background image

INSTALLATION INSTRUCTIONS

3-phase R-22 Split System Heat Pump

8

506 01 5001 00

H. EVACUATING LINE SET AND INDOOR COIL

The unit is shipped with a factory refrigerant charge. The
liquid line and suction line service valves have been
closed after final testing at the factory. Do not disturb
these valves until the line set and indoor coil have been
evacuated and leak checked, or the charge in the unit
may be lost.

NOTE:

 Do not use any portion of the factory charge for

purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Never use the outdoor unit compressor as a vacu‐
um pump. Doing so may damage the compressor.

Line set and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. If
deep vacuum equipment is not available, the alternate
triple evacuation method may be used by following the
specified procedure.

If vacuum must be interrupted during the evacuation
procedure, always break vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump
capable of pulling a vacuum to 500 microns and a vacuum
gauge capable of accurately measuring this vacuum
level. The deep vacuum method is the most positive way
of assuring a system is free of air and water.

Watch the vacuum gauge as the system is pulling down.
The response of the gauge is an indicator of the condition
of the system (refer to Figure 9).

With no leaks in the system, allow the vacuum pump to
run for 30 minutes minimum at the deep vacuum level.

Figure 9

Deep Vacuum Gauge Response

and System Conditions

500

MINUTES

0

1

2

4

6

1000

1500

LEAK IN
SYSTEM

VACUUM TIGHT
TOO WET

TIGHT
DRY SYSTEM

2000

M

ICRONS

2500

3000

3500

4000

4500

5000

3

7

5

Triple Evacuation Method

The triple evacuation method should only be used when
system does not contain any water in liquid form and
vacuum pump is only capable of pulling down to 28 inches
of mercury. Refer to Fig. 10 and proceed is as follows:

1.

Pull system down to 28 inches of mercury and
allow pump to continue operating for an additional
15 minutes.

2.

Close manifold valves or valve at vacuum pump
and shut off vacuum pump.

3.

Connect a nitrogen cylinder and regulator to
system and fill with nitrogen until system pressure
is 2 psig.

4.

Close nitrogen valve and allow system to stand for
1 hour. During this time, dry nitrogen will diffuse
throughout the system absorbing moisture.

5.

Repeat this procedure as indicated in Figure 10.

6.

After the final evacuate sequence, confirm there
are no leaks in the system. If a leak is found, repeat
the entire process after repair is made.

Figure 10

Triple Evacuation Sequence

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

I. OPENING SERVICE VALVES

Outdoor units are shipped with a refrigerant charge
sealed in the unit. Opening the service valves releases
this charge into the system.

NOTE:

 Open the Suction service valve first. If the Liquid

service valve is opened first, oil from the compressor may
be drawn into the indoor coil TXV, restricting refrigerant
flow and affecting operation of the system.

Remove Suction service valve cap and insert a hex
wrench into the valve stem. Hold the valve body steady
with an end-wrench and back out the stem by turning the
hex wrench counterclockwise. Turn the stem until it just
contacts the rolled lip of the valve body.

After the refrigerant charge has bled into the system,
open the Liquid service valve.

Summary of Contents for H2H3 Series

Page 1: ...manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labe...

Page 2: ...r runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined areas where re...

Page 3: ...it System Heat Pump 506 01 5001 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Page 4: ...orms that are self supporting and span several load bearing walls These suggestions are to minimize noise and vibration transmission through the structure If the structure is a home or apartment avoid...

Page 5: ...in the field use dehydrated or dry sealed deoxidized copper refrigeration tubing Do not use copper water pipe Do not remove rubber plugs or caps from copper tubing until connections are ready to be ma...

Page 6: ...ION UNIT OPERATION HAZARD Failure to follow this caution may result in improp er product operation Do not bury more than 36 of line set underground Refrigerant may migrate to cooler buried section dur...

Page 7: ...g against inside of piston body 3 Find plastic bag taped to unit containing copper adapter tube with brass nut 4 Install adapter tube against retainer and thread brass nut onto liquid service valve Ti...

Page 8: ...2 4 6 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500 5000 3 7 5 Triple Evacuation Method The triple evacuation method should only be used when sys...

Page 9: ...nces Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground rod Supply Vol...

Page 10: ...ircuit Connections LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR C W 2 L G Y E O R C W 2 L G Y E O R ODT...

Page 11: ...door fan motor lead from OF2 on control board refer to Figure 15 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in hea...

Page 12: ...Operate unit a minimum of 10 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operate in low speed when outdoor ambient temperature is below 82 F Pull one of the...

Page 13: ...satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipped with a time delay relay circuit the blower runs an additional length of...

Page 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC S...

Page 15: ...estriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT 1...

Page 16: ...R and C are reverse wired TRIP LED and ALERT LED flashing together Verify R and C terminals are supplied with 19 28VAC ALERT Flash Code 3 Compressor short cycling displayed incorrectly Verify Y termi...

Reviews: