440 01 1051 02

Specifications are subject to change without notice.

CIRCULATION AIR BLOWER DATA (CFM & L/s)

*9MPX060F12

 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

1478

697

1204

568

901

425

703

332

0.2

50

1418

669

1154

545

864

408

649

306

0.3

75

1350

637

1103

521

818

386

588

277

0.4

100

1280

604

1053

497

765

361

538

254

0.5

125

1201

567

993

469

720

340

488

230

0.6

149

1116

527

924

436

672

317

459

217

0.7

174

1023

483

846

399

620

293

408

193

0.8

199

931

439

764

361

558

263

365

172

0.9

224

825

389

683

322

489

231

317

150

1

249

730

345

590

278

428

202

233

110

*9MPX080J12

 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

1456

687

1326

626

1123

530

976

461

0.2

50

1440

680

1312

619

1112

525

941

444

0.3

75

1420

670

1280

604

1085

512

909

429

0.4

100

1379

651

1241

586

1043

492

870

411

0.5

125

1325

625

1209

571

1002

473

818

386

0.6

149

1261

595

1155

545

952

449

784

370

0.7

174

1208

570

1082

511

893

421

714

337

0.8

199

1115

526

1001

472

792

374

640

302

0.9

224

1007

475

868

410

702

331

567

268

1

249

830

392

746

352

608

287

491

232

NOTE: (1) Data Based on Bottom Only or One Side return.

(2) Gray area is above maximum temperature rise range.

# CFM 

 Cubic Feet Per Minute airflow. Filter required for each

return

air inlet.

Airflow perfomance includes 1” (25.4mm) washable [600 FPM (3.0

m/s) max] filter media.

Bellyband Location on Motor 

 A Dimension

A

Model

*9MPX

inches

mm

060F12

1

3

/

8

35.1

080J12

1

7

/

8

46

080J20

1

7

/

8

46

100L20

1

5

/

8

41.9

*9MPX080J16 

(1)(2) * Denote Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

2032

959

1690

798

1246

588

922

435

0.2

50

1952

921

1650

779

1250

590

898

424

0.3

75

1874

884

1601

756

1226

579

872

412

0.4

100

1785

842

1533

723

1187

560

838

395

0.5

125

1688

797

1462

690

1151

543

806

380

0.6

149

1593

752

1381

652

1090

514

769

363

0.7

174

1482

699

1287

607

1014

479

711

336

0.8

199

1360

642

1182

558

918

433

643

303

0.9

224

1231

581

1053

497

790

373

570

269

1

249

1052

496

850

401

678

320

488

230

*9MPX100L20

 (1)(2) * Denotes Brand

Exterrnal

 Static Pressure

(in wc/Pa)

Speed

Tap

HI

MED H

MED L

LO

in wc

Pa

CFM

L/s

CFM

L/s

CFM

L/s

CFM

L/s

0.1

25

2240

1057

2137

1008

1993

941

1820

859

0.2

50

2163

1021

2062

973

1934

913

1768

834

0.3

75

2083

983

1992

940

1872

883

1722

813

0.4

100

2002

945

1916

904

1801

850

1656

782

0.5

125

1912

902

1833

865

1723

813

1590

750

0.6

149

1821

859

1745

824

1636

772

1513

714

0.7

174

1727

815

1654

781

1547

730

1426

673

0.8

199

1618

764

1551

732

1437

678

1325

625

0.9

224

1502

709

1430

675

1315

621

1199

566

1

249

1356

640

1275

602

1159

547

1047

494

MAX CFM’s for Factory Washable  Filters

Filter  Size  (in/mm)

CFM

L/s

14

 X 25

/ 356 x 635

1400

661

16

 X 25

/ 406 x 635

1600

755

20

 X 25

/ 508 x 635

2000

944

24

 X 25

/ 610 x 635

2500

1180

Max CFM based on 600 FPM (3.0 m/s)

NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s). These filters

only allow half the airflow when compared to 600 FPM (3.0 m/s) filters.

Summary of Contents for C9MPX

Page 1: ...Installation Requirements 4 INSTALLATION 6 Combustion Ventilation Air 10 Vent Combustion Air Piping 14 Concentric Vent Termination 32 Gas Supply and Piping 34 Electrical Wiring 39 Ductwork and Filter...

Page 2: ...t above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in...

Page 3: ...ondensate Drain Trapped Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and Adjustments Section...

Page 4: ...sult in personal injury death and or property damage This furnace is not designed for use in mobile homes trailers or recreational vehicles WARNING CUT HAZARD Failure to follow this caution may result...

Page 5: ...following 1 Thoroughly read this manual and labels on the unit This will help you understand how your unit operates and the hazards involved with gas and electricity 2 Do not use this unit if any part...

Page 6: ...ing could result in personal injury or death Do NOT operate furnace in a corrosive atmosphere containing chlorine fluorine or any other damaging chemicals which could shorten furnace life Refer to Com...

Page 7: ...g ignition input rate temperature rise and venting according to these instructions CARBON MONOXIDE POISONING HAZARD FaiIure to follow this warning could result in personal injury or death Do NOT opera...

Page 8: ...panels Note On the Direct Vent furnace the vent pipe attaches to the furnace through the side panels The combustion air pipe attaches to the top panel or to the alternate location on the side panel O...

Page 9: ...111 16 175 16 215 8 21 4 131 4 24 47 8 215 8 17 8 297 8 273 16 913 16 3311 16 KO KO KnockOut 609 6 30 2 249 2 31 7 73 549 3 27 109 5 122 2 758 8 690 6 549 3 855 7 439 7 42 9 123 8 177 8 47 6 469 9 723...

Page 10: ...the National Fuel Gas Code NFGC ANSI Z223 1 NFPA 54 2009 in the U S 2 Sections 8 2 8 3 8 5 8 6 8 7 and 8 8 of National Standard of Canada Natural Gas and Propane Installation Code NSCNGPIC CSA B149 1...

Page 11: ...one permanent outdoor opening is used the opening requires a 1 sq in of free area per 3 000 BTUH 7 cm2 kW for combined input of all gas appliances in the space see Table 1 and b not less than the sum...

Page 12: ...75 kW 100 000 BTU 29 300 kW 125 000 BTU 36 625 kW ft3 m3 0 60 1 050 29 7 1 400 39 2 1 750 49 1 250 35 1 875 52 5 2 500 70 3 125 87 5 0 50 1 260 35 3 1 680 47 04 2 100 58 8 1 500 42 2 250 63 3 000 84 3...

Page 13: ...QUIRED based on good trade practices local codes and good judgement of the installer Manufacturer does NOT take responsibility for modifications made to existing equipment CARBON MONOXIDE POISONING HA...

Page 14: ...1527 __ F628 D2468 D2661 D2235 PVC D1785 D2241 F891 D2466 D2665 F656 D2564 CPVC F441 F442 F438 F493 ABS to PVC D3138 NOTE 1 In Canada all pipe fittings cements must conform to applicable CSA standards...

Page 15: ...ion such as Armaflex or other equivalent type of insulation 3 Insulate combustion air inlet piping when run in warm humid spaces Sizing Combustion Air and Vent Pipe Consult Table 3 select the proper d...

Page 16: ...water heater vent or other appliance s direct vent intake or exhaust 12 30 cm 12 30 cm N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exha...

Page 17: ...dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exhaust O Cle...

Page 18: ...prevent kinking buckling of the drain tube The clip should remain in the furnace between the door switch plate and the blower shelf Figure 10 during operation See Figure 20 for proper routing and ins...

Page 19: ...in tube will exit Install casing grommet black rubber 5 8 15 9mm ID grommet in loose parts bag Install the 1 2 CPVC street elbow on discharge of trap Install the black PVC tube connector 3 4 18 1mm PV...

Page 20: ...ain tee Install Vent Pipe grommet in side of casing Cut an appropriate length of 2 50 8mm PVC pipe long enough to exit the cabinet and connect the vent drain to either A standard field supplied 2 50 8...

Page 21: ...screws Move the caps to the top of the trap and mount the trap externally to the left side of the unit using the two 2 screws provided Cut the 5 8 15 9mm ID corrugated hose as shown above and fasten...

Page 22: ...burner compartment to the blower compartment and secure with screws Move the caps to the top of the trap and mount the trap externally to the right side of the unit using the two 2 screws provided Co...

Page 23: ...ther with the 2 short 1 2 12 7mm ID elbow tubes and connect the lower discharge port of the vent drain to the trap Secure all connections with clamps Install the vent pipe grommet into the casing Cut...

Page 24: ...t Mount the trap externally to the bottom side of the unit using the two screws provided in the location shown Cut the corrugated tube as shown in the illustration above Connect the corrugated hose fr...

Page 25: ...and secure with screws Remove knockout from the side of the furnace casing where drain tube will exit Mount the trap externally to the bottom side of the unit using the two screws provided in the loca...

Page 26: ...nockout from the side of the furnace casing where drain tube will exit Mount the trap externally to the bottom side of the unit using the two screws provided in the location shown Cut the corrugated t...

Page 27: ...to the bottom side of the unit using the two screws provided in the location shown Cut the corrugated tube as shown in the illustration above Connect the corrugated hose from the transition to the tr...

Page 28: ...e furnace for the application Preassemble the vent and combustion air piping from the furnace to the vent termination Do not cement the pipe joints until the pipe preassembly process is complete Combu...

Page 29: ...llow primer to dry before applying cement 3 Apply a thin coat of cement evenly in the socket Quickly apply a heavy coat of cement to the pipe end and insert pipe into fittings with a slight twisting m...

Page 30: ...IN 12 304 8mm MIN Vertical Termination 1 Figure 25 shows the proper installation and clearances for vertical vent termination The vertical roof termination should be sealed with a plumbing roof boot o...

Page 31: ...or 2 503 8mm maximum separation 25 22 02d Vent Combustion Air Exhaust 1 25 4mm Maximum Exhaust A A Inlet Figure 28 Sidewall Inlet Vent and Exhaust Air Termination Dimension A is touching or 2 50 8mm m...

Page 32: ...diction gas inspection authority municipal building department fire department etc should be consulted before installation to determine the need to obtain a permit Consignes sp ciales pour l installat...

Page 33: ...OTE A field supplied stainless steel screw may be used to secure the rain cap to the pipe instead of cementing when field disassembly is desired for cleaning See Figure 34 If assembly needs to be exte...

Page 34: ...snow level or grade whichever is greater 1 25 4mm max 12 304 8mm min 8 Install the rain cap and the small diameter pipe assembly in the Y concentric fitting and the large pipe assembly Ensure that the...

Page 35: ...ll the gas pipe grommet to the furnace side panel with the gas pipe entry If needed remove the 2 50 8mm hole plug from the plastic accessory bag and relocate to the open hole in the furnace side panel...

Page 36: ...ane gas is recommended Propane Conversion An accessory kit shall be used to convert to propane gas use see the furnace rating plate for the Propane conversion accessory kit part number FIRE EXPLOSION...

Page 37: ...to 914 4m column in Table 6 and Table 7 Table 7 LPG or PROPANE GAS MANIFOLD PRESSURE in wc HEATING VALUE BTU CU FT FURNACE INPUT BTU BURNER MEAN ELEVATION FEET ABOVE SEA LEVEL ft m 0 to 2000 2001 to...

Page 38: ...perly sized orifices 4 Tighten orifices so it is seated and gas tight See Figure 39 5 Reinstall manifold Ensure burners do NOT bind on new orifices Natural Gas Input Rating Check SEE CHECKS AND ADJUST...

Page 39: ...using two self tapping screws from bag 6 Apply two hole plugs from bag at left J Box location Thermostat Thermostat location has an important effect on the operation of the unit Follow instructions i...

Page 40: ...on outlet side of furnace 3 For furnaces installed without a cooling coil it is recommended that the outlet duct be provided with a removable access panel This panel should be accessible when the fur...

Page 41: ...with a minimum of 1 25 4mm insulation with indoor type vapor barrier Filters A Filter must be used Filters are not supplied with these furnaces but can be purchased from the distributor Use either fil...

Page 42: ...uct flanges on the furnace MUST be broken down to provide proper fit up to the subbase Use duct pliers to bend the duct flanges flat onto the furnace casing DO NOT bend the duct flanges inward toward...

Page 43: ...d on the right side of the furnace in order to run the copper or plastic tubing for the condensate drain line Checks and Adjustments NOTE Verify the input rate of the furnace FIRE OR EXPLOSION HAZARD...

Page 44: ...he smallest dial on the gas meter to make one complete revolution Refer to Example NOTE If meter uses a 2 cubic foot dial divide results seconds by two Example BTUH Natural Gas BTU Content No of Secon...

Page 45: ...g motor speed lead Note For motors with 4 speed leads it will be necessary to tape off the terminal of the motor speed lead removed from the Heat or Cool terminal with electrical tape since an open te...

Page 46: ...ntinuously while there are no other blower demands from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired m...

Page 47: ...ff fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediately following power reset then replace control...

Page 48: ...48 440 01 1051 02 Specifications are subject to change without notice Wiring Diagram 9MPX...

Page 49: ...change without notice Models Dual Certified 9MPX060F12A2 9MPX080J12A2 9MPX080J16A2 9MPX100L20A2 Denotes Brand Save This Manual For Future Reference 95 Furnace Upflow Horizontal Downflow International...

Page 50: ...7 423 3 2 797 2 9 722 1 9 473 2 0 498 3 2 797 2 9 722 1 9 473 2 0 498 3 2 797 2 9 722 2 3 573 2 4 598 3 2 797 2 9 722 Limits Controls Rollout Switch oF oC Limit Control Setting oF oC Auxilliary Switc...

Page 51: ...3 0 m s max filter media Bellyband Location on Motor A Dimension A Model 9MPX inches mm 060F12 13 8 35 1 080J12 17 8 46 080J20 17 8 46 100L20 15 8 41 9 9MPX080J16 1 2 Denote Brand Exterrnal Static Pre...

Page 52: ...ied installer service agency local gas supplier or your distributor or branch for information or assistance The qualified installer or agency must use only factory authorized and listed kits or access...

Reviews: