Bus data cables with slave terminals
You can connect up to 8 slave terminals to each bus interface. A maximum of 16 slave terminals
can be connected to the controller.
n
Always connect a slave terminal with address 1 to bus 1.
n
Evenly distribute the slave terminals among the three bus interfaces. The factory setting for
the interfaces is as follows:
– Bus 1: 6 slave terminals max.
– Bus 2: 4 slave terminals max.
– Bus 3: 6 slave terminals max.
Make sure that each slave terminal has a unique hardware address within the bus.
Data cables with slave terminals can be connected in two ways.
Connections on the printed circuit board [
n
On the front panel using RJ45 connectors
n
Internally to screw terminal 600
Bus data cables with RJ45 connectors
For trouble-free operation, please observe the following:
n
Ground the line shields of the data cables via the female RJ45 connector.
n
Only use shielded cables and shielded connection components, such as male Hirose connectors.
Bus data cable to screw terminal 600
n
Use
shield
terminals for grounding the cable shields.
n
Secure the cable with a strain relief.