International comfort products NH4H4 Installation Instructions Manual Download Page 2

2

428 01 9702 01

Specifications subject to change without notice.

INSTALLATION

IMPORTANT

: Effective January 1, 2015, all split system and

packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
R

410A refrigerant systems operate at higher pressures than

standard R

22 systems. Do not use R

22 service equipment

or components on R

410A refrigerant equipment.

PERSONAL INJURY AND EQUIPMENT DAMAGE

HAZARD

Failure to follow this caution may result in personal injury

and / or equipment damage.

DO NOT

 operate the unit without a filter or with grille

removed.

CAUTION

!

COMPLETE PRE

INSTALLATION CHECKS 

Unpack Unit

Move the unit to final location. Remove unit from carton, being

careful not to damage service valves and grilles.

Inspect Shipment

File a claim with the shipping company if shipment is damaged or

incomplete. Check the unit nameplates to ensure units match job

requirements.

Consider System Requirements

Consult local building codes and NEC for special installation

requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant

piping, and servicing unit. Locate unit so that condenser airflow is

unrestricted on both sides.
Unit may be mounted on a level pad directly on base legs or

mounted on raised pads at support points.

Matching the Heat Pump to an Indoor Unit

The NH4H4 heat pump units can be matched to corresponding

indoor units. The NH4H4 unit can be matched with under

ceiling

and residential fan coils and evaporator coils. Refer to separate

indoor unit literature for more information.

Expansion Device 

 Ducted System Cooling Mode

A hard shutoff, thermostatic expansion valve (TXV) is required at

the indoor section of the system for proper operation of these

products. If the indoor section of the system is not equipped with a

hard shutoff TXV, refer to Spec Sheet for the correct TXV kit to be

installed. Follow the instructions in the kit for proper installation.

Check AccuRater Metering Device 

 Heating Mode

The correct AccuRater (bypass type) refrigerant control is required

for system capacity optimization. An AccuRater device with

field

replaceable piston is supplied with the outdoor unit (see Fig.

2).

Do not

 interchange components between the AccuRater device

types. Matching of outdoor unit with indoor unit may require field

replacement of piston. Replace piston, if required, before

connecting refrigerant lines. See Fig. 2. Piston replacement

instructions are included in the indoor unit installation instructions.
After system installation is complete, see the Refrigerant Charging

section in this document to check and/or adjust refrigerant charge.

*

NOTE: 

Piston Orientation - Install tapered end

of piston in the direction of the outdoor equipment
for proper heating operation

*

A07407b

Fig. 2

 - 

AccuRater (bypass type)

Metering Device Components

RIG AND MOUNT UNIT

Mounting on Ground

Mount unit on a solid, level concrete pad. Position unit so water or

ice from roof does not fall directly onto unit. Use field

provided

snow stand or ice rack where prolonged subfreezing temperatures

or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6

field

supplied tie

down bolts should be used and fastened through

slots provided in unit mounting feet.

Mounting on Roof

Mount unit on a level platform or frame at least 6 in. (152.4 mm)

above roof surface. Isolate unit and tubing from structure.

Clearance Requirements

Single Unit Applications: With coil facing wall: Allow 6” (152.4

mm) minimum clearance on coil side and coil end and 20” (504.0

mm) minimum clearance on fan side. Allow 24” (609.6 mm)

minimum clearance on compressor end for service.  

With fan facing wall: Allow 8” (203.2 mm) minimum clearance on

fan side and coil end and 20” (504.0 mm) minimum clearance on

coil side. Allow 24” (609.6 mm) minimum clearance on

compressor end for service when units are stacked or there is less

than 40” (1016 mm) of clearance above the unit. If there is 40”

(1016 mm) clearance above unit and the top panel is accessible for

removal allow 8” (203.2 mm) minimum clearance on compressor

end for service.

Multi

unit  Applications: Allow 24” (609.6 mm) minimum

clearance between fan and coil sides of multiple units. Arrange

units so discharge of one does not enter inlet of another. Allow 24”

(609.6 mm) minimum clearance on compressor end when units are

stacked or there is less than 40” (1016 mm) of clearance above the

unit. If there is 40” (1016 mm) clearance above unit and the top

panel is accessible for removal allow 8” (203.2 mm) minimum

clearance on compressor end for service.   

When two units are installed end to end with the coil ends facing

each other allow 12” (304.8 mm) minimum clearance between

units.

IMPORTANT

: When installing multiple units, ensure the

discharge air from one unit is not drawn into another unit. When

installing single or multiple units in an alcove, roof well, or

partially enclosed area, ensure there is adequate ventilation to

prevent recirculation of discharge air.

Summary of Contents for NH4H4

Page 1: ...all warnings or cautions included in literatureand attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current...

Page 2: ...nterchange components between the AccuRater device types Matching of outdoor unit with indoor unit may require field replacement of piston Replace piston if required before connecting refrigerant line...

Page 3: ...accessories If either refrigerant tubing or indoor coil is exposed to the atmosphere the system must be evacuated following good refrigeration practices Run refrigerant tubes as directly as possible a...

Page 4: ...ct in the unit control box as shown on the unit label diagram and Fig 5 Unit must be grounded LEGEND NEC National Electrical Code TB Terminal Board TB Connections Field Wiring Factory Wiring A07428 Fi...

Page 5: ...h opens WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death DO NOT attempt to simulate these system abnormalities high pressures pose a serious safet...

Page 6: ...ng Mode Solenoid De energized Refrigerant Charging WARNING PERSONAL INJURY AND OR EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result in personal injury and or equipment damage Wear sa...

Page 7: ...could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical sep...

Page 8: ...4X24 A EA 4X30 A EN A D 4X30 A EHD4X30A FEM4P30 A TXV FEM4X30 B FMA4P30 A TXV FMA4X30 A FM C U 4P30 A TXV FM C U 4X30 A FXM4X30 A 3 FS M U 4P30 A TXV EA 4X36 A EN A D W 4X36 A EHD4X36A FEM4P36 A TXV F...

Page 9: ...43 6 14 11 12 15 9 20 7 25 4 115 47 8 13 14 10 18 8 23 5 Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weight in NOTE Sup...

Page 10: ...10 428 01 9702 01 Specifications subject to change without notice Copyright 2015 International Comfort Products Lewisburg TN 37091 USA...

Reviews: