background image

ET8415CR

Contact Ratings:    

UL

CSA 

Load Type

Voltage

Frequency

30 Amp

30 Amp

Resistive

120/240 VAC

60 Hz

20 Amp

20 Amp

Resistive

28 VDC

– 

30 Amp

30 Amp

Inductive

120/240 VAC

60 Hz

20 Amp

20 Amp

Ballast

120-277 VAC

60 Hz

5 Amp

5 Amp

Tungsten

120/240 VAC

60 Hz

1 HP

1 HP

Motor

120 VAC

60 Hz

2 HP

2 HP

Motor

240 VAC

60 Hz

4.5 Amp

Electronic Ballast

120-277 VAC

60 Hz

Input Voltage:  

120 -277 VAC, 50/60 Hz 

Power Consumption:  

7 Watts maximum

Contact Configuration:  

SPST x4 

Pulse Feature:  

2-second pulse option for contactor and bell ringing applications.

Auto DST:  

Automatic adjustment for Daylight Saving Time

Supercapacitor Backup:  

  100 hour supercapacitor maintains date and accurate time. Supercapacitor fully 

recharges in 30 minutes.

Wiring Terminals: 

#18 to #10 AWG wire

Minimum ON/OFF Time: 

1 minute

Maximum ON/OFF Time:  

6 days, 23 hours 59 minutes

Warranty: 

Limited 1 year

Model Number

Circuits

Switch

Volts AC

Rating

Enclosure

Shipping Weight

ET8415CR*

4

SPST

120-277

30 Amps

Type 3R Steel

3.7 lbs. (1.7 kg)

*Can be wired to DPST

Specification

The 7-Day Astronomic electronic-type time switch shall be capable of permitting up to 28 ON/28 OFF events. In  

addition, the time switch shall include selectable Astronomic (sunrise/sunset) settings for each day and circuit to allow 

load switching at sunset and/or sunrise without a photo control device. The time switch shall provide a minimum ON or 

OFF time of 1 minute. The time switch to be powered by ___ (120)(208)(240)(277) VAC, ___ (50)(60) Hz power supply. The 

time switch mechanism features a snap-in design to provide easy mechanism removal for mounting the enclosure. The 

time switch enclosure shall be a Type 3R Steel lockable enclosure that shall be painted with an electrostatic process to 

eliminate the potential for corrosion. The time switch shall provide clear terminal identification on a see-through  

non-curling terminal insulator. Terminal connections shall provide secure connections for wire sizes up to #10 AWG.  

Switch configuration shall be _____ (SPST)(DPST) with a UL or CSA listed switch rating of:
   

• Resistive: 30 Amps @ 120/240 VAC

   

• Resistive: 20 Amps @ 28 VDC

   

• Inductive: 30 Amps @ 120/240 VAC

   

• Tungsten: 5 Amps @ 120/240 VAC

   

• Ballast: 20 Amps @ 120-277 VAC

   

• Motor: 1 HP @ 120 VAC

   

• Motor: 2 HP @ 240 VAC 

The time switch shall be UL or CSA listed under UL category 916 Energy Management Equipment and shall be  

Intermatic model ET8415CR.

www.intermatic.com

 

Energy Controls

300ET10048

ET8415CR

Reviews: