SETTING / BATTERY
Battery:
-->
DisChg Protect: Enable
990 min.
Batt Test Type:
Till Batt Low
Battery:
-->
DisChg Protect: Enable
990 min.
Batt Test Type:
Short Time:
10 sec
Battery:
-->
DisChg Protect: Enable
990 min.
Batt Test Type:
Long Time:
10 min
DISCHARGE PROTECTION FUNCTION:
Enable:
UPS will shutdown automatically to protect batteries.
Shutdown will be produced according to time in minutes set below
(from 000 to 990 min.)
Disable:
Batteries protection disable. UPS will run until reach very low
battery level.
000-990:
Set time in minutes for Discharge protection function.
BATTERY TEST TYPE:
Short Time:
Battery tests will be performed during 10 seconds.
Long Time:
Battery tests will be performed during 10 minutes.
Till Battery Low:
Battery tests will be performed until reaching battery
low level.
SETTING / CALIBRATION
Calibration:
-->
Batt: 273.0 +0.0
Inv: 220.0 +0.0
Chg: 273.0 +0.0
BATT:
Calibrate value indicated in LCD for battery voltage.
INV:
Adjust the inverter output voltage. Available only in:
Online mode
Battery mode
CVCF mode
CHG:
Adjust the charger output voltage. Available only in:
Bypass mode
Online mode
ECO mode
CVCF mode
** Batteries must be disconnected from charger before making any
adjustment.