background image

6

Table 3 – 3–Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

Connect Control Wiring

Route 24v control wires through control wiring grommet and

connect leads to control wiring. See Thermostat Installation
Instructions for wiring specific unit combinations. (See Fig. 11.)
Use No. 18 AWG color–coded, insulated (35

°

C minimum) wire. If

thermostat is located more than 100 ft (30.5 m) from unit, as
measured along the control voltage wires, use No. 16 AWG

color–coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 2 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

24 VAC HOT

R

C

W2

Y

G

R

C

RVS COOLING

C

W2

HP THERMOSTAT

 TYPICAL

FAN COIL

HEAT 

PUMP

G

O

E

W2

E

W3

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT

STAGE 1

INDOOR FAN

EMERGENCY

HEAT

O

*
*
*

 IF AVAILABLE

*

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

A02325 / A97413

Fig. 11 – Generic Wiring Diagrams

(See thermostat Installation Instructions

for specific unit combinations)

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a

minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to

outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft (23.4 m), or when outdoor unit is 20 ft (6.09 m) below indoor
unit. Refer to the Residential Piping and Long Line Guideline.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.

Start–Up

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury,

equipment damage or improper operation.

S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Do not disable low pressure switch in scroll compressor

applications.

S

Compressor dome temperatures may be hot.

Follow these steps to properly start up system:

1. After system is evacuated, fully open liquid and vapor ser-

vice valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to
refrigerant flow (back seated). Replace caps finger–tight and

tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control to

ON or AUTO mode, as desired. Operate unit for 15
minutes. Check system refrigerant charge.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 42801510700

Replaces: New

Summary of Contents for N4H4-G

Page 1: ...o follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing or operating refrigerant compressors Pressurized mi...

Page 2: ...ance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in...

Page 3: ...evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected To Factory Approved Indoor Unit Outdoor unit contains approximate system refrigerant charge for op...

Page 4: ...loth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR Connection Diameter Tube Diameter...

Page 5: ...power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect uni...

Page 6: ...e electrical disconnect to outdoor unit A crankcase heater is required if refrigerant tubing is longer than 80 ft 23 4 m or when outdoor unit is 20 ft 6 09 m below indoor unit Refer to the Residential...

Page 7: ...tactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on to continue warming conditioned spaces To initiate defrost the defr...

Page 8: ...able 7 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcooling temperature at a specific li quid line pressure add refri...

Page 9: ...EHD4X24AAL EN A D 4X36L21 EHD4X36AAL 3 EN A D W 4X48L21 EHD4X48AAL FEM4X24 BL EHD4X30AAL EN A D W 4X36L17 EHD4X42AAL 5 EHD4X42AAL EHD4X60AAL 3 FMA4P18 A FEM4P30 AL EHD4X30AAL FEM4P36 AL EHD4X48AAL FE...

Page 10: ...3 WLN C W 424CA WLNC484DA WAHL184B WLNC304BA WLNC304BA WLN C W 424CA 3 WLN C W 484CA WLN C W 604DA 3 WAHL244B WAPL304A WLN C W 364BA WAPL364A WLNC484DA WAPL484A FMA4P18 A WAHL304B WLNC364CA WAPL424A...

Page 11: ...3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F outdoor ambient and 80 F dry bulb...

Page 12: ...180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S R 410A refrigerant as with other HFCs...

Reviews: