background image

The Proper Installation & Maintenance of TW-DA.

All power and signals must be de-energised before connecting any wiring, or altering any Jumpers or Dip Switches.

MOUNTING.

(1)

Mount in a clean environment in an electrical cabinet on DIN or EN rail.

(2)

Do not subject to vibration or excess temperature or humidity variations.

(3)

Avoid mounting in cabinets with power control equipment.

(4)

To maintain compliance with the EMC Directives, the TW-DA must be mounted in a fully enclosed, metal, electrical
cabinet. The cabinet must be properly earthed, with appropriate input / output entry points, cabling and filtering.

WIRING.

(1)

All cables should be good quality overall screened INSTRUMENTATION CABLE with the screen earthed at one
end only.

(2)

Signal cables should be laid a minimum distance of 300mm from any power cables.

(3)

For 2 wire current loops and 2 wire voltage signals or 2 wire current signals, Austral Standard Cables B5102ES
is recommended. For 3 wire transmitters Austral Standard Cables B5103ES is recommended.

(4)

It is recommended that you do not ground current loops and use power supplies with ungrounded outputs.

(5)

Lightning arrestors should be used when there is a danger from this source.

(6)

Refer to diagrams for connection information.

COMMISSIONING.

(1)

Once all the above conditions have been carried out and the wiring checked apply power to the TW-DA
loop and allow five minutes for it to stabilize.

(2)

Take a low (approx. 10%) and high (approx. 90%) reading of the variable being measured by the transducer
supplying the signal to the TW-DA, and ensure that this agrees with the level being indicated by the PLC or
indicator, etc., that the TW-DA is connected to. Adjust for any difference using the Zero & Span Pots in the top
of the TW-DA enclosure with a small screwdriver, until the two levels agree. (Clockwise to increase the output
reading and anticlockwise to decrease the output reading.)

MAINTENANCE.

(1)

Repeat (2) of Commissioning.

(2)

Do it regularly - at least once every 12 months.

13.07-4

TW-DA 010212.p65

Intech 

INSTRUMENTS LTD

ww w . i n t e c h . c o . n z

Christchurch Ph: +64 3 343 0646

Auckland Ph: 09 827 1930
Email: 

[email protected]

Summary of Contents for TW-DA

Page 1: ...erter Quality Assurance Programme The modern technology and strict procedures of the ISO9001 Quality Assurance Programme applied during design development production and final inspection grant the long term reliability of the instrument 13 07 1 Ordering Information TW DA X Standard Unit 4 Digital Inputs 4 20mA Output TW DA Special Range Calibration D AO Ordering Examples TW DA 6 A TW DA 6 Digital ...

Page 2: ...nstitute guaranteed properties and is not intended to affirm the suitability of a product for a particular application Due to ongoing research and development designs specifications and documentation are subject to change without notification Regrettably omissions and exceptions cannot be completely ruled out No liability will be accepted for errors omissions or amendments to this specification Te...

Page 3: ... gives 64 output steps 1 59 per step Use B32 for MSB B1 for LSB MSB Most significant bit LSB Least significant bit Calibrating the TW DA to the Required Ranges Note To range the unit select the output range first 1 With no digital inputs active use the ZERO Pot to calibrate the 0 point Note When adjusting 0 10V or 0 20mA ensure you do not overwind the ZERO Pot A slight offset may be left Wind the ...

Page 4: ...l Standard Cables B5103ES is recommended 4 It is recommended that you do not ground current loops and use power supplies with ungrounded outputs 5 Lightning arrestors should be used when there is a danger from this source 6 Refer to diagrams for connection information COMMISSIONING 1 Once all the above conditions have been carried out and the wiring checked apply power to the TW DA loop and allow ...

Reviews: