background image

- 5 -

I:\OFFICE\Web Site\distiller pdf\100CSCE.wpd

2.

Insertion Probes —

Straight run is not critical, but if trying to hold a precise set point, some straight run is useful,
such as 10 to 20 pipe diameters on the inlet and at least 6 diameters on the outlet.

The various probe transducers are mounted through a threaded collar (NPT/2I) or flanged tee
(BF/2I).  Other fittings and sensor designs are also available and are discussed on the Custom
Information page.  Generally the probes are sized so the tips extend  ½  to 1 inch beyond the pipe
center line when properly installed.  However, for larger pipes, the probes may extend to within

1

/

8

 of a diameter from the inside pipe wall.

Proper alignment of the sensor with flow is important; the flow direction is indicated on the
transducer tag and/or etched into the transducer.  All dual probe transducers are installed so that
the two probes are side-by-side across the fluid stream.  Never rotate the electronics box.  If this
occurs the flow switch could be damaged and/or installed misaligned with the flow direction.

For high temperature applications, the sensor and surrounding line should be well insulated.  Leave
a portion of the transducer neck un-insulated to allow heat dissipation before reaching the junction
box.

2.2 ELECTRICAL CONNECTIONS (See Figure 1)

!! CAUTION:

 Prior to opening the electrical enclosure, service personnel

shall be properly grounded with an anti-static device to prevent damage to
components within the electrical enclosure.

The input power requirement is listed on the tag on the electronics enclosure; make sure the input power
source is compatible.  The power requirement is 24 Vdc.  The DC power supply must be well filtered and
grounded and comply with all applicable E.U. standards (i.e. EN61000-4 EMC).

The input power and relay connections are made as shown in Figure 1.  Note the connector is removable for
easier insertion of the wires.  Once all connections are made, firmly push the connector back onto its base.
Be sure the wires are stress relieved sufficiently to prevent an inadvertent disconnect.

!! IMPORTANT:  In order to preserve the electromagnetic immunity levels
necessary for CE compliance the following must be strictly observed:

1.

Power must be supplied via no smaller than 24 AWG (0.25 mm

2

) twisted, shielded copper wire.

2.

Relay contacts must be connected to their load via a twisted, shielded cable of appropriate wire
gauge for the load.  A minimum of 20 AWG copper wire (0.7 mm

2

) is recommended.

3.

Both shields (power and relay wires) shall be terminated on the ground terminal of the flow switch
while leaving the opposite ends un-terminated.

4.

Maximum rated load for the relay contacts is 5 amps resistive at no more than 30 Vdc.

5.

Wiring shall be enclosed in a properly grounded, armored metallic sheath.

6.

Additionally, for TU style instruments, earth ground the flow tube, using the tube ground
connection.  Grounding is important for EMC immunity.

Summary of Contents for Rheotherm 100CS

Page 1: ...have been thus defective this warranty being expressly in lieu of all other warranties express or implied and all other obligation or liabilities on Intek s part The purchaser will assume all responsi...

Page 2: ...START 7 3 2 SWITCH SETTINGS 7 3 3 GENERAL INFORMATION 7 3 4 USE AS A LEVEL SWITCH 7 SECTION 4 MAINTENANCE 8 4 1 GENERAL MAINTENANCE 8 4 2 SPARE PARTS 8 4 3 TROUBLE SHOOTING 9 TABLE I TROUBLE SHOOTING...

Page 3: ...ndicating high and low flow conditions Key features of Rheotherm flow switches are Non intrusive flow monitoring For pipe sizes from 030 to inch flow sensing is done from outside the flow tube No movi...

Page 4: ...ive transducer Example of Example of TU probe with probe with NPT fitting flange fitting 1 3 PRECAUTIONS 1 Use proper input power Check the label on the unit for the input power requirements 2 Use rea...

Page 5: ...nstructionscoverinstallation operationandmaintenance ofRheothermflowswitches instandard configurations Any special information pertaining to your unit is covered under CUSTOM INFORMATION SECTION 6 Tim...

Page 6: ...alling CAUTION The electronics box should never be rotated for any reason Straight run for a flow switch is not a requirement particularly for flow no flow indications but for best repeatability some...

Page 7: ...el shall be properly grounded with an anti static device to prevent damage to components within the electrical enclosure The input power requirement is listed on the tag on the electronics enclosure m...

Page 8: ...0 seconds and depends on where the trip adjust is set 2 4 ADJUSTING THE TRIP POINT Adjust the flow switch trip point as follows see Figure 2 for trip potentiometer location All adjustments must be mad...

Page 9: ...O contact is open and LED color becomes red High Flow Switch The relay operation is exactly as described above When used as a high flow switch the alarm condition is considered to be when the relay i...

Page 10: ...nts gas bubbles and non solubles can result in measurement below actual flow rates Periodic checks and cleaning should be performed to insure a clean pipe or probe surface It should be part of normal...

Page 11: ...iometer clockwise until layer build up stabilizes After switch has been operating properly relay trips with flow above trip level and cannot be adjusted using SECTION 2 4 instructions Relay does not t...

Page 12: ...ewed SECTION 4 3 TROUBLE SHOOTING and have questions please call our experienced engineers for assistance In many cases we can solve a problem over the phone Please provide as complete a description a...

Page 13: ...CATION Model no Serial no Customer identification 6 2 CONFIGURATION The configuration of this unit as originally shipped from the factory Input Power 24 Vdc Line Connection 6 3 SPECIAL INSTRUCTIONS Re...

Page 14: ...terface connector Enclosure lid 24 14 Ga Flow switch electronics Check enclosure label for proper input power For VDC input connect positive to H or terminal and negative to N or Figure 1 Model 100CS...

Reviews: