TROUBLESHOOTING

   

  SYMPTOM 

CAUSE(S) 

CORRECTIVE ACTION

 

 

1.  Filter Pump will not start 

1a. Defective thermostat 

Replace thermostat

    when temp. is below 32˚F. 

1b. Defective relay 

Replace relay

     

1c. Faulty wiring 

Check wiring

     

1d. Power outage 

Install stand-by power

  2.  Time Switch will not keep time 

2a. Frequent power outages 

Reset dial

    -dial is turning. 

2b. Wrong voltage/cycle 

Change clock motor

     

2c. Loose clock motor connections 

Check connections

  3.  Time Switch Dial stops at ON  

3a. Loose tripper 

Check/change tripper

    or OFF tripper. 

3b. Bent dial 

Check/change mechanism

     

3c. Defective motor 

Change clock motor

  4.  Load is ON at all times - dial is 

4a. Welded contacts 

Change mechanism

    turning. 

4b. Two ON-trippers on dial 

Change tripper

     

4c. Defective mechanism 

Change mechanism

 

120 VOLT WIRING

Interconnecting wiring diagram between Model PF1103 or PF1103M Freeze 

Protection Control and a 120 volt Time Switch and 120 volt Filter Pump

1.
2.

PF1103 FREEZE PROTECTION CONTROL

120 VOLT TIME SWITCH OR AIR SWITCH