background image

 

2 / 6 

P/N 466-

2934 • REV A • ISS 26MAY17 

• 

Avoid locations that expose the sensors to possible false 
alarm sources such as: 
- Glass airlocks and vestibule areas 
- Kitchens 
- Corner mountings 
- Residential car garages 
- Small utility rooms 
- Stairwells 
- Bathrooms 
- Small acoustically live rooms 

Coverage range 

The sensors are omnidirectional, providing 360° coverage. 
Coverage is measured from a sensor to the point on the glass 
farthest from the sensor. The sensors can be mounted as 
close as 3.3 ft. (1 m) from the glass. The maximum range 
depends on the type of glass being protected: 

Armor-coated glass 

Mount the sensors no more than 12 ft. (3.65 m) from the glass. 

Plate, tempered, laminated, and wired glass 

When the sensors are mounted on the ceiling or the opposite 
or adjoining wall, (Figure 2 below) maximum range is 25 ft. 
(7.5 m). 

Figure 2: Maximum coverage range 

 

Testing 

Test the sensor upon installation and if the window glass-type 
is changed. 

The sensors are designed to detect the breaking of framed 
glass mounted in an outside wall. Testing the sensors with 
unframed glass, broken bottles, etc., may not trip the sensors. 
The sensors typically do not trip to glass breaking in the middle 
of the room. To verify sensor range and operation, you need to 
use the UTC Fire & Security 5709C hand-held tester. 

Test mode 

To put the sensors in test mode, do the following: 

1.  Connect a 9-volt battery to the sensor for pretesting. 

2.  Temporarily mount sensor in the desired location. 

3.  Use the 5709C hand-held tester to put the sensor into test 

mode. Set the tester to tempered glass and hold the tester 
on top of the sensor (Figure 3 below). Activate the tester, 
this will trip the sensor into test mode for one minute. In 

test mode, the LED will blink continuously. To extend test 
time, activate the tester at least once a minute. 

When the system is armed and the sensor trips to an alarm 
condition, the LED will light solid for four seconds and then 
revert back to a one minute test mode. At the end of one 
minute, the LED will extinguish if it is in 

set up LED

 mode, or 

the LED will light if it is in 

latching LED

 

mode. 

Figure 3: Activating test mode 

 

Sensor test 

Before you can test the sensors, they must be in test mode 
(blinking). To test the sensors, do the following: 

1.  Choose the laminated setting on the tester. 

2.  Hold the tester near the surface of the glass to be 

protected and aim the speaker at the sensor. Be sure the 
tester is at the point on the glass farthest from the sensor. 
If closed drapes or curtains are present, hold the tester 
behind them (Figure 4 below). 

Figure 4: Testing behind curtains 

 

3.  Press the test button on the tester. The LED on the sensor 

should stay on for four seconds to indicate the glass is 
within detection range of the sensor. If the LED does not 
stay on for four seconds, move the sensor and retest. 

For latching LED, provide a power reset by removing power 
and resetting the LED. 

 

25 ft. (7.5 m)

25 

ft. (

7.5

 m)

Hold tester so that the speaker is
within 1 inch of sensor microphone.

In test mode the sensor LED will light
solid for about 4 seconds, 
then blink for about a minute.

1 inch

 

Summary of Contents for ShatterPro II

Page 1: ...in direct line of sight of the glass to be protected However since sound travels out from a broken window a position 8 ft 2 4 m into the room provides better detection The mounting location can affect sensor detection ability To ensure optimum performance the coverage zone width should be no greater than two times the distance from the sensor to the closest point of glass For instance if a sensor ...

Page 2: ...ed location 3 Use the 5709C hand held tester to put the sensor into test mode Set the tester to tempered glass and hold the tester on top of the sensor Figure 3 below Activate the tester this will trip the sensor into test mode for one minute In test mode the LED will blink continuously To extend test time activate the tester at least once a minute When the system is armed and the sensor trips to ...

Page 3: ...ifications Voltage 9 to 16 VDC Current Typical Maximum 15 mA 25 mA Relay output On resistance Off resistance Normally closed open 4 seconds upon alarm 10 Ω 5 10 1 MΩ Maximum loop rating 16 VDC 50 mA relay Detection range 3 3 to 25 ft 1 to 7 5 m 360 Minimum glass size 12 by 24 in 0 3 by 0 6 m Recommended glass thickness Plate Tempered Wired Laminated 3 32 to 1 4 in 2 4 to 6 4 mm 1 8 to 1 4 in 3 2 t...

Page 4: ...E G THROUGH NOTICE THAT INTERLOGIX NO LONGER PROVIDES FIRMWARE UPDATES OR BUG FIXES MAY RESULT IN REDUCED PERFORMANCE MALFUNCTION AND OR INCREASED VULNERABILITY TO HACKING COMPROMISE AND OR CIRCUMVENTION INTERLOGIX DOES NOT ENCRYPT COMMUNICATIONS BETWEEN ITS ALARM OR SECURITY PANELS AND THEIR OUTPUTS INPUTS INCLUDING BUT NOT LIMITED TO SENSORS OR DETECTORS UNLESS REQUIRED BY APPLICABLE LAW AS A RE...

Page 5: ...NGE WITHOUT NOTICE UPDATED INFORMATION CAN BE FOUND AT WWW UTCFSSECURITYPRODUCTS EU PRODUCT WARNING INTERLOGIX ASSUMES NO RESPONSIBILITY FOR INACCURACIES OR OMISSIONS AND SPECIFICALLY DISCLAIMS ANY LIABILITIES LOSSES OR RISKS PERSONAL OR OTHERWISE INCURRED AS A CONSEQUENCE DIRECTLY OR INDIRECTLY OF THE USE OR APPLICATION OF ANY OF THE CONTENTS OF THIS DOCUMENT THIS PUBLICATION MAY CONTAIN EXAMPLES...

Page 6: ...6 6 P N 466 2934 REV A ISS 26MAY17 ...

Reviews: