MODEL ICS 12/25A
INPUT: 117 Volts AC 60Hz, 480 VA
OUTPUT: 12 Volts DC, 25 Amps
MODEL ICS 24/25A
INPUT: 117 Volts AC 60Hz, 900 VA
OUTPUT: 24 Volts DC, 25 Amps
MODEL ICS 36/20A
INPUT: 117 Volts AC 60Hz, 1120 VA
OUTPUT: 36 Volts DC, 20 Amps
MODEL ICS 48/20A
INPUT: 117 Volts AC 60Hz, 1500 VA
OUTPUT: 48 Volts DC, 20 Amps
Optional Export AC Input Ratings
100v-50Hz AC Input (Japan)
115/ 230v -50Hz AC Input (Europe) (CE)
Full Wave Phase Controlled Rectification
CONTROL:
Voltage limit:
Normal Mode 2.42 V/Cell
Gel-Cell Mode 2.33 V/Cell
Liquid Electrolyte Mode 2.62 V/Cell
Current limited to AMP rating MEAN DC.
Automatic timer starts when first stage voltage
limit reached. Proportional CV stage
timer - t/2+1 hour.
Constant voltage 2.3 V/Cell after timeout, with
Temperature Compenation.
PROTECTION:
Electronic reverse polarity. Short circuit shutdown
and current limit.
Combined Circuit Breaker and power switch on
front panel.
BATTERY TYPE & RATING (See Page 11 BTS)
ICS chargersare for use with Lead Acid Batteries of
Minimum capacity 50 AH, Gel Cell, Absorbed
Electrolyte or Liquid Electrolyte types by using the
BTS (Battery Type Switch)
DIMENSIONS: (Inches)
12.0 " WIDE, 7.0" FRONT TO BACK, 7.0" HIGH
MODEL PS 12/5
INPUT: 117 Volts AC 60Hz, 110 VA
OUTPUT: 5 Amps DC 12 Volts
MODEL PS 12/10
INPUT: 117 Volts AC 60Hz, 220 VA
OUTPUT: 10 Amps DC 12 Volts
MODEL PS 24/5
INPUT: 117 Volts AC 60Hz, 200 VA
OUTPUT: 5 Amps DC 24 Volts
MODEL PS 24/8
INPUT: 117 Volts AC 60Hz, 320 VA
OUTPUT: 8 Amps DC 24 Volts
Optional Export AC Input Ratings
100v-50Hz AC Input (Japan)
115/ 230v -50Hz AC Input (Europe)
Full Wave Phase Controlled Rectification
CONTROL:
Voltage limit:
Normal Mode 2.42 V/Cell
Gel-Cell Mode 2.33 V/Cell
Liquid Electrolyte Mode 2.62 V/Cell
Current limited to AMP rating MEAN DC.
Automatic timer starts when first stage voltage limit
reached. Proportional CV stage timer - t/2+1 hour.
Constant voltage 2.3 V/Cell after timeout, with
Temperature Compensation.
PROTECTION:
Electronic reverse polarity. Short circuit
shutdown.
and current limit.
AC Input fuse in AC Input connector
BATTERY TYPE & RATING (See Page 11 BTS)
PS chargers are for use with Lead Acid Batteries, Gel
Cell Absorbed Electrolyte or Liquid Electrolyte types by
using the BTS (Battery Type Switch)
DIMENSIONS: (Inches)
6.5" WIDE, 6.0" FRONT TO BACK, 5.25" HIGH
PROFESSIONAL SERIES
12 & 24 VOLT
SPECIFICATIONS
INDUSTRIAL/ COMMERCIAL SERIES
12,24,36,& 48 VOLT
SPECIFICATIONS
CONFORMS
TO
U.L. 1236
2