background image

 

P/N 1077877 

• REV 2 • ISS 19MAR19 

 

5 / 6 

bar LED graph should either be OFF or only the first LED 
should be intermittently ON. 

2.  Conduct a series of impacts along the protected surface 

while observing the bar LED graph. Look for a response 
on the bar LED that illuminates the first 4 red LEDs, plus 
the yellow and green LEDs and 1 to 3 of the upper level 
red LEDs. Ideally, the 10th LED will not illuminate. (The 
yellow LED indicates the signal is near the alarm 
Threshold, and the Green LED indicates the signal has 
exceeded the Threshold.) 

3.  If the signal response always illuminates the 10th LED, 

lower the Gain 1 level and repeat the test OR if the signal 
response does not illuminate the Green LED and at least 1 
of the upper red LEDs, increase the gain 1 level and 
repeat the test. When the response is consistently above 
the Green LED and at, or below, the 10th red LED, the 
Gain is optimized for the installation. 

Setting the Climb alarm parameters (sustained attack) 

1.  Use S1 to set the Climb time parameter (the duration of a 

sustained attack that must occur within the Time Window 
to cause an alarm). 

2.  Use S2 to set the Time Window (the period in which the 

time specified by the Climb setting must accumulate, or 
the time in which the specified number of Cuts must occur 
to cause an alarm). 

3.  Conduct a series of simulated attacks along the protected 

surface while observing the bar LED graph. If the sensor 
does not detect and alarm for some of the simulated 
attacks, raise the Gain 1 level and repeat the tests. 

4.  If the attack simulations always cause alarms, use these 

settings and monitor the system for nuisance alarms. If the 
nuisance alarm rate (NAR) is too high, lower the Gain 1 
level. 

5.  Repeat this process until the sensor always detects the 

simulated attacks, and the NAR is acceptable. 

Setting the Cut alarm parameters (impact attack) 

1.  Use S3 to set the number of impacts required to cause an 

alarm (the impacts must occur within the Time Widow 
setting). 

2.  Simulate a series of impact attacks along the protected 

surface while observing the bar LED graph. Look at the 
bar LED for a response that is above the Threshold 
(Green LED ON) for each impact. 

3.  If the impact attack simulations always cause alarms, use 

these settings and monitor the system for nuisance 
alarms. If the nuisance alarm rate (NAR) is too high, lower 
the Gain 1 level. If the processor does not always alarm 
for the impact attack simulations raise the Gain 1 level. 

4.  Repeat this process until the sensor always detects the 

simulated attacks, and the NAR is acceptable. 

Connecting the Universal Configuration 
Module 

For UCM calibration, set switch S5-4 to OFF, and cycle the 
power. 

Switch 5-4 must be OFF to operate with UCM configuration 
parameters. 

Remove the enclosure cover and connect the UCM computer 
to the processor via USB (T1). 

Start the UCM software (the UCM Connect dialog displays). 

The FlexPI Status window opens.

Select the Network Type: Silver Network

Select the Device Type: FlexPI

Select the connection type USB

Select Connect to establish a 

connection to the processor

 

Note: 

Select F1 to launch the UCM online help file. 

Regulatory information 

 

Manufacturer 

PLACED ON THE MARKET BY: 
UTC Fire & Security Americas Corporation, Inc. 
3211 Progress Drive, Lincolnton, NC, 28092, 
USA 

AUTHORIZED EU REPRESENTATIVE: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Product warnings 
and disclaimers 

 

THESE PRODUCTS ARE INTENDED FOR 
SALE TO AND INSTALLATION BY QUALIFIED 
PROFESSIONALS. UTC FIRE & SECURITY 
CANNOT PROVIDE ANY ASSURANCE THAT 
ANY PERSON OR ENTITY BUYING ITS 
PRODUCTS, INCLUDING 

ANY “AUTHORIZED 

DEALER” OR “AUTHORIZED RESELLER”, IS 
PROPERLY TRAINED OR EXPERIENCED TO 
CORRECTLY INSTALL FIRE AND SECURITY 
RELATED PRODUCTS. 

For more information on warranty disclaimers and 
product safety information, please check 

https://firesecurityproducts.com/policy/product-
warning/

 or scan the QR code. 

Certification 

 

European Union 
directives 

UTC Fire & Security hereby declares that this 
device is in compliance with the applicable 
requirements and provisions of the Directive 
2014/30/EU and/or 2014/35/EU. For more 
information see www.utcfireandsecurity.com or 
www.interlogix.com. 

 

2012/19/EU (WEEE directive): Products marked 
with this symbol cannot be disposed of as 
unsorted municipal waste in the European Union. 
For proper recycling, return this product to your 
local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated 
collection points. For more information see: 
www.recyclethis.info 

Additional information 

For further details on the products, please refer to the product 
information included in the UCM software CD (DF950CM). 

For contact information see our Web site: 

utcfssecurityproducts.eu

 o

www.interlogix.com

 

For customer support, see

 www.interlogix.com/customer-

support

  

 

Copyright © 2011 UTC Fire & Security. All rights reserved. 

Summary of Contents for FlexPI

Page 1: ... roofs with wooden trusses cable spacing app 60 cm 2 ft fastened every 30 cm 1 ft The minimum recommended cable spacing is 30 cm 1 ft Installation rules Mount the enclosure indoors at the start point of the sensor zone OR mount the enclosure up to 30 m away from the zone and use lead in cable to make the connection to the processor Use one processor and sensor cable to protect one type of surface ...

Page 2: ...ge on each side of the support posts 30 cm 12 in Cable installation example wall mount 2 44 m 8 ft 1 22 m 4 ft 1 22 m 4 ft 81 cm 2 7 ft 81 cm 2 7 ft 81 cm 2 7 ft 2 44 m 8 ft double cable pass single cable pass terminator processor sensor cable alarm and power cable Cable installation example wall mount triple cable pass 61 cm 2 ft 2 44 m 8 ft 61 cm 2 ft 61 cm 2 ft 61 cm 2 ft triple cable pass plus...

Page 3: ...Remove 6 mm of center conductor insulator Join the cables center to center and shield to shield Press the terminal block and cable into the enclosure Snap the enclosure shut splice 2 Separate the braided shield Install the center conductor and shield in one side of the terminal block and the resistor in the other splice termination termination termination splice Apply 3 or 4 wraps of electrical ta...

Page 4: ...inals accept wires from 12 to 24 AWG RELAYCONNECTIONS 30V 0 5ARELAY T5 PWRINPUT 12 48VDC T4 SUPERVISION SONALERT ALARM NC COM NO NC COM NO COM NO FLEX IN GND shield center conductor VDC VDC alarm NO alarm COM alarm NC supervision NO supervisionCOM supervisionNC sonalert NO sonalert COM Connection details DIP switch settings DIP switch calibration 1 Set switch S5 4 to ON switch calibration and swit...

Page 5: ...lower the Gain 1 level If the processor does not always alarm for the impact attack simulations raise the Gain 1 level 4 Repeat this process until the sensor always detects the simulated attacks and the NAR is acceptable Connecting the Universal Configuration Module For UCM calibration set switch S5 4 to OFF and cycle the power Switch 5 4 must be OFF to operate with UCM configuration parameters Re...

Page 6: ...6 6 P N 1077877 REV 2 ISS 19MAR19 ...

Reviews: