652

664

736

L/s

741

712

681

647

611

585

584

High

Watts

1112

930

856

834

825

811

793

L/s

799

788

756

718

683

650

611

*Air delivery values are based on operating voltage of 400

v, wet coil, without filter or electric heater. 

NOTES: 1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh (165 L/s for each 3.5 kW) of rated cooling capacity. 

Evaporator coil frosting may occur at airflow below this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

Summary of Contents for PH4E Series

Page 1: ...Accessory Electric heaters Installation 10 Sequence of Operation 10 PRE START UP 13 START UP 13 Checking Cooling Heating Control Operation 13 Check for Refrigerant Leaks 13 PAGE Start Up Adjustments...

Page 2: ...and screws Although special care is taken to reduce sharp edges to a minimum be extremely careful when handling parts or reaching into the unit CAUTION INTRODUCTION The PH4E heat pump is fully self co...

Page 3: ...le materials Slab mounted units should be at least 4 in 102 mm above the highest expected water and runoff levels Do not use unit if it has been under water Step 4 Rig and Place Unit Rigging and handl...

Page 4: ...4 513 01 3402 02 FIGURE 3 MODEL SIZE 24 36 DIMENSIONS...

Page 5: ...5 513 01 3402 02 FIGURE 4 MODEL SIZE 48 DIMENSIONS...

Page 6: ...NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1...

Page 7: ...standards of the NFPA for installation of non residence type air conditioning and ventilating systems NFPA 90A or residence type NFPA 90B and or local codes and ordinances Select and size ductwork sup...

Page 8: ...ight seal 4 All units must have field supplied filters or accessory filter rack installed in the return air side of the unit Recommended sizes for filters are shown in Table 1 5 Size all ductwork for...

Page 9: ...to the unit ground screw in the control compartment or conduit approved for electrical ground when installed in accordance with NEC NFPA 70 National Fire Protection Association latest edition in Canad...

Page 10: ...rom transformer splice connection and connect black wire from transformer to splice connection Insulate unused blue transformer tap See transformer label During unit start up check secondary voltage t...

Page 11: ...4 15 4 5 9 3 7 34 4 15 4 5 9 4 7 44 INDOOR BLOWER Nominal Cooling Airflow CFM Nominal Cooling Airflow L s Size in Size cm Motor HP Motor W 800 378 10x10 25 4x25 4 1 4 187 1000 472 10x10 25 4x25 4 1 2...

Page 12: ...12 513 01 3402 02 FIGURE 12 Wiring Diagram 400 3 50...

Page 13: ...cellaneous loose parts have been removed 5 Each unit system has 2 Schrader type ports one low side Schrader fitting located on the suction line and one high side Schrader fitting located on the compre...

Page 14: ...a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airflow across either coil or both coils Proceed as follows 1 Remove cap from lo...

Page 15: ...ow Watts 303 305 306 300 Cfm 969 879 785 687 High Watts 435 428 428 422 Cfm 963 833 758 676 PH4E30 Low Watts 1002 954 921 889 853 814 Cfm 1189 1115 1041 971 903 833 High Watts 700 683 688 755 Cfm 1223...

Page 16: ...55 850 944 1038 7 5 8 2 9 2 10 4 11 7 12 9 14 9 16 7 18 7 Step 3 Defrost Control Quiet Shift Quiet Shift is a field selectable defrost mode which will eliminate occasional noise that could be heard at...

Page 17: ...esult in personal injury or death 1 Turn off electrical power to the unit and install a lockout tag before performing any maintenance or service on this unit 2 Use extreme caution when removing panels...

Page 18: ...l be sure to clean between the coils Be sure to flush all dirt and debris from the unit base Inspect the drain pan and condensate drain line when inspecting the coils Clean the drain pan and condensat...

Page 19: ...lly indicates a refrigerant leak If oil is detected or if low performance is suspected leak test all refrigerant tubing using an electronic leak detector or liquid soap solution If a refrigerant leak...

Page 20: ...4E including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charging Refrigerant PROPERTY HAZARD PERSONAL INJURY OR ENVIRONMENTAL...

Page 21: ...system charge so that pressure gauges read zero gauge Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liqu...

Page 22: ...ned to detect HFC refrigerant R 410A as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressure...

Page 23: ...nd correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refr...

Page 24: ...IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMP...

Reviews: