background image

443 06 4003 00

11

Specifications  subject to change without notice.

6. Remove cap that conceals adjustment screw for gas

valve regulator. (See 

Figure 23

)

7. Turn adjusting screw using supplied ADJUSTING KEY

either counterclockwise (out) to decrease input rate or

clockwise (in) to increase rate. (See 

Figure 21

)

8. Replace cap and check rate. Cap MUST be in place to

actuate regulator.

9. Repeat Steps 5 through 8 until correct input rate is

obtained.

Figure 21

Manifold Pressure Adjustment Key

ON/OFF SWITCH

INLET 
PRESSURE TAP

REGULATOR PLUNGER 

ADJUSTING KEY 

GAS PRESSURE 
REGULATOR 

MANIFOLD  
PRESSURE TAP 

BURNER REFERENCE
PRESSURE TAP

A11509

NOTE

:  Gas valve LP/NAT cap MUST be in place with LP

arrow pointing toward gas valve when checking input rate.

When correct input is obtained, main burner flame should be
clear blue, almost transparent (See 

Figure 22

). Be sure cap is

in place when finished.

Figure 22

Burner Flame

Burner Flame

Burner

Manifold

A11461

When correct input is obtained, make sure cap that conceals

gas valve regulator adjustment screw is oriented properly for

propane (LP) gas. The LP arrow should be pointing toward gas

valve. (See 

Figure 21

)

10. Remove jumper across R and W thermostat connections

to terminate call for heat.

11. Turn furnace gas valve control knob or switch to OFF

position.

12. Turn gas supply manual shutoff valve to OFF position.
13. Turn off furnace power supply.
14. Remove manometer and replace manifold pressure tab

plug. (See 

Figure 21

)

15. Turn furnace gas valve switch to ON position.
16. Turn on furnace power supply.
17. Set room thermostat to call for heat.

!

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury

and/or death.
NEVER test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections. A fire or

explosion may result causing property damage, personal

injury or loss of life.

!

AVERTISSEMENT

RISQUE D’EXPLOSION ET D’INCENDIE

Le fait de ne pas suivre cet avertissement pourrait entraîner

des dommages corporels et / ou la mort.
Ne jamais examiner pour les fuites de gaz avec une flamme

vive. Utilisez plutôt un savon fait specifiquement pour la

détection des fuites de gaz pour verifier tous les connections.

Un incendie ou une explosion peut entrainer des dommages

matériels, des blessures ou la mort.

18. Check pressure tap plug for gas leaks when main

burners ignite.

19. Check for correct burner flame.
20. Observe unit operation through two complete heating

cycles.

21. See Sequence of Operation in furnace Installation,

Start

Up, and Operating Instructions.

22. Set room thermostat to desired temperature.
23. After making the required manifold pressure

adjustments, check and adjust the furnace temperature

rise per the furnace installation instructions.

CHECK LOW GAS PRESSURE SWITCH

The newly installed low gas pressure switch is a safety device

used to guard against adverse burner operating characteristics

that can result from low gas supply pressure. Switch opens at

not less than 6.5 in. w.c. and closes at not greater than 10.2 in.

w.c.
This switch also prevents operation when the propane tank

level is low which can result in gas with a high concentration of

impurities, additives, and residues that have settled to the

bottom of the tank. Operation under these conditions can

cause harm to the heat exchanger system. This normally open

switch closes when gas is supplied to gas valve under normal

operating pressure.
The closed switch completes control circuit. Should an

interruption or reduction in gas supply occur, the gas pressure

at switch drops below low gas pressure switch setting, and

switch opens. Any interruption in control circuit (in which low

gas pressure switch is wired) quickly closes gas valve and

stops gas flow to burners. When normal gas pressure is

restored, the system must be electrically reset to re

establish

normal heating operation.
Before leaving installation, observe unit operation through two

complete heating cycles. During this time, turn gas supply to

gas valve off just long enough to completely extinguish burner

flame, then instantly restore full gas supply. To ensure proper

low gas pressure switch operation, observe that there is no gas

supply to burners until after hot surface igniter begins glowing.

LABEL APPLICATION

1. Fill in Conversion Responsibility Label (337991

101)

previously applied to inside of main furnace door by

installer. Date, name, and address of organization

Summary of Contents for NAHB00101MH

Page 1: ...hat may apply Follow all safety codes In the United States follow all safety codes including the current edition of the National Fuel Gas Code NFGC NFPA No 54 ANSI Z223 1 In Canada refer to the curren...

Page 2: ...Gas to Propane SECTION III Conversion from Propane to Natural Gas SECTION I INITIAL KIT INSTALLATION Procedure 1 General A downflow furnace application is where furnace blower is located above combust...

Page 3: ...SING IS NOT INSTALLED NOT SHOWN 1 Accessory floor base MUST be used Review floor base Installation Instructions before installation 2 Secure accessory floor base to structure using 5 16 in 8 mm lag sc...

Page 4: ...tor harness from gas valve Disconnect wires from Hot Surface Igniter HSI and Flame Sensor See Figure 9 8 Support the manifold and remove the four 4 screws that secure the manifold assembly to the burn...

Page 5: ...igure 8 for label location 1 Attach Conversion Responsibility Label 340323 101 inside of main furnace door See Figure 7 Date name and address of organization making this conversion are required See Fi...

Page 6: ...n furnace rating plate is for installations at altitudes up to 2000 ft 610 M In the U S A the input rating for altitudes above 2000 ft 610 M must be reduced by 2 percent for each 1000 ft 305 M above s...

Page 7: ...Figure 14 Igniter Position Back View 2 1 2 in 64 4 1 1 4 in 31 8 A11405 Figure 15 Igniter Position Side View A12392 2 in 2 5 mm 3 8 in 3 16 in 0 8 1 5 50 mm 9 6 mm 4 6 mm 3 32 in 1 32 3 64 in Figure 1...

Page 8: ...iels des blessures ou la mort 2 Apply pipe dope sparingly to the male threads of the 1 8 in black iron street elbow Install the street elbow into the gas valve inlet pressure tap Point the open end of...

Page 9: ...re 9 2 Align the orifices in the manifold assembly with the support rings on the end of the burner 3 Insert the orifices in the support rings of the burners Manifold mounting tabs should fit flush aga...

Page 10: ...osition CHECK FURNACE AND MAKE ADJUSTMENTS 1 Be sure main gas and electric supplies to furnace are off 2 Remove 1 8 in 3 mm pipe plug from manifold pressure tap on downstream side of gas valve 3 Attac...

Page 11: ...lamme vive Utilisez plut t un savon fait specifiquement pour la d tection des fuites de gaz pour verifier tous les connections Un incendie ou une explosion peut entrainer des dommages mat riels des bl...

Page 12: ...by manifold pressure and orifice size Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft 610 M In the U S A the input rating for altitudes above 2000 ft 610M must...

Page 13: ...e 1 8 in NPT pipe plug from the tee fitting on the Low Gas Pressure Switch 5 Remove the Low Gas Pressure Switch from fittings on gas valve and discard 6 Remove remaining fittings from gas valve and di...

Page 14: ...with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal inj...

Page 15: ...for gas meter test dial to complete one revolution e Refer to Table 4 for cu ft of gas per hr f Multiply gas rate cu ft hr X heating value Btu cu ft using natural gas heating value from local gas uti...

Page 16: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 17: ...3 3 42 3 4 2134 700 43 3 5 43 3 7 43 3 8 42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44...

Page 18: ...313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120...

Reviews: