EM1400 Series Installation Guide

Dual Voltage Input Card

120v or 277v

Lighting Relays:

Normally Closed (NCL)
30A @ 277Vac Ballast
20A @ 120Vac Tungsten
20A @ 347Vac Ballast
SCCR 18Ka @ 277Vac 
Rated 250,000 Cycles

Relay Status LED

LED is ON when the relay is 
OFF (the relay is NC).

Smacker Strip

provides relay coils with 
power so that they can be 
controlled by the control 
card

High Voltage Barrier:

(16 gauge steel)

Power Supply Card

Supplies power to the 

different cards inside the 

relay panel

Electronics Backplate:

(when open exposes the 

high voltage backplate) 

High voltage - low voltage 

barrier

High Voltage Backplate 

Mixed voltages are 
allowed (120v and 277v) 
in accordance with the 
NEC and local code 
requirements.

Electronics Backplate 

High voltage - low voltage barrier

Programming Buttons

(in 

Master Panel only)

:

Scroll and tab to access 
control features for the 
system

Assign Button:

Used to assign an address or 
change an existing address 
to the relay control card

Zone Buttons:

To enable the zone buttons 
push and hold assign button 
for 10 sec. The push 2, 4, 
6, 2, 6. Repeat twice to get 
back to discreet mode.

Contact Closure Address 
Button:

Assign/change an address or 
existing address on optional 
contact closure input portion 
of the relay control card.

Contact Closure Inputs:

 14 

programmable/global inputs

DTC Clock 

(in Master Panel only)

:

32-channel, 365-day astro 

clock to access and program 

the entire system

Photocell Input

(in Master Panel only)

:

Outdoor photocell input

Relay Control Card:

Manual control and network 

control of individual relays

Manual Control Buttons 

(Relays 1-16)

Toggles each relay ON and 
OFF. When the pilot LED is 

ON, the Relay Status LED 

is OFF (“Relay Status LED”

 

below) 

 Digital Bus Connectors:

Two RJ45 connectors

Panel Details

Summary of Contents for EM1400 SERIES

Page 1: ...ing Schematic 7 Trouble Shooting 8 The EM1400 series is a programmable relay panel with 8 or 16 relays A master panel can stand alone or can control up to 16 digital devices photocell cards digital sw...

Page 2: ...iate lugs and Neutral and Ground as indicated 1 2 3 Do not power up the panel electronics until the bus has been activated see the Quick Start Guide You can check for faults while landing conductors o...

Page 3: ...ve the chassis from the enclosure Avoid rubbing the sides of the chassis against the enclosure Store the chassis in the original shipping case or any safe location until needed 1 2 3 4 1 2 Control of...

Page 4: ...orth Electronics Backplate Neutral Hot Relay 1 To Load Overview Line Low Voltage Connections The EM1400 digital bus allows up to 16 digital devices not including photo cells or contact closures device...

Page 5: ...s Contact Closure Inputs 14 programmable contact inputs can control any relay s in any panel s for manual on off or over ride Use shielded cable for distances over 150 feet Connect the drain wire to t...

Page 6: ...ramming Buttons in Master Panel only Scroll and tab to access control features for the system Assign Button Used to assign an address or change an existing address to the relay control card Zone Butto...

Page 7: ...ive 2 Zones 9 16 Active 4 6 8 10 Discrete Mode 12 8 Zone Mode 14 16 Zone Mode 16 1 3 5 7 9 11 13 15 Optional Input Address Assign Input 4 1 Photocell Input DualVoltage Input Card Power Supply Card Xfo...

Page 8: ...ss an override switch is acti vated the relay will turn off 1 1 1 2 2 2 3 3 Online Bus Connector A B 12 Gnd Hand Auto Switch Zone 2 Zone 4 Zone 6 Zone 8 Zone 1 Zone 3 Zone 5 Zone 7 Assigns relays to a...

Reviews: