International comfort products NH4H4 Installation Instructions Manual Download Page 6

6

428 01 9702 01

Specifications subject to change without notice.

The defrost timer limits defrosting period to 10 minutes. Normally,

the frost is removed and the defrost thermostat contacts open to

terminate defrosting before 10 minutes have elapsed. When

defrosting is terminated, the outdoor

fan motor is energized, and

reversing valve solenoid is de

energized, returning unit to heating

cycle.

Reversing Valve

In heat pumps, changeover between heating and cooling modes is

accomplished with a valve that reverses flow of refrigerant in the

system. The reversing valve solenoid can be checked with the

power off using an ohmmeter. Check for continuity and shorting to

ground. With control circuit (24 v) power on, check for correct

voltage at solenoid coil, and for burned or overheated solenoid.
With unit operating, other items can be checked, such as frost or

condensate on refrigerant lines.
Using a remote measuring device, check inlet and outlet line

temperatures. Do not touch lines. If reversing valve is operating

normally, inlet and outlet temperatures on appropriate lines should

be similar. Any temperature difference would be due to heat loss or

gain across valve body. Temperatures are best checked with a

remote reading electronic

type thermometer with multiple probes.

Figures 7 and 8 show test points on reversing valve for recording

temperatures. Insulate points for more accurate reading. If valve is

defective:

1. Shut off all power to unit.
2. Remove all charge from system.
3. Remove valve using a tubing cutter.
4. Install new valve (wrap valve with a wet rag to prevent

overheating while brazing).

5. After valve is brazed in, check for leaks.
6. Evacuate and charge system. Operate system in both modes

several times to be sure valve functions properly.

LEGEND

TP — 

Test Point

A07433

Fig. 7

 - 

Reversing Valve

(Cooling Mode or Defrost Mode, Solenoid Energized)

LEGEND

TP — 

Test Point

A07434

Fig. 8

 - 

Reversing Valve

(Heating Mode, Solenoid De

energized)

Refrigerant Charging

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Wear safety glasses and gloves when handling refrigerant.

Do not overcharge system 

 this can cause compressor

flooding.

!

WARNING

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Service valves must be fully back

seated to close service

port. There is no Schrader valve at the service port, and

failure to back

seat the valve could result in loss of system

charge or personal injury.

NOTE

:  Do not vent or de

pressurize unit refrigerant to

atmosphere. Remove and recover refrigerant following accepted
practices.
All units are shipped with the refrigerant charge listed on the

nameplate.
Refer to Specification Sheet and consider the following when

working with R

410A refrigerant:

S

R

410A refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400
psig, DOT (Department of Transportation) 4BA400 or

DOT BW400.

S

R

410A systems should be charged with liquid refrigerant.

Use a commercial type metering device in the manifold

hose when charging into suction line with compressor op-

erating.

S

Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low

side retard.

S

Use hoses with 700 psig service pressure rating.

S

R

410A refrigerant, as with other HFCs, is only compat-

ible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Polyol Ester oils absorb moisture rapidly. Do not expose oil
to atmosphere.

S

Polyol Ester oils may cause damage to certain plastics and
roofing materials.

S

Wrap all filter driers and service valves with wet cloth when
brazing.

S

 factory approved, liquid

line filter drier is required on ev-

ery unit.

S

Do not use a TXV (thermostatic expansion valve) designed
for use with R

22 refrigerant. Refer to separate indoor unit

installation instructions for more details.

S

If using a suction line drier, do not leave in place for more
than 72 hours.

Summary of Contents for NH4H4

Page 1: ...all warnings or cautions included in literatureand attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current...

Page 2: ...nterchange components between the AccuRater device types Matching of outdoor unit with indoor unit may require field replacement of piston Replace piston if required before connecting refrigerant line...

Page 3: ...accessories If either refrigerant tubing or indoor coil is exposed to the atmosphere the system must be evacuated following good refrigeration practices Run refrigerant tubes as directly as possible a...

Page 4: ...ct in the unit control box as shown on the unit label diagram and Fig 5 Unit must be grounded LEGEND NEC National Electrical Code TB Terminal Board TB Connections Field Wiring Factory Wiring A07428 Fi...

Page 5: ...h opens WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death DO NOT attempt to simulate these system abnormalities high pressures pose a serious safet...

Page 6: ...ng Mode Solenoid De energized Refrigerant Charging WARNING PERSONAL INJURY AND OR EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result in personal injury and or equipment damage Wear sa...

Page 7: ...could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical sep...

Page 8: ...4X24 A EA 4X30 A EN A D 4X30 A EHD4X30A FEM4P30 A TXV FEM4X30 B FMA4P30 A TXV FMA4X30 A FM C U 4P30 A TXV FM C U 4X30 A FXM4X30 A 3 FS M U 4P30 A TXV EA 4X36 A EN A D W 4X36 A EHD4X36A FEM4P36 A TXV F...

Page 9: ...43 6 14 11 12 15 9 20 7 25 4 115 47 8 13 14 10 18 8 23 5 Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weight in NOTE Sup...

Page 10: ...10 428 01 9702 01 Specifications subject to change without notice Copyright 2015 International Comfort Products Lewisburg TN 37091 USA...

Reviews: