background image

Mount the enclosure in the desired location using the 3 mount-

5. 

ing holes provided.

Position at eye level if possible, providing space to the left of 
the enclosure for the cover to swing open fully, as shown.

Replace the mechanism in the enclosure.

6. 

Lift the left side of the plastic insulator off the retaining post and 

7. 

pivot it up and away to expose the terminal strip.
Strip the supply and load wires to 1/2”.

8. 

Use AWG#10-#18 copper conductors only.

Knockouts

Mounting holes

1

Neutral

120VAC 

Input

Hot

2

3

4

Timer Power

Load

Install jumper 

only if timer input 

and load voltage 

are the same

ET1705 configured for SPST, 120 VAC load

1

Line 2

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Load 

2

Timer Power

ET1715 configured for SPDT load switching

1

Line 2

240VAC Input

Line 1

2

3

4

5

6

Line 1

Line 2

Install jumper only if timer input 

and load voltage are the same

Timer Power

Load

ET1725 configured for 240VAC DPST load  

with jumper set to SIM

1

Line 2

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

ON

Install jumper only if timer input 

and load voltage are the same

OFF

Timer Power

ET1725 configured for pulse SPST load  

with jumper set to PUL

1

Line 2

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Timer Power

Load 

2

ET1725 configured for 2 SPST loads  

with jumper set to IND

1

Line 2

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Timer Power

Load 

2

ET1725 configured for DPST loads  

with jumper set to SIM

Mounting 

hole

Knockouts

Mounting 

hole

Insert the wire ends under the proper terminal plates (see wir-

9. 

ing diagrams elsewhere on this page) and tighten the screws 
firmly. 
Connect ground wire to grounding terminal at bottom of enclosure.

10. 

Replace the plastic insulator on the retaining post.

11. 

Remove the battery case by sliding it down as shown by the 

12. 

arrows, then install 2 AAA alkaline batteries. Make sure the 
batteries are pointing in the direction shown.
Verify that the display is 

13. 

ON

 to make sure the batteries are OK.

If the display shows scrambled information, press the RESET 
button to clear it up.

Apply power to the Time Switch.

14. 

IMPORTANT: 

15. 

Press and hold the 

ENTER

 button, then press the 

RESET

 button. The screen will flash 12:00 AM and MON, and 

timer status is Manual Mode.

NOTE: You must reset the time switch using this procedure 
whenever you change the jumpers.

The Time Switch is now ready for programming.

Programming Overview

By pressing the 

MODE

 button, the Time Switch will cycle through the 

menus necessary for programming the current time, date, and timed 
events.
The basic procedure is to use the 

MODE

 button to move from one 

menu to the next (e.g., DATE, TIME, etc.), the 

+

 or 

– 

buttons for the 

first part of a setting (e.g., MONTH), the 

ENTER

 button to move to 

the next part of the setting (e.g., YEAR), then 

MODE

 to exit and move 

to the next menu. To skip a menu, press 

MODE

 to move ahead.

If you make a mistake, press the 

MODE

 button repeatedly to cycle 

back around to the error, then make the correct entry. 
NOTE:
 DATE and TIME must be set before you can access any 
other programming menus.

1 – Setting Date

Press the 

1. 

MODE

 button repeatedly until the words SET and 

DATE appear in the upper area of the display.
Press the 

2. 

+

 or 

 buttons to enter the current Month.

Press the 

3. 

ENTER

 button when the Month is correct to save the 

setting. The screen advances to current Date.
Again press the 

4. 

+

 or 

– 

buttons to enter the current Date, fol-

lowed by the 

ENTER

 button.

Repeat to set the correct Year.

5. 

Press the 

6. 

MODE

 button to exit and advance to setting the time.

Reviews: