LSU80A : Load Support Unit
Operators Manual
CURRENT MEASUREMENT
5.1
CHECKING PROCEDURE
5.1.1
Voltage validation
With no load connected to the LU80A switch on and press the START push button.
Using the OUTPUT TRIM
push buttons set the output voltage to 24.0V. Note if
you press and hold either the
push buttons the adjustment will be continuous.
With the calibrated voltmeter connected to the output terminals verify that the voltage
reading is 24.0V +/- 0.2V
If the voltage is outside of tolerance follow the ADUSTMENT PROCEDURE for voltage.
5.1.2
Current validation
With a load which will give a steady 50A connected to the LU80A switch on and press
the START push button.