background image

5

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Installation of filter drier in liquid line is required.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used (see triple evacuation

procedure in service manual). Always break a vacuum with dry
nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and

liquid water. A tight dry system will hold a vacuum of 1000
microns after approximately 7 minutes. (See Fig. 8.)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

2000

M

ICRO

NS

2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 8 – Deep Vacuum Graph

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, makings sure wire ties on feeder tubes are
secure and tight.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
Do not supply power to unit with compressor terminal box

cover removed.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440–14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit
control box.

Connect Ground and Power Wires

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 9.

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 9 – Line Connections

A00010

Fig. 10 – 3–Phase Monitor Control

(Applies to 3–Phase Units Only)

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 42801510700

Replaces: New

Summary of Contents for N4H4-G

Page 1: ...o follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing or operating refrigerant compressors Pressurized mi...

Page 2: ...ance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in...

Page 3: ...evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected To Factory Approved Indoor Unit Outdoor unit contains approximate system refrigerant charge for op...

Page 4: ...loth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR Connection Diameter Tube Diameter...

Page 5: ...power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect uni...

Page 6: ...e electrical disconnect to outdoor unit A crankcase heater is required if refrigerant tubing is longer than 80 ft 23 4 m or when outdoor unit is 20 ft 6 09 m below indoor unit Refer to the Residential...

Page 7: ...tactor is energized Defrost mode is identical to cooling mode except that outdoor fan motor stops and second stage heat is turned on to continue warming conditioned spaces To initiate defrost the defr...

Page 8: ...able 7 Find the point where required subcooling temperature intersects measured liquid service valve pres sure 6 To obtain required subcooling temperature at a specific li quid line pressure add refri...

Page 9: ...EHD4X24AAL EN A D 4X36L21 EHD4X36AAL 3 EN A D W 4X48L21 EHD4X48AAL FEM4X24 BL EHD4X30AAL EN A D W 4X36L17 EHD4X42AAL 5 EHD4X42AAL EHD4X60AAL 3 FMA4P18 A FEM4P30 AL EHD4X30AAL FEM4P36 AL EHD4X48AAL FE...

Page 10: ...3 WLN C W 424CA WLNC484DA WAHL184B WLNC304BA WLNC304BA WLN C W 424CA 3 WLN C W 484CA WLN C W 604DA 3 WAHL244B WAPL304A WLN C W 364BA WAPL364A WLNC484DA WAPL484A FMA4P18 A WAHL304B WLNC364CA WAPL424A...

Page 11: ...3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3 6 8 Optimum performance point 82 F outdoor ambient and 80 F dry bulb...

Page 12: ...180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S R 410A refrigerant as with other HFCs...

Reviews: